Permit Information
Permit NumberBLD98-03916
StatusFinaled
Name TONY CHUNG
Site Address 1404 W JEFFERSON ST
Project NameBOISE RESCUE MISSION
Customer Number 
ePlanReviewNo
Description
WOMEN'S SHELTER FOR BOISE RESCUE MISSION * TO CONVERT AN EXISTING CHURCH BUILDING INTO A WOMEN'S SHELTER FACILITY. THIS BUILDING IS TWO FLOORS WITH A BASEMENT. THE BASEMENT IS APPROXIMATELY 6075 SQ.FT AND IS THE DINING AND KITCHEN FACILITY. THE FIRST FLOOR IS APPROXIMATELY 6794 SQ.FT AND IS ADMINISTRATIVE OFFICES AND CONGERGATE RESIDENCE. THE SECOND FLOOR IS APPROXIMATELY 2731 SQ.FT. WITH ADMINISTRATIVE OFFICE AND CONGREGATE RESIDENCE. THE INSTALLATION OF A NFPA 13-R FIRE SPRINKLER SYSTEM IS REQUIRED. WORK TO INCLUDE THE COMPLETE REMODEL OF THE BUILDING INCLUDING MECHANICAL, ELECTRICAL, PLUMBING AND CODE UPDATES. AN ADDITION IS APPROXIMATELY 4,842 SQ.FT. AND MINIMUM AMOUNT OF SITE WORK. REFER TO BLD99-0723 FOR PARTICIAL DEMO WORK. DRH98-0157 CUP98-0044, CUP98-0115 MJP PC#885-98
Contact Information
See Activities list for contact information
Color Key
Current location of plans being reviewed:  
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary (BLD)  6/17/2003  
Fee Review-notes12/22/1998 3/15/2000 DONE
Fee Review-notes5/5/1999 3/15/2000 DONE
change in values
Permanent occupancy UNPAID FEE  3/8/2000 DONE
Perm. Occ. Cert. #8151 issued 3-8-00 to the Boise Rescue Mission.
Permanent Occupancy 3/7/20003/7/2000 DONE
Details
Telephone call  2/23/2000 PART
Talked with Tony Chung re: status of temp. - he hopes to have project completed by the end of February.
BLD-Final1/11/20001/12/20001/12/2000APART
Details
SIGNED THE OCC REQ CARD TEMP COL bill --###-#### fn occ
Temporary occupancy  1/12/2000 DONE
Temp. Occ. Cert. #3967 issued 1-12-00 to the Boise Rescue Mission.
BLD-Conference1/6/20001/6/20001/6/2000AFAIL
Details
met with bill and tony on the acessability requirements for door hardware and restrooms low level xit sign req,s
BLD-Conference1/4/20001/4/20001/4/2000PPART
Details
Scheduled by a contractor via Hello! on 01/04/2000 at 11:05:54. Contact: ###-####.
BLD-Final12/28/199912/29/199912/29/1999AFAIL
Details
C/N ISSUED DOOR HARDWARE ANDEXIT SIGNS NOT INSTALLEDBILL ###-####
FIRE-Final Inspection12/27/199912/28/199912/28/1999APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/27/1999 at 16:14:15. Contact: ###-####. Occ. approved.
FIRE-Final Inspection12/16/199912/17/199912/17/1999AFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/16/1999 at 08:55:37. Contact: ###-####. C/N issued- too many items to list.
FIRE-Sprinkler Rough-in11/18/199911/19/199911/19/1999AFAIL
DetailsRick Jackson
###-#### Sidewall in corridor.
FIRE-Supply Line Flush11/18/199911/19/199911/19/1999APASS
DetailsRick Jackson
###-#### Flush ok.
FIRE-Alarm Testing9/27/19999/30/19999/30/1999 FAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 09/27/1999 at 15:18:59. Contact: ###-####. Alarms not complete; reviewed plans and installation
BLD-Conference9/23/19999/23/19999/23/1999PPART
Details
Conf. On drywall behind tubs
BLD-Conference9/22/19999/22/19999/22/1999APART
Details
with bill needs to have drywall behind the tubs, will look at solutions
INSP - Framing/Rough-in8/27/19998/30/19998/30/1999AFAIL
Details
08/30/99 338 - ele box protectionn required
INSP - Wall cover8/20/19998/20/19998/20/1999 FAIL
CN issued for walk-in cooler location. Rated wall and door jamb must be maintained.
SUPER- Supervisor's review8/20/19998/20/19998/20/1999 FAIL
Site visit (cooler area).
