Permit Information
Permit NumberBLD98-01052
StatusExpired
Name IDAHO ICE WORLD (SHELL)
Site Address 7072 S EISENMAN RD
Project NameIDAHO ICE WORLD-SHELL/CORE
Customer Number 
ePlanReviewNo
Description
IDAHO ICEWORLD (SHELL AND CORE PERMIT)* TO CONSTRUCT A NEW 92,150 SQ. FT., TWO STORY SHELL & CORE BUILDING FOR FUTURE ASSEMBLY USES. THE PORTION OF THIS BUILDING THAT WILL ENCLOSE THE FUTURE ICE RINKS WILL BE CONSTRUCTED WITH A "BEHLEN" PREENGINEERED STEEL STRUCTURE WITH METAL ROOF AND EXTERIOR SKIN. THE CENTER CORE WILL BE CONSTRUCTED OF STRUCTURAL STEEL FRAMING, CONCRETE MASONRY WALLS, METAL AND CONCRETE SECOND FLOOR DECK AND METAL ROOF SYSTEM. THE FUTURE RETAIL SALES AREAS OF THE BUILDING ARE CONSTRUCTED OF STRUCTURAL STEEL FRAME, EXTERIOR NONBEARING STEEL STUDS WALLS AND A METAL ROOF SYSTEM. THIS BUILDING IS WILL BE FULLY FIRE SPRINKLED. THE SPRINKLERS ARE BEING USED FOR BUILDING AREA INCREASES. THIS IS A SHELL AND CORE PERMIT ONLY AND NO OCCUPANCY IS ALLOWED UNDER THIS PERMIT. SEPARATE TENANT IMPROVEMENT PERMITS WILL BE REQUIRED TO FINISH THIS BUILDING FOR OCCUPANCY. ALL CONSTRUCTION MUST BE DONE PER THE APPROVED PLANS AND ATTACHED REQUIREMENT LIST. CUP98-0050/DRH98-0035/JCM PC#242-98. JCM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary (BLD)  7/30/2003 DONE
DOC - Permit Expired1/12/20011/12/20011/12/2001APASS
DetailsJim Storey
Added by Inspector: 301 On 1/12/2001 9:27:40 AM
Receive PAYMENT IN FULL  9/3/1999
CHANGE STATUS TO (F)  8/11/1999
Fee Review-notes5/4/1999 5/4/1999
1,205,950.00 additional value..permit bld98-1484 was 373,024.00 less value I took 373,024.00 from 1,205,950.00 = 832,926.00 and added that to this permit
(F) Reprint permit  5/4/1999
INSP-Final Inspection12/4/199812/4/199812/4/1998PPART
DetailsRick Jackson
temp occ approved for 2nd floor; c/n issued
INSP-Final Inspection12/3/199812/3/199812/3/1998APART
DetailsRick Jackson
walk through for final occupancy - work not completed
INSP-Final Inspection12/1/199812/1/199812/1/1998PPART
DetailsRick Jackson
checked progress for final
SUPER- Supervisor's review11/30/199811/30/199811/30/1998
both rinks approved for temp. systems work to be retested this week. needs to shut down units with duct detectors.
INSP-Final Inspection11/30/199811/30/199811/30/1998PPART
DetailsRick Jackson
checked progress for final with George S.
INSP-Final Inspection11/25/199811/25/199811/25/1998PPART
DetailsRick Jackson
temp occ approved for first floor only
INSP - Framing/Rough-in11/24/199811/24/199811/24/1998 PART
DetailsRuss Owen
/ / 407 - PARTIAL INSPECTION TO CHECK FOR ITEMS TO TO OBTAIN TEMP OC F
INSP-Final Inspection11/24/199811/24/199811/24/1998PFAIL
DetailsRick Jackson
alarms not complete; sprinklers okay
INSP - Conference11/23/199811/23/199811/23/1998 PART
DetailsRuss Owen
/ / 407 - OUT TO JOB SITE FOR PROGRESS CHECK.
