Permanent Occupancy | | 8/5/1999 | 8/5/1999 | | DONE |
|
|
|
|
INSP - Final | 8/3/1999 | 8/5/1999 | 8/5/1999 | A | PASS |
Jim Storey
|
|
|
08/05/99 301 - ###-#### BRIAN
|
INSP-Final Inspection | 8/3/1999 | 8/5/1999 | 8/5/1999 | A | PASS |
Rick Jackson
|
|
|
10:00 AM TALKED TO RICK. BRIAN ###-#### occ approved
|
Permanent occupancy | | | 8/5/1999 | | PASS |
|
|
|
Perm. Occ. Cert. #7862 issued 8-5-99 to Whiteman Industries.
|
INSP-Conference | 8/3/1999 | 8/3/1999 | 8/3/1999 | A | PART |
Rick Jackson
|
|
|
requirements for final sign-off; set up final inspection for 8/5
|
INSP - Final | 7/21/1999 | 7/27/1999 | 7/27/1999 | A | FAIL |
Jim Storey
|
|
|
07/27/99 301 - c/n
|
INSP-Final Inspection | 7/21/1999 | 7/27/1999 | 7/27/1999 | A | FAIL |
Rick Jackson
|
|
|
BRIAN ###-#### LIFE SAFETY at 10:00 as per rick j. fire lanes
|
Code Occupancy Approval | | | 7/26/1999 | | PASS |
|
|
|
ALL CONDITIONS OF DRH97-0173 HAVE BEEN MET, FINAL OCCUPANCY SIGNED OFF AND BOND RELEASE
|
Code Occupancy Approval | | | 7/21/1999 | | |
|
|
|
Final requested by Brian Henderson ###-####
|
SUPER- Supervisor's review | 4/1/1999 | 4/1/1999 | 4/1/1999 | | |
|
|
|
ready for final once spriklers clear and sign offs obtained.
|
SUPER- Supervisor's review | 2/16/1999 | 2/16/1999 | 2/16/1999 | | |
|
|
|
dave l. not finaled yet. waiting for spray booth info
|
SUPER- Supervisor's review | 2/5/1999 | 2/5/1999 | 2/5/1999 | | |
|
|
|
mechanical issues on line equipment settled and we can clear the issue of owner installed portable equipment
|
INSP-Conference | 1/26/1999 | 1/26/1999 | 1/26/1999 | | PART |
Rick Jackson
|
|
|
/ / 409 - SPRAY BOOTH APPROVED FOR USE
|
SUPER- Supervisor's review | 1/26/1999 | 1/26/1999 | 1/26/1999 | | |
|
|
|
marlene dave lightfoot jim storey myself ment concerning permit requirment for paint line installed from out of state. it is portable equip and can be removed so we permitted installation on the building permit and gas by local contractor
|
INSP-Conference | 1/25/1999 | 1/25/1999 | 1/25/1999 | A | PART |
Rick Jackson
|
|
|
discussed resubmittal on booth - they will submit info for the booth operation
|
INSP-Conference | 1/22/1999 | 1/22/1999 | 1/22/1999 | P | FAIL |
Rick Jackson
|
|
|
discussed with VP the paint booth operation. placed not to occupy sticker on unit and issued c/n to not to use the paint booth until approved.
|
Print Occupancy Form | | | 1/22/1999 | | |
|
|
|
|
Inspection Record Card- Bld | | | 1/22/1999 | | |
|
|
|
|
INSP-Final Inspection | 1/20/1999 | 1/21/1999 | 1/21/1999 | A | FAIL |
Rick Jackson
|
|
|
mike -###-#### fn fire insp exsisting paint booth inspection - unit removed from old shop and installed in new fab building: doesn't comply with NFPA or UFC - will discuss with plan check and inspections about shutting it down
|
SUPER- Supervisor's review | 1/20/1999 | 1/20/1999 | 1/20/1999 | | |
|
|
|
dave lightfoot working with storey to reconcile problem of lack of permits and fees on line equipment per lightfoots c/n
|
SUPER- Supervisor's review | 1/12/1999 | 1/12/1999 | 1/12/1999 | | |
|
|
|
confusion on fees and mec inspection. dave lightfoot is getting with drake mechanical to see what the problem was. dave is to fill me in and we will respond to the owner.