INSP - Framing/Rough-in8/3/19998/3/19998/3/1999PPART
Details
08/03/99 338 - made ok to cover upper ceilings and walls w/o plmg.
SUPER- Supervisor's review7/28/19997/28/19997/28/1999
still in progess
SUPER- Supervisor's review7/15/19997/15/19997/15/1999
reviewd panel with elec inspector. marv will check clearance from ducts and contractor will build wall assembly behind panel to remove it from rated wall.
SUPER- Supervisor's review7/14/19997/14/19997/14/1999
on site with p. paine. reviewed frame with bill keys job super. fireblock throughout cut off conceiled space and call for another inspection. question on panel=elec in rated wall.
INSP - Wall cover7/14/19997/14/19997/14/1999 FAIL
Details
/ / 338 - WITH SUPERVISOR NOT READY FOR INSP OTHER AGENCIES NOT APPROV
INSP - Wall cover7/14/19997/14/19997/14/1999 FAIL
Details
/ / 338 - WITH SUPERVISOR NOT READY FOR INSP OTHER AGENCIES NOT APPROV
INSP - Framing/Rough-in7/12/19997/13/19997/13/1999AFAIL
Details
07/13/99 338 - not ready for any inspections super not on the jobsite wi
Routing - FIRE6/16/1999 6/23/1999
FED EXED ONE COPY OF PLANS TO FLOYD. BILL A HAS REMAINING COPY. KMM RECEIVED PLANS BACK FROM FLOYD. HE COULD NOT SEE HOW THEY APPLIED TO HIM FOR REVIEW. I ROUTED BACK TO MIKE P. KMM
Plan resubmittals received  6/22/1999 PEND
RECEIVED PLUMBING RESUBMITTALS FROM ENDSLEY AND ASSOCIATES, FORWARDED SAME TO MIKE PHILLIPS. DAR 6/22/99
INSP - Framing/Rough-in6/2/19996/2/19996/2/1999 PART
Details
06/02/99 338 - conf with owner,arch drywaller and the contr on the rated
INSP - Foundation5/27/19995/27/19996/1/1999PCANC
DetailsJim Storey
05/27/99 301 - p paine
INSP - Foundation5/25/19995/25/19995/25/1999PPART
Details
05/25/99 338 - ok for form completed areas
INSP - Foundation5/19/19995/21/19995/21/1999PPART
Details
05/21/99 338 - madeok to pour the ele, and to grade walls
INSP - Foundation5/19/19995/20/19995/20/1999PPART
Details
05/20/99 338 - ok to pour walls at the ele/stairwell
SUPER- Supervisor's review5/18/19995/18/19995/18/1999
met with tom cory to review tji installation tom made recomendations for temparary shoring to support floor in basement but tjis were ok
SUPER- Supervisor's review5/14/19995/14/19995/14/1999 PEND
Tom Cory.
SUPER- Supervisor's review5/13/19995/13/19995/13/1999
rebar improperly set per plan correct to meet plan and call for reinspect
INSP - Foundation5/12/19995/13/19995/13/1999PPART
Details
05/13/99 338 - ok to complete the footing pours
INSP - Foundation5/11/19995/12/19995/12/1999PPART
Details
05/12/99 338 - madeok to pour the footings of north addition only
INSP - Foundation5/10/19995/11/19995/11/1999APART
Details
05/11/99 338 - madeok for the elevator pit walls only
INSP - Foundation5/11/19995/11/19995/11/1999P
Details
pooring at 3:30 Randy ###-####
INSP - Framing/Rough-in5/6/19995/7/19995/7/1999AFAIL
Details
05/07/99 338 - need more conf been working on the project w/o permits
Print Occupancy Form  5/5/1999
Issue PAID IN FULL permit  5/5/1999
Inspection Record Card- Bld  5/5/1999
Plan assigned to (M_P)12/23/1998 5/4/1999 PASS
DetailsMike Phillips
05/04/99 16:17:39 M_P - this action updated by action script from <<>> in Case No. BLD98-3916
Routing - FIRE5/3/1999 5/4/1999 PASS
Print Pending Permit.LaserJet4  5/4/1999 PASS
PLANS/APPL TAKEN TO FRONT DESK  5/4/1999 PASS
Plan Reviewer's activity  5/4/1999 PASS
Routing - PLAN CHECK5/4/1999 5/4/1999
Plan resubmittals received  5/3/1999
RECEIVED TWO COPIES OF REVISED E-7 SHEETS ROUTED TO MIKE P. KMM
Routing - FIRE4/30/1999 4/30/1999 FAIL
Need to show electrical to operate the fire/smoke dampers.