INSP-Final Inspection11/20/199811/20/199811/20/1998PPART
DetailsRick Jackson
temp occ approved for rink "a" only for the weekend
Print Occupancy Form  11/20/1998
INSP-Sprinkler Rough-in/Hydro11/19/199811/19/199811/19/1998PFAIL
DetailsRick Jackson
small leak, will retest on 11/20
INSP - Conference11/19/199811/18/199811/19/1998 PART
DetailsRuss Owen
/ / 407 - MEET WITH THE APPROPRIATE PARTIES TO LOOK AT THE POSSIBILITY
INSP-Final Inspection11/18/199811/18/199811/18/1998PFAIL
DetailsRick Jackson
rink "a" occ request met with project manager to discuss requirements for opening; all issues on c/n will be ready?
INSP - Final11/13/199811/16/199811/16/1998PPART
DetailsRuss Owen
MEET WITH PHIL TO SCHEDUAL TIME FOR TEMP OC AT RINK A.
INSP - Framing/Rough-in11/10/199811/10/199811/10/1998APART
DetailsRuss Owen
meet with architect and other trades for profit meeting.
INSP-Conference11/10/199811/10/199811/10/1998APART
DetailsRick Jackson
smoke dampers in floors; alarm testing and sprinkler tests will be done on 11/20;
INSP-Conference11/4/199811/4/199811/4/1998 PART
DetailsMike Kinnear
Notice of 1 EQ brace in concession need stress load check. Higher temp heads in Zamboni and compressor rooms, etc. FDC shall be clear and straight access from obstruction. Shall have QR heads in "light hazard occupancies" no matter what the system is designed for!
SUPER- Supervisor's review11/3/199811/2/199811/2/1998
alarm plans not quite complete but won't hold up temp. Floyd will review facility and give me an update.
INSP-Sprinkler Rough-in/Hydro10/27/199810/27/199810/27/1998APART
DetailsRick Jackson
reviewed FDC location and continued with rough-in
SUPER- Supervisor's review10/26/199810/26/199810/26/1998
shell is progressing exterior to be cleaned up, no constuction materials left inside or out for temp occ.
INSP-Conference10/26/199810/26/199810/26/1998APART
DetailsRick Jackson
profit meeting for partial opening scheduled for 11/13 - gave requirements to contractor
INSP-Sprinkler Rough-in/Hydro10/21/199810/21/199810/21/1998PPART
DetailsRick Jackson
DOUG ###-#### upper floor has main and branch lines installed - no drops for heads in yet. peak heads are 26 inches from peak - okay. told doug a hydro test is still needed for all wet. window heads all installed
SUPER- Supervisor's review10/12/199810/12/199810/12/1998
gary himes needs to give us info on sprinkler heads in certain areas. this is good example of plan needs to be complete prior to inspection.
INSP-Sprinkler Rough-in/Hydro10/12/199810/12/199810/12/1998APART
DetailsRick Jackson
requested info from designer about heads on 2nd floor within 2 feet of peak - awaiting info.
INSP-Final Inspection10/6/199810/6/199810/6/1998PPART
DetailsRick Jackson
doug ###-#### not a final - hydro test of first floor locker/bathroom/zamboni areas - okay. heads not cut, rehydro after heads are cut (hard lid within the above areas)
SUPER- Supervisor's review10/5/199810/5/199810/5/1998
hydro tests these tests are time consuming about 1 and half hours.
INSP-Sprinkler Rough-in/Hydro10/5/199810/5/199810/5/1998APART
DetailsRick Jackson
early rough-in of shell, sway bracing not installed yet;
INSP-Sprinkler Rough-in/Hydro9/17/19989/18/19989/18/1998APASS
DetailsRick Jackson
phil ###-#### rink a & b dry system; antifreeze loop and hose stations okay for hydro. rest of wet and dry canopy not installed.
INSP-Conference9/17/19989/17/19989/17/1998APART
DetailsRick Jackson
discussed hydro testing dry system/antifreeze system in arenas. will test on 9/18
INSP-Supply line flush9/4/19989/4/19989/4/1998APASS
DetailsRick Jackson
underground flush and hydro okay
INSP - Framing/Rough-in9/1/19989/1/19989/1/1998PPART
DetailsRuss Owen
went out reviewed plans for tenant t-i.
INSP - Framing/Rough-in8/7/19988/7/19988/7/1998APART
DetailsRuss Owen
08/07/98 407 - partial inspection,only.