|
INSP-Alarm Testing | 1/12/1999 | 1/12/1999 | 1/12/1999 | A | PASS |
Rick Jackson
|
|
|
tested preaction system only. okay per plans. still need knox box, perm address, label annunciator
|
SUPER- Supervisor's review | 1/11/1999 | 1/11/1999 | 1/11/1999 | | |
|
|
|
reviewed paint equipment installed with owner. inspection needed to take place on gas lines. Dave lightfoot will check with mec contractor to find out why inspection was not called for
|
INSP - Final | 12/28/1998 | 12/29/1998 | 12/29/1998 | A | PART |
Jim Storey
|
|
|
12/29/98 301 - SCLG-OK SUSPENDED CEILING at main entry
|
INSP-Conference | 12/29/1998 | 12/29/1998 | 12/29/1998 | A | PART |
Rick Jackson
|
|
|
checked status for final; recheck preaction system functions
|
INSP - Framing/Rough-in | 12/21/1998 | 12/22/1998 | 12/22/1998 | A | PART |
Jim Storey
|
|
|
12/22/98 301 - TCO -TEMP C OF O ISSUED need follow up in 90 days
|
Temporary occupancy | | | 12/22/1998 | | PASS |
|
|
|
Temp. Occ. Cert. #3763 issued 12-22-98 to Whiteman Industries.
|
INSP - Final | 12/21/1998 | 12/21/1998 | 12/21/1998 | | NR |
Jim Storey
|
|
|
12/21/98 301 - jeff ###-#### temp occ insp
|
INSP - Final | 12/18/1998 | 12/21/1998 | 12/21/1998 | A | NR |
Jim Storey
|
|
|
12/21/98 301 - jeff ###-#### temp occ insp
|
INSP-Final Inspection | 12/18/1998 | 12/21/1998 | 12/21/1998 | A | PART |
Rick Jackson
|
|
|
12/21/98 409 - JEFF...###-#### test preaction; perm address; NFPA 72 ansd central station certificate
|
INSP-Final Inspection | 12/18/1998 | 12/18/1998 | 12/18/1998 | P | FAIL |
Rick Jackson
|
|
|
12/18/98 409 - sprinklers not complete in office area
|
INSP - Framing/Rough-in | 12/15/1998 | 12/15/1998 | 12/15/1998 | P | PART |
Jim Storey
|
|
|
12/15/98 301 - SCLG-OK SUSPENDED CEILING
|
Temporary occupancy | | | 12/15/1998 | | PASS |
|
|
|
Temp. Occ. cert. #3759 issued 12-15-98 to Whiteman Industries, portion of warehouse only.
|
INSP - Final | 12/14/1998 | 12/14/1998 | 12/14/1998 | P | PART |
Jim Storey
|
|
|
12/14/98 301 - TEMP OK FOR GRID LINE 1 THRU H IN F-1 OCC ONLY.
|
INSP-Final Inspection | 12/14/1998 | 12/14/1998 | 12/14/1998 | P | PART |
Rick Jackson
|
|
|
temp occ approved for fab area grid lines a-h only. tested alarms, sprinklers, etc. preaction system not complete. office areas not ready
|
Code Occupancy Approval | | | 12/10/1998 | | FAIL |
|
|
|
REQUEST FOR TEMPORARY OCCUPANCY, BOND POSTED WITH CATHY FOR OVER $7,000 TO COMPLETE LANDSCAPE PER DR, I OKED THE AMOUNT AND SIGNED OFF FOR TEMPORARY OCCUPANCY.
|
INSP-Conference | 12/8/1998 | 12/8/1998 | 12/8/1998 | A | PART |
Rick Jackson
|
|
|
discussed requirements for temp occ with contractor and owners
|
INSP - Final | 12/7/1998 | 12/8/1998 | 12/8/1998 | A | NR |
Jim Storey
|
|
|
12/08/98 301 - conf for temp occ. work in progess
|
Code Occupancy Approval | | | 12/4/1998 | | |
|
|
|
Temporary requested by Casey ###-####. Contact either Casey or Joel with questions.
