Permit Information
Permit NumberBLD98-02788
StatusFinaled
Name HILLCREST RETIREMENT CENTER
Site Address 1093 S HILTON ST
Project Name 
Customer Number 
ePlanReviewNo
Description
To repair and protect all penetrations of the existing one-hour fire-resistive corridor walls throughout the Hillcrest Retirement home facility and to install a new listed 1-hour rated suspended ceiling assembly with appropriate smoke/fire dampers installed to maintain the integrity of the assembly as well as appropriate protection of light fixture's, speakers, etc. as called out in the approved installation instructions for the assembly. An alarm detection system compatible for monitoring & activation of all smoke detection, sprinkler system flow notification, etc. as monitored by the Fire Dept. shall be in installed in conjunction with the upgrade. All per architects code analysis upgrade report of August 1997, on file. Project is being completed ahead of original time frame agreement. Note: This facility has been fully sprinkled for 1-hour substitution. PC#98-635 / drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Letter of compliance  2/14/2000 DONE
Letter of Compliance #15232 issued 2-14-00.
FIRE-Final Inspection9/30/199910/4/199910/4/1999ACANC
DetailsJoe Tawney
Scheduled by a contractor via Hello! on 09/30/1999 at 14:54:40. Contact: ###-####.//FIRE PREVIOUSLY OK'D//
BLD-Final10/4/199910/4/199910/4/1999APASS
DetailsCarl Dependahl
PER CARL PASSED FOR FN -CARD TO OWNER'S REP
BLD-Conference9/17/19999/17/19999/17/1999 PART
KEEP C/N, INSTALL RATED HATCH
INSP - Final9/9/19999/10/19999/10/1999PFAIL
DetailsCarl Dependahl
add rated access hatch, etc.c/n
INSP-Final Inspection9/9/19999/9/19999/9/1999PPASS
DetailsJoe Tawney
ok for certificate of occupancy
INSP-Alarm Testing8/27/19998/30/19998/30/1999APART
DetailsJoe Tawney
09/01/99 406 - ALARM TEST OK SIGNED TEMP
INSP-Conference8/17/19998/17/19998/17/1999 PART
DetailsJoe Tawney
/ / 406 - CONF WITH DOYLE ON ALARM SYSTEM
INSP - Framing/Rough-in5/5/19995/6/19995/6/1999APART
DetailsCarl Dependahl
05/06/99 340 - OK TO DROP TILES AT 1HR GRID].
INSP - Framing/Rough-in5/4/19995/5/19995/5/1999AFAIL
DetailsRuss Owen
05/05/99 407 - 1hour ceiling tile ,light can details no good.not per det
INSP - Framing/Rough-in4/27/19994/28/19994/29/1999ANR
DetailsCarl Dependahl
04/28/99 340 - need data for firestops at 1hr grid
INSP - Framing/Rough-in4/20/19994/21/19994/19/1999AFAIL
DetailsCarl Dependahl
04/21/99 340 - phone is [3454460].; need install tents at grid, ok to co
INSP - Framing/Rough-in3/30/19993/30/19993/30/1999 PART
DetailsCarl Dependahl
/ / 340 - VERBAL C/N , NEED LISTING OR DETAIL FOR LITES, FIRESTOP PENE
INSP - Framing/Rough-in3/29/19993/29/19993/29/1999 PART
DetailsCarl Dependahl
/ / 340 - OK TO DROP TILES AT DINING, NEED DESIGN FOR TENTS AT LITES E
INSP-Conference3/24/19993/26/19993/26/1999APART
DetailsCarl Dependahl
doyle ###-#### conference only, need 1hr grid.
INSP-Conference3/24/19993/26/19993/26/1999APART
DetailsJoe Tawney
03/26/99 406 - CONFR ON S/F DAMPERS AND DETECTION
INSP-Conference3/26/19993/26/19993/26/1999 PASS
DetailsCarl Dependahl
03/26/99 340 - doyle ###-#### conference only met arch onsite, discussed fire/smoke dampers, 1hr grid, need listing fo
INSP - Framing/Rough-in3/24/19993/24/19993/24/1999 PART
DetailsCarl Dependahl
/ / 340 - NO INSP, CONF ONLY; NEED TO SET UP APPT RE DAMPERS
Issue PAID IN FULL permit  12/16/1998
Issue PAID IN FULL permit  12/16/1998
Issue PAID IN FULL permit  12/16/1998
Plan assigned to (DRS)9/17/1998 11/24/1998 PASS
DetailsDan Stuart
11/24/98 12:56:27 DRS - this action updated by action script from <<>> in Case No. BLD98-2788
Print Occupancy Form  11/24/1998
Inspection Record Card- Bld  11/24/1998
PLANS/APPL TAKEN TO FRONT DESK  11/24/1998 PASS
TO FRON DESK TO PROCESS FOR ISSUANCE OF PERMIT.
Routing - PLAN CHECK11/23/1998 11/24/1998 PASS
PROCESSING FOR ISSUANCE OF PERMIT.
Routing - FIRE11/19/1998 11/23/1998 PASS
type of damper in central core still not clear.....may need additional smoke detectors
Routing - PLAN CHECK10/26/1998 11/18/1998 PEND
Inserted resubmittals & assembled copies of U.L. & Evaluation reports referenced by architect. Plans recirculated to Fire Dept for review.
Plan resubmittals received  11/16/1998
RECEIVED THREE REVISED COPIES OF SHEETS T, 1,2,3,4,5, ROUTED TO DAN S. KMM
Plan Review Completed(1st rev)  10/24/1998 FAIL
ubc and ufc
Routing - FIRE10/23/1998 10/23/1998 FAIL
smoke dampers not right
Telephone call  10/22/1998 PEND
Call to Pat McKeegan, architect of record to discuss concerns about the designs for the constructed assemblies proposed to be built for protection of the duct penetrations at the new proposed ceiling. Pat is working on new details as we speak and says that his mechanical personell were having problems finding approved smoke/fire dampers. I asked Pat to stop by and review the details with me today when he came in for a 3 p.m. meeting.
Meeting  10/22/1998
Reviewed a listed Smoke/Fire Damper assemly listed by Ruskin Mfg. I gave him a copy of the information I got off of the internet. If it checks out for him he will present the new design shortly so the permit can be processed.
Plan resubmittals requested  10/22/1998
Requested clarification from architect concerning the protective system to be used at the duct penetrations within the new 1-hour rated corridor system, when we met at 4:00 p.m. this afternoon.
Routing - PLAN CHECK10/21/1998 10/22/1998 PEND
Met with architect to discuss concerns and ask for clarification. Gave him source to research for smoke/fire dampers for suspended ceiling installation. Forwarding paln to Fire Dept. for review.
Print Pending Permit.LaserJet4  10/22/1998 PEND
Routing - PLAN CHECK9/17/1998 10/21/1998 PEND
Picked up plans to begin review.
Plan routing begun/TENANTS  9/17/1998
Route to PLAN CHECK and FIRE.
Plan assigned to (MYS)9/10/1998 9/17/1998
DetailsMarlene Southard
Routing - PUBLIC WORKS9/11/1998 9/14/1998 PASS
Plans ACCEPTED BY PLAN TECH  9/11/1998
Recd Pcfee & Taken To Pln CK  9/10/1998
Application received  9/10/1998