BLD-Final | 5/17/2000 | 5/18/2000 | 5/18/2000 | A | PASS |
|
|
|
###-#### c/c# 19339 5/19/00 8:29:55 AM
|
FIRE-Final Inspection | 5/17/2000 | 5/18/2000 | 5/18/2000 | A | PASS |
Rick Jackson
|
|
|
###-####
|
Letter of compliance | | | 5/18/2000 | | PASS |
|
|
|
Letter of Compliance #19339 issued 5-18-00.
|
BLD-Final | 1/6/2000 | 1/7/2000 | 1/7/2000 | A | FAIL |
|
|
|
JERRY FISHER ###-#### FN OCC WITH 409 AND ALL CONTRACTORS
|
FIRE-Final Inspection | 1/6/2000 | 1/7/2000 | 1/7/2000 | A | FAIL |
Rick Jackson
|
|
|
JERRY ###-#### FIRE FN. Doors not operational/ installed as required per plans.
|
Fee Review-notes | 6/21/1999 | | 6/21/1999 | | DONE |
|
|
|
|
INSP-Alarm Testing | 5/20/1999 | 5/20/1999 | 5/20/1999 | P | FAIL |
Rick Jackson
|
|
|
audibility poor in 1st floor; pressurization fans not working properly;
|
INSP-Alarm Testing | 5/18/1999 | 5/18/1999 | 5/18/1999 | P | FAIL |
Rick Jackson
|
|
|
alarms not complete -
|
INSP - Framing/Rough-in | 4/22/1999 | 4/22/1999 | 4/22/1999 | P | PART |
|
|
|
04/26/99 338 - made ok to install door at the fire room
|
Issue PAID IN FULL permit | | | 3/8/1999 | | |
|
|
|
|
Print Occupancy Form | | | 3/8/1999 | | |
|
|
|
|
Telephone call | | | 3/8/1999 | | |
|
|
|
talked to bob gave dollar amount
|
Plan assigned to (DRS) | 1/27/1999 | | 3/5/1999 | | PASS |
Dan Stuart
|
|
|
03/05/99 21:03:58 DRS - this action updated by action script from <<>> in Case No. BLD99-0224
|
Telephone call | | | 3/5/1999 | | |
|
|
|
Call from Steve of H&L Architects to verify that I will send list of doors needing to be corrected to H&L Arch.
|
Print Pending Permit.LaserJet4 | | | 3/5/1999 | | PASS |
|
|
|
Processing for issuance of a permit.
|
Telephone call | | | 3/5/1999 | | |
|
|
|
Call from Steve Dunbar from H&L Architect to check on my review of the door analysis they had done for the building and to fax information to him noting which particular doors would be required to be upgraded as part of the 1992 "Letter of Agreement". I completed by review and faxed a copy to him at approximately 6:30 P>M> on Friday night. I will attach a copy to each set of plans and move forward to issue permit.
|
Routing - PLAN CHECK | 3/4/1999 | | 3/5/1999 | | PASS |
|
|
|
Met with Jim Hernandez & John Hughes of AT&T & H&L Architects to review their resubmittals, disciver any deficiencies and to move forward with issuaing a permit. Floyd Varley accepted resubmittals for alarms, detection & sprinklers and I reviewed the plans for doors, fire walls and protection of openings and penetrations with the understanding that even if not complete on resubmittals, I would redline the plans with requirements to be met and Jim Hernandex, AT&T Bulding Engineer would see the items were completed. I have put notes & comments together on plans and am prepared to process for issuance of permit.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/5/1999 | | PASS |
|
|
|
Routing to permit desk for processing. desk
|
Meeting | | | 3/4/1999 | | |
|
|
|
Meeting with Floyd Varley, Jim Hernandez (AT&T Building Engineer), John Hughes (Architect w/ H&L)and Dan Stuart. New plans & submittals were brought to the meeting by the architect along with responses to previous plan review comments of 9/30/98, 2/2/99 & 3/4/99 for Fire Dept. & 2/11/99 of Bulding Plans Corrections list. We reviewed each item still open on the proposed Fire Command Center project for which this permit was applied for as well as all outstanding questions having to do with the 1992 agreement letter for required modifications to the facility because of the new office occuapncy located more than 75 feet above grade causing this facility to be reclassified as an exisitng high rise. The sprinkler system, smoke detection, alarms, 1-hour occupancy separation walls with 1-hour protected opening for doors and ducts and penetrations that separates the sprinkled areas from the nonsprinkled telecommunications equipment rooms, pressurization of the center and East stair enclosures and the exit system serving the 6th floor offices (to include rated doors to the enclosures and into the enclosure extension located on the first floor) were reviewed item by item. The resubmitted plans did not indicate if fire dampers were/are present at all ducts penetrating the one-hour occupancy separation walls required under the 1992 agreement. I will make this requirement noted on the plans as well as mark the specific walls as designated on the small set of plans submitted to show locations. The fire & structural inspectors will verify compliance with the 1991 UBC for these areas as agreed. Floyd has verbally accepted information as showing compliance with Fire Code review and will approve plans for permit issuance. I will check the doors presented as to current ratings & proposed upgrades and let H&L Architects know what doors are speciffically part of the 1992 upgrade agreement.