|
INSP-Conference | 12/2/1998 | 12/2/1998 | 12/2/1998 | P | PART |
Rick Jackson
|
|
|
to determine requirements for moving in equipment and partial occupancy. off-site monitoring; extinguishers; tape on sprinkler heads; pre-action system plans; knox box; test alarms
|
INSP - Framing/Rough-in | 11/5/1998 | 11/6/1998 | 11/6/1998 | A | PART |
Tom Arcoraci
|
|
|
11/06/98 408 - JEFF--###-#### ok to cover one side of office area
|
INSP-Final Inspection | 11/5/1998 | 11/6/1998 | 11/6/1998 | P | PART |
Joe Tawney
|
|
|
11/06/98 406 - MIKE- ###-#### FIRE INSP OK ON ABOVE GROUND HYDRO TEST EXC FDC PIPING OK ON RI EXC OBSTR HEADS
|
INSP - Framing/Rough-in | 11/2/1998 | 11/2/1998 | 11/2/1998 | A | PART |
Jim Storey
|
|
|
11/02/98 301 - framing ok on a3 occ
|
INSP - Framing/Rough-in | 10/30/1998 | 10/30/1998 | 10/30/1998 | P | FAIL |
|
|
|
10/30/98 333 - ###-####
|
INSP-Supply line flush | 10/22/1998 | 10/22/1998 | 10/22/1998 | P | PASS |
Rick Jackson
|
|
|
underground flush okay
|
INSP-Sprinkler Rough-in/Hydro | 10/13/1998 | 10/13/1998 | 10/13/1998 | A | PART |
Rick Jackson
|
|
|
underground hydro okay. sway bracing needed as most areas not complete. okay to cover in 1st floor of bathroom areas (fab area)
|
INSP - Framing/Rough-in | 10/12/1998 | 10/12/1998 | 10/12/1998 | P | PART |
Jim Storey
|
|
|
10/12/98 301 - JEFF ###-#### FRAM-OK FRAMING ì
|
INSP-Sprinkler Rough-in/Hydro | 9/24/1998 | 9/24/1998 | 9/24/1998 | A | PART |
Rick Jackson
|
|
|
checked approved plans and general area, recheck riser piping for hangers
|
Plan resubmittals received | | | 9/15/1998 | | |
|
|
|
RESUBS OK'D BY DAVE LIGHTFOOT..HE WILL TAKE COPY TO JOB SITE..OTHER COPY WENT TO RECORDS
|
INSP - Concrete | 9/1/1998 | 9/1/1998 | 9/1/1998 | | PASS |
Jim Storey
|
|
|
09/01/98 301 - after lunch early afternoon terry ###-#### 2nd lift massonary restrooms ok
|
INSP - Concrete | 8/28/1998 | 8/28/1998 | 8/28/1998 | A | CANC |
Russ Owen
|
|
|
requires special insp. 08/28/98 407 - first thing in the morning terry ###-####
|
INSP - Concrete | 8/25/1998 | 8/26/1998 | 8/26/1998 | A | FAIL |
Jim Storey
|
|
|
08/26/98 301 - terry ###-#### CORR-CORREC-CALL FOR REINSP WHEN COMPLETED arch. and engineer of record submit info. to resolve 4 idems posted on site.
|
90 day tracking............. | | 4/28/1998 | 7/27/1998 | | PEND |
|
|
|
|
(F) Reprint permit | | | 7/13/1998 | | |
|
|
|
|
Print Occupancy Form | | | 7/10/1998 | | |
|
|
|
|
Inspection Record Card- Bld | | | 7/10/1998 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 7/10/1998 | | |
|
|
|
|
Routing - PLAN CHECK | 6/23/1998 | | 7/9/1998 | | PASS |
|
|
|
|
Plan assigned to (JCM) | 5/20/1998 | | 7/9/1998 | | PASS |
John Menard
|
|
|
|
Plan resubmittals received | | | 7/9/1998 | | PASS |
|
|
|
|
Telephone call | | | 7/9/1998 | | |
|
|
|
CALL BILL MATTER PERMIT READY
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/9/1998 | | PASS |
|
|
|
|
Plan resubmittals requested | | | 7/6/1998 | | PEND |
|
|
|
FAXED BILL MATTER A REQUEST FOR AN ADDITIONAL RESUBMITTAL.
