Receive PAYMENT IN FULL | | | 9/23/1999 | | DONE |
|
|
|
|
Fee Review-notes | 4/30/1999 | | 8/23/1999 | | |
|
|
|
ADDITIONAL PERMIT WAS ISSUED AFTER I DID AUDIT
|
(F) Reprint permit | | | 8/23/1999 | | |
|
|
|
|
INSP - Final | 7/13/1999 | 7/14/1999 | 7/14/1999 | P | PASS |
Carl Dependahl
|
|
|
07/14/99 340 - ###-#### rod.; ok card to cont.
|
Letter of compliance | | | 7/14/1999 | | PASS |
|
|
|
issued cert. of compliance 7/14/99-#17880 kitchen remodel
|
Receive PAYMENT IN FULL | | | 7/8/1999 | | |
|
|
|
|
INSP-Final Inspection | 6/3/1999 | 6/4/1999 | 6/4/1999 | A | PASS |
Joe Tawney
|
|
|
06/04/99 406 - REINSP OK FOR CERT OF COMPLETION
|
INSP-Final Inspection | 5/17/1999 | 5/19/1999 | 5/19/1999 | A | FAIL |
Rick Jackson
|
|
|
TRIP TEST FOR ANCIL SYSTEM ansul system okay; balance report shows EF's at only 48%
|
INSP - Final | 5/18/1999 | 5/19/1999 | 5/19/1999 | A | FAIL |
Carl Dependahl
|
|
|
05/19/99 340 - fryer req's proper flow to exhaust , waiting balance repo
|
INSP-Final Inspection | 5/19/1999 | 5/19/1999 | 5/19/1999 | P | PART |
Rick Jackson
|
|
|
temp occ approved - EF's are at 68% - will reinspect on 05/26/99 for getting to design exhaust
|
SUPER- Supervisor's review | 5/19/1999 | 5/18/1999 | 5/18/1999 | | PEND |
|
|
|
|
INSP - Framing/Rough-in | 5/12/1999 | 5/14/1999 | 5/14/1999 | A | PART |
Carl Dependahl
|
|
|
05/14/99 340 - trip test/ conference/ requested 9:00/Rod ###-####; fryer
|
INSP-Conference | 5/12/1999 | 5/14/1999 | 5/14/1999 | A | PART |
Joe Tawney
|
|
|
05/14/99 406 - OK ON INSTALLATION AND TEST OF DEEP FRYER HOOD
|
INSP - Framing/Rough-in | 5/13/1999 | 5/13/1999 | 5/13/1999 | | PART |
Carl Dependahl
|
|
|
/ / 340 - CONF W/ BLDR, SHAFT WALL INT LAYER OK
|
INSP - Framing/Rough-in | 5/7/1999 | 5/7/1999 | 5/7/1999 | P | PART |
Carl Dependahl
|
|
|
05/07/99 340 - CONFERENCE Rod Fender; remodel while open; shaft w.i.p...
|
INSP - Framing/Rough-in | 5/3/1999 | 5/4/1999 | 5/4/1999 | A | FAIL |
Jim Storey
|
|
|
05/04/99 301 - trans to p paine
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/30/1999 | | PASS |
|
|
|
|
Issue PAID IN FULL permit | | | 4/30/1999 | | |
|
|
|
|
Plan Reviewer's activity | | | 4/30/1999 | | PASS |
|
|
|
|
Print Pending Permit.LaserJet4 | | | 4/30/1999 | | PASS |
|
|
|
|
Print Occupancy Form | | | 4/30/1999 | | |
|
|
|
|
Inspection Record Card- Bld | | | 4/30/1999 | | |
|
|
|
|
Telephone call | | | 4/30/1999 | | PASS |
|
|
|
talked to dawn to verify plans are ready
|
Plan assigned to (M_P) | 4/19/1999 | | 4/30/1999 | | PASS |
Mike Phillips
|
|
|
04/30/99 14:17:30 M_P - this action updated by action script from <<>> in Case No. BLD99-0973
|
Routing - PLANNING | 4/28/1999 | | 4/29/1999 | | PASS |
|
|
|
Restriping of parking lot for accessibility approved per attached memo and plan from Steve Trout. MGS.
|
Routing - PLAN CHECK | 4/23/1999 | | 4/28/1999 | | |
|
|
|
routing to planning for review of parking lot.
|
Plan Reviewer's activity | | | 4/23/1999 | | PEND |
|
|
|
Waiting for architect to provide letter about accessibility issues.
|
Telephone call | | | 4/23/1999 | | |
|
|
|
Phoned Steve and left message I am waiting for letter about accessibility to issue permit.
|
Routing - PLUMBING | 4/19/1999 | | 4/23/1999 | | PASS |
|
|
|
|
Routing - FIRE | 4/23/1999 | | 4/