Plan Reviewer's activity  4/30/1999 PEND
Routing to Fire Departmetn for review.
Routing - PLAN CHECK4/14/1999 4/30/1999
Routing to fire department for follow up review.
Plan resubmittals received  4/26/1999 PEND
RECEIVED PLAN RESUBMITTALS FROM THOMAS ENSLEY & ASSOCIATES, FORWARDED SAME TO MIKE PHILLIPS. DAR 4/26/99
Routing - FIRE4/13/1999 4/13/1999 CANC
no change from last time through on issues
Routing - PLAN CHECK4/2/1999 4/12/1999
Routing to fire department for follow up review.
Plan Reviewer's activity  4/12/1999 FAIL
Second set of corrections sent out.
Plan resubmittals requested  4/12/1999 FAIL
Second set of corrections requested.
Plan resubmittals received  4/5/1999 PEND
Receive resubmittals from Thomas Ensley Architects, forwarded same to Michael Phillips. DAR 4/5/99
Routing - FIRE4/2/1999 4/2/1999 FAIL
mechanical plans still don't protect corridor or show cooking hood shaft
Routing - PLUMBING3/31/1999 4/2/1999 PASS
Plan Reviewer's activity  3/26/1999 FAIL
Requested additional meeting with Tom to discuss resubmittals. Have meeting on March 30 at 1:30.
Plan resubmittals received  3/23/1999 PEND
Received plan resubmittals from T.R.Ensley & Associates, Architects, forwarded same to Michael Phillips. DAR 3/23/99
Routing - FIRE3/5/1999 3/10/1999 FAIL
corridor protection, grease duct protection, exits from 2nd floor
Plan Review Completed(1st rev)  3/10/1999 FAIL
plumbing, ubc and ufc
Routing - PLAN CHECK2/1/1999 3/5/1999
Plan resubmittals requested  3/3/1999 FAIL
ADDITIONAL INFORMATION REQUIRED TO BE SUBMITTED FOR AN ADDITIONAL REVIEW.
Plan resubmittals received  2/24/1999
RECEIVED THREE COPIES OF REVISED SHEETS M1.1, P0.0, P0.1, P2.1, P2.2, P2.3, P2.4, P3.1, P4.1, PLUS THREE COPIES OF ADDENDA AND CLARIFICATIONS ADDENDUM NO. 2 ROUTED TO MIKE P. KMM
Plan resubmittals received  2/9/1999 PEND
RECEIVED ADDENDUM NUMBER 1 FROM THOMAS ENSLEY AND ASSOCIATES, FORWARDED SAME TO MIKE PHILLIPS. DAR 1/10/99
Routing - PLUMBING1/28/1999 2/1/1999 FAIL
Routing - PUBLIC WORKS1/21/1999 1/28/1999 PASS
Routing - PLANNING1/7/1999 1/21/1999 PASS
Per DRH98-0157 conditions
Routing - PLANNING1/5/1999 1/7/1999 PASS
CUP98-0044, CUP98-0115 I HAVE APROVED THESE PLANS AND SENT THEM ON TO DESIGN REVIEW FOR REVIEW SAR
Routing Off Site - C.D.H12/23/1998 1/5/1999 PASS
12-23-98 CAROL WILL BE INTO LOOK AT PLANS. KMM
Plans ACCEPTED BY PLAN TECH  1/5/1999 PASS
BRIAN MURPHY RECEIVED FIVE COPIES OF GRADING AND DRAINAGE PLUS CALCS. WILL ROUTE TO PW WHEN I RECEIVE BACK FROM CDH. KMM
Routing Off Site - STRUCTURAL12/23/1998 12/23/1998
ENG. WILL BE DONE INHOUSE PER JOHN M.
Plan routing begun/NEW & ADDTN  12/23/1998 PEND
SEE ACTION A006 PEND.
Plans ACCEPTED BY PLAN TECH  12/23/1998 PEND
REQUIRES FIVE COPIES OF GRADING AND DRAINAGE PLANS WITH CALCS. PER BRIAN M. WILL ROUTE TO CDH IN THE MEAN TIME. KMM CONTACTED TONY CHUNG OF THIS NEED.
Waiting for Cert. of Value  12/22/1998 PASS
Recd Pcfee & Taken To Pln CK  12/22/1998
Application received  12/22/1998 PASS
Routing - PLUMBING6/22/1999