|
Routing - FIRE | 7/2/1998 | | 7/2/1998 | | PASS |
|
|
|
allowed permit approval pending delayed submittals on paint booths, haz mat plan, lp tank, and fire alarms
|
Routing - PUBLIC WORKS | 6/23/1998 | | 6/23/1998 | | PASS |
|
|
|
|
Plan Review Completed(1st rev) | | | 6/19/1998 | | FAIL |
|
|
|
UBC Public WKS and UFC fail
|
Routing - FIRE | 6/11/1998 | | 6/19/1998 | | FAIL |
|
|
|
need info on paint booth, powder coat booth and haz mat. alarm plans needed for delayed submittal
|
Plan resubmittals requested | | | 6/11/1998 | | PEND |
|
|
|
MAILED BILL MATTER A COPY OF THE CORRECTION LIST.
|
Routing - PLAN CHECK | 5/27/1998 | | 6/11/1998 | | PEND |
|
|
|
|
Routing Off Site - STRUCTURAL | 6/2/1998 | | 6/5/1998 | | PEND |
|
|
|
|
Plan resubmittals received | | | 5/29/1998 | | |
|
|
|
RECIEVED RESUBMITTALS AND SENT THEM TO JOHN MENARD
|
Telephone call | | | 5/28/1998 | | PASS |
|
|
|
TALKED TO BILL MATTER TO VERIFY THAT PLANS ARE READY
|
Routing - PUBLIC WORKS | 5/26/1998 | | 5/27/1998 | | FAIL |
|
|
|
MANUFACTURING PROCESS CLEANER FLOW INFO OF BE PROVIDED TO WALT BAUMGARTNER AND NECESSARY TO COMPLETE FEES. PER BAD
|
Routing - PLUMBING | 5/19/1998 | | 5/22/1998 | | PASS |
|
|
|
|
Plan Reviewer's activity | | | 5/22/1998 | | PEND |
|
|
|
FAXED BILL MATTER A COPY OF THE STRUCTURAL PLAN REVIEW COMMENTS TO FORWARD TO THE ENGINEER OF RECORD TO RESPOND.
|
Plan assigned to (MYS) | 4/28/1998 | | 5/20/1998 | | |
Marlene Southard
|
|
|
|
Routing - PLANNING | 5/13/1998 | | 5/19/1998 | | PASS |
|
|
|
drh97-0173
|
Routing Off Site - STRUCTURAL | 5/7/1998 | | 5/18/1998 | | PEND |
|
|
|
SENT TO ATWOOD HINZMAN AND JONES RECEIVED COMENTS FROM RILEY MAHAFFEY, SECOND REVIEW REQUIRED. 5/1998 DAR
|
Routing - PUBLIC WORKS | 5/7/1998 | | 5/13/1998 | | FAIL |
|
|
|
INCOMPLETE LEGAL DESCRIPTION, INCOMPLETE SITE PLAN, PROOF OF LEGAL LAND DIVISION, REQUIRES DRAINAGE PLAN APPROVAL PER JRICH MANUFACTURING PROCESS CLEANER FLOW INFO TO BE PROVIDED TO WALT BAUMGARTNER AND NECESSARY TO COMPLETE FEES PER BDUGGER.
|
Plans ACCEPTED BY PLAN CHECK | | | 5/7/1998 | | PEND |
|
|
|
RECEIVED PLANS AS REQUESTED. NEED SITE PLAN DEPICTING SITE UTILITIES, RECEIVED SAME ON 5/6/98
|
Routing - PLAN CHECK | 4/28/1998 | | 5/7/1998 | | PEND |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 4/28/1998 | | PEND |
|
|
|
|
Application received | | | 4/28/1998 | | |
|
|
|
|