INSP - Framing/Rough-in8/7/19988/7/19988/7/1998 PART
DetailsJim Storey
/ / 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED fire stopping of floor assemb stud framing at gable weld detail west end expantion foint need fire sto detail not as per
INSP - Framing/Rough-in8/6/19988/6/19988/6/1998PCANC
DetailsRuss Owen
unable to do inspection this day.
90 day tracking............. 4/17/19987/16/1998 PEND
(F) Reprint permit  6/4/1998
Issue PAID IN FULL permit  6/3/1998
Inspection Record Card- Bld  6/2/1998
PLANS/APPL TAKEN TO FRONT DESK  6/2/1998 PASS
Plan assigned to (JCM)4/21/1998 6/1/1998 PASS
DetailsJohn Menard
Routing Off Site - STRUCTURAL5/20/1998 6/1/1998 PASS
RECEIVED APPROVAL FOR RESUBMITTALS FROM CH2MHILL.
Routing - PLAN CHECK5/26/1998 6/1/1998 PASS
Plan Reviewer's activity  5/27/1998 PEND
FAXED CHERYL PEARSE AT HUMMEL'S OFFICE WITH REQUESTED INFORMATION REQUIRED BASED ON THE RESUBMITTED PLANS.
Plan resubmittals received  5/27/1998 PASS
RECIEVED RESUBMITTALS FROM HUMMEL AND SENT THEM TO JOHN MENARD - RESUBMITTALS REVIEWED AND APPROVED - JCM
Plan resubmittals requested  5/27/1998 PEND
Routing - PLAN CHECK5/12/1998 5/22/1998 PEND
Routing - FIRE5/22/1998 5/21/1998 PASS
Plan resubmittals received  5/19/1998
RECIEVED RESUBMITTALS FROM HUMMEL SENT TO JOHN MENARD
Routing Off Site - STRUCTURAL4/22/1998 5/15/1998
ONE SET OF PLNS AND SPECS SENT TO CH2MHILL. RESULTS OF REVIEW RETURNED, RESUBMITAL REQUIRED.
Plan resubmittals received  5/15/1998 PEND
Plan resubmittals received  5/15/1998 PEND
RECEIVED RESUBS FROM HUMMEL FOWARDED SAME TO JOHN MENARD.
Routing - FIRE5/6/1998 5/11/1998 FAIL
Routing - PLAN CHECK4/22/1998 5/5/1998 PEND
ONE SET OF PLANS AND SPECS TO JOHN MENARD AND ONE SET OF PLANS TO PUBLIC WORKS. DAR
Routing - PLUMBING5/4/1998 5/5/1998 PASS
Plan resubmittals requested  5/5/1998 PEND
E-MAILED CHERYL PEARSE AT HUMMEL ARCHITECTS WITH A COPY OF THE CORRECTION LIST AND FOLLOWED WITH A MAILED COPY.
Routing - PLANNING5/4/1998 5/4/1998 PASS
CROSS REFERENCE FILES: CUP97-100 AND CUP98-035 CROSS REFERENCE DRH97-0236 AND DRH98-0050
Routing - PLANNING4/24/1998 4/30/1998 PASS
0NE SET OF PLANS TO PLANNING AND ZONING ONE SET TO JOHN MENARD. x-ref. DRH97-0236 and DRH98-0050
Routing - PUBLIC WORKS4/22/1998 4/24/1998 PASS
ONE SET OF PLANS AND SPECS TO PUBLIC WORKS AND ONE SET TO JOHN MENARD.
Routing - PLAN CHECK4/17/1998 4/22/1998 PEND
Plans ACCEPTED BY PLAN CHECK  4/22/1998 PEND
ON 17APRIL98 PLANS AND SPECS WERE RECEIVED BUT NO SHOP DRAWINGS WERE RECEIVED PLANS WERE PUT ON HOLD BECAUSE NO SHOP DRAWINGS WERE RECEIVED. SHOP DRAWINGS RECEIVED 4/21/98. DAR
Plan assigned to (MYS)4/17/1998 4/21/1998
DetailsMarlene Southard
Recd Pcfee & Taken To Pln CK  4/17/1998 PEND
Application received  4/17/1998