BLD-Final | 2/8/2000 | 2/8/2000 | 2/8/2000 | P | PASS |
Carl Dependahl
|
|
|
Final reinspect - all other agencies have signed off - restaurant signed card @office ok
|
FIRE-Final Inspection | 2/8/2000 | 2/8/2000 | 2/8/2000 | P | PASS |
Joe Tawney
|
|
|
Final reinspect - restaurant. Reinspection ok for permanent occ
|
Permanent Occupancy | | 2/8/2000 | 2/8/2000 | | DONE |
|
|
|
|
Permanent occupancy UNPAID FEE | | | 2/8/2000 | | DONE |
|
|
|
Perm. Occ. Cert. #8130 issued 2-8-00 to the Hollywood Chinese Restaurant.
|
FIRE-Final Inspection | 1/31/2000 | 2/4/2000 | 2/4/2000 | A | FAIL |
Joe Tawney
|
|
|
###-####; Bing Lee. Reinsp. need copy of hood suppression system installation report. 2/4/00 1:16:42 PM
|
FIRE-Final Inspection | 1/12/2000 | 1/14/2000 | 1/14/2000 | A | FAIL |
Joe Tawney
|
|
|
Bing ###-#### Reinsp. final duct detector. 1/14/00 2:59:54 PM
|
FIRE-Final Inspection | 1/3/2000 | 1/4/2000 | 1/4/2000 | A | FAIL |
Joe Tawney
|
|
|
###-####. Reinsp. fail C/N not completed.
|
FIRE-Final Inspection | 12/17/1999 | 12/23/1999 | 12/23/1999 | A | FAIL |
Joe Tawney
|
|
|
Bing Lee, ###-#### - final reinspect. Reinsp. alarm vendor could not be there.
|
BLD-Final | 12/17/1999 | 12/23/1999 | 12/23/1999 | P | FAIL |
Carl Dependahl
|
|
|
Hollywood Restaurant, Bing Lee - ###-####; fail, has fire c/n
|
FIRE-Final Inspection | 12/13/1999 | 12/14/1999 | 12/14/1999 | P | FAIL |
Joe Tawney
|
|
|
BING-- ###-#### FIRE FN Reinsp. Fail new C/N issued.
|
BLD-Conference | 12/1/1999 | 12/1/1999 | 12/1/1999 | | PASS |
|
|
|
Bing Lee came in and we discussed getting the outstanding finals on restaurant.
|
Conference | 11/23/1999 | 11/23/1999 | 11/23/1999 | | DONE |
|
|
|
Talked w/Bing Lee (owner of business) and explained to him that he needed to get final inspections.
|
(F) Reprint permit | | | 11/18/1999 | | DONE |
|
|
|
|
Fee Review-notes | 2/4/1999 | | 11/18/1999 | | DONE |
|
|
|
ADDITIONAL VALUE FROM SUBS CONT. LH
|
CHANGE STATUS TO (TMP) | | | 10/29/1999 | | DONE |
|
|
|
|
INSP - Final | 7/30/1999 | 8/2/1999 | 8/2/1999 | A | PART |
Wes Worcester
|
|
|
08/02/99 342 - ###-#### Bing Li needed address #'s, temp ok
|
Temporary occupancy | | | 8/2/1999 | | PASS |
|
|
|
Temp. Occ. Cert. #3880 isssued 8-2-99 to the Hollywood Chinese Restaurant.
|
INSP-Alarm Testing | 7/30/1999 | 7/30/1999 | 7/30/1999 | | PART |
Joe Tawney
|
|
|
/ / 406 - OK ON ALARM TEST OF COOKING HOODS
|
INSP - Final | 7/30/1999 | 7/30/1999 | 7/30/1999 | | PART |
Joe Tawney
|
|
|
/ / 406 - OK FOR TEMP OCC DUCT DET & LED'S
|
INSP-Final Inspection | 7/23/1999 | 7/28/1999 | 7/28/1999 | A | FAIL |
Joe Tawney
|
|
|
07/28/99 406 - FINAL FAIL ALARM SYSTEM, EMERG LIGHTS, DUCT DET
|
INSP - Framing/Rough-in | 7/19/1999 | 7/19/1999 | 7/19/1999 | P | PART |
Carl Dependahl
|
|
|
07/19/99 340 - as per robert fireshaft inspection ###-#### or ###-#### robert; add'l shaft ok
|
INSP - Framing/ Rough-in | 6/25/1999 | 6/25/1999 | 6/25/1999 | | PART |
Carl Dependahl
|
|
|
/ / 340 - HOODS OK PER AL H
|
INSP - Framing/Rough-in | 6/17/1999 | 6/17/1999 | 6/17/1999 | P | PART |
Carl Dependahl
|
|
|
06/17/99 340 - robert Kelly ###-#### clg ok, moved shaft ok
|
INSP - Framing/Rough-in | 6/10/1999 | 6/10/1999 | 6/10/1999 | P | FAIL |
Carl Dependahl
|
|
|
06/10/99 340 - shaft moved, not accessible, keep c/n
|
INSP - Framing/Rough-in | 6/7/1999 | 6/7/1999 | 6/7/1999 | | PART |
Carl Dependahl
|
|
|
/ / 340 - REC'D RESUB FOR ADD'L PARTITIONS, OK. DISCUSSED SHAFTS W/ CONTRACTOR
|
INSP - Framing/Rough-in | 6/2/1999 | 6/2/1999 | 6/2/1999 | | FAIL |
Carl Dependahl
|
|
|
/ / 340 - SHAFT TOBEMOVED, SUBMIT FORUSE OF FIREMASTER.