|
Routing - FIRE | 3/4/1999 | | 3/4/1999 | | PASS |
|
|
|
approved as noted on plans provided this date by ATT and Cator Ruma
|
Plan resubmittals received | | | 3/4/1999 | | |
|
|
|
Received answers to all requests and a verbal agreement from Mr. Hernandez & Mr. Hughes to complete the project per notes & attachments we put on plans to help clarify if we will move forward with issuing the permit. Floyd and I agreed we could work with them based on the new information reveived.
|
Plan resubmittals requested | | | 2/11/1999 | | PARK |
|
|
|
PLAN REVIEW COMPLETED WITH FAX AND LETTER TO ARCHITECT SCOTT KEUHN AND AT&T PROJECT MANAGER JIM HERNANDEZ.
|
Plan Reviewer's activity | | | 2/11/1999 | | |
|
|
|
REVIEWED PLANS WITH FLOYD AND THE INABILITY TO GET COMPLETE PLANS AS REQUESTED AMNY TIMES OVER IN RELATION TO THE 1992 LETTER UPGRADE AGREEMENT WITH AT&T & US WEST AND THE CITY BUILDING & FIRE DEPARTMENTS. THE FIRE COMMAND CENTER IS PART OF THE AGREEMENT AS WELL AS THOSE ITEMS NOTED CONCERNIGN FIRE SEPARATION WALLS, SMOKE DETECTION, ALARMS & SPRINKLER SYSTEM PLANS FOR APPROVAL TO ISSUE A PERMIT. WE CONTINUOUSLY GET ONLY PARTIAL PLANS WITHOUT THE INFORMATION REQUESTED AND ASSURED WE WOULD GET EACH TIME THE PARTIES COMNE TO THE CITY TO SEEK TO GET OUT OF SOME REQUIREMENT OR CONFUSE AN ISSUE BY STATING WE KEEP CHANGING REQUIRMENTS. AFTER WE ONCE AGAIN READ THE AGREEMENT AND CODE APPLICABLE TO SHOW THAT WE HAVE NOT CHANGED BUT THEY HAVE NOT READ THE REQUIREMENTS, THEY LEAVE STATING WE WILL HAVE WHAT IS NEEDED ASAP. THIS HASN'T HAPPENDED YET. NOT
|
Routing - PLAN CHECK | 2/9/1999 | | 2/11/1999 | | PARK |
|
|
|
I GAVE A SET OF PLANS TO FLOYD TO REVIEW BASED ON A CONVERSATION HE HAD WITH MR. HUGHES WHILE I REVIEWED THE OTHER. THE PLANS DO NOT PROVIDE THE INFORMATION REQYUIRED IN A JANUARY 6, 1999 MEETING WE HELD WITH PROJECT REPS, FLOYD & MYSELF TO TRY AND GET THE FINAL PROCESS UNDERWAY. PLANS ARE PARKED BEHIND MY DESK UNTIL RESUBMITTALS ARE RECEIVED.
|
Routing - FIRE | 2/9/1999 | | 2/10/1999 | | FAIL |
|
|
|
PLANS BACK TO PLAN REVIEW TO HOLD UNTIL SUBMITTAL REQUIRED ARE SUBMITTED.
|
Routing - PLAN CHECK | 2/2/1999 | | 2/8/1999 | | |
|
|
|
PICKED UP PLANS TO BEGIN REVIEW.
|
Routing - FIRE | 1/27/1999 | | 2/2/1999 | | FAIL |
|
|
|
alarm plans do not meet the requirements of the 1992 agreement or corrections required of the 9/98 review of the fire alarm system.
|
Plan assigned to (MYS) | 1/26/1999 | | 1/27/1999 | | |
Marlene Southard
|
|
|
|
Plan routing begun/TENANTS | | | 1/27/1999 | | |
|
|
|
Route to FIRE and PLAN CHECK.
|
Application received | | | 1/26/1999 | | PASS |
|
|
|
|
Received Certificate of Value | | | 1/26/1999 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 1/26/1999 | | PASS |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 1/26/1999 | | |
|
|
|
|