|
INSP - Final | 5/17/1999 | 5/17/1999 | 5/17/1999 | | FAIL |
Carl Dependahl
|
|
|
05/14/99 340 - Rob ###-####; need permit for hoods & add'l hvac...swamp
|
INSP-Final Inspection | 5/14/1999 | 5/14/1999 | 5/14/1999 | P | PART |
Joe Tawney
|
|
|
05/14/99 406 - PRELIMINARY INSP OF SPKLRS AND HOOD SHAFTS
|
INSP - Framing/Rough-in | 5/13/1999 | 5/14/1999 | 5/14/1999 | A | PART |
Carl Dependahl
|
|
|
05/14/99 340 - bing ###-####; 1st shaft ok, add fasteners, ok to install
|
INSP - Framing/Rough-in | 5/6/1999 | 5/7/1999 | 5/7/1999 | P | PART |
Carl Dependahl
|
|
|
05/07/99 340 - Bing ###-####; wip on shafts; hard grid at kitch ok
|
INSP - Framing/Rough-in | 4/16/1999 | 4/19/1999 | 4/18/1999 | A | PART |
Carl Dependahl
|
|
|
04/19/99 340 - bing ###-####; add struts at grid...install/ inspect shaf
|
INSP - Framing/Rough-in | 4/15/1999 | 4/16/1999 | 4/16/1999 | A | NR |
Carl Dependahl
|
|
|
04/16/99 340 - ###-#### no acces, recall
|
INSP - Framing/Rough-in | 4/5/1999 | 4/6/1999 | 4/6/1999 | P | FAIL |
Carl Dependahl
|
|
|
04/06/99 340 - ###-####; fireblocks, need shaft, ok to cover
|
INSP - Framing/Rough-in | 3/31/1999 | 3/31/1999 | 3/31/1999 | | NR |
Carl Dependahl
|
|
|
/ / 340 - CONF W/ FRAMER, REC'D RESUB. NEED ELEC R/I
|
INSP - Framing/Rough-in | 3/25/1999 | 3/25/1999 | 3/25/1999 | P | FAIL |
Carl Dependahl
|
|
|
03/25/99 340 - ###-#### Robert need other r/is
|
Issue PAID IN FULL permit | | | 2/3/1999 | | |
|
|
|
|
Plan assigned to (ADS) | 1/11/1999 | | 1/26/1999 | | PASS |
|
|
|
01/26/99 14:08:24 ADS - this action updated by action script from <<>> in Case No. BLD99-0022
|
Plan resubmittals received | | | 1/26/1999 | | |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/26/1999 | | |
|
|
|
|
Print Occupancy Form | | | 1/26/1999 | | |
|
|
|
|
Inspection Record Card- Bld | | | 1/26/1999 | | |
|
|
|
|
Routing - PLAN CHECK | 1/15/1999 | | 1/26/1999 | | PASS |
|
|
|
|
INSP - Footings | 1/22/1999 | 1/22/1999 | 1/22/1999 | | FAIL |
Carl Dependahl
|
|
|
/ / 340 - early start, poured
|
Routing - FIRE | 1/14/1999 | | 1/15/1999 | | PASS |
|
|
|
|
Plan Review Completed(1st rev) | | | 1/15/1999 | | PASS |
|
|
|
|
Plan resubmittals requested | | | 1/14/1999 | | FAIL |
|
|
|
Notice faxed & mailed to architect. Kitchen restroom needs to be accessible.
|
Routing - PLUMBING | 1/12/1999 | | 1/13/1999 | | PASS |
|
|
|
|
Routing - PUBLIC WORKS | 1/11/1999 | | 1/12/1999 | | PASS |
|
|
|
|
Plan routing begun/TENANTS | | | 1/11/1999 | | |
|
|
|
Route to PUBLIC WORKS, PLUMBING, PLAN CHECK and FIRE. PLANS APPROVED BY CENTRAL DISTRICT HEALTH (BOB JUE) ON 1/4/99.
|
Application received | | | 1/5/1999 | | |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 1/5/1999 | | PEND |
|
|
|
SHEETS A1,A2,A3,A4 NEED STAMPED AND SIGNED BY BILLY RAY STRITE. DAR 1/6/99. CALLED TRENT KOCI ADVISED HIM OF UNSIGNED PLANS, HE SAID HE WOULD SEND DREW OVER TO PICK THE PLANS UP TO BE SIGNED. DAR 1/6/99 PLANS RETURNED FROM BRS STAMPED AND SEALED. DAR 1/8/99
|
Routing - PLAN CHECK | 1/13/1999 | | 1/14/1998 | | FAIL |
|
|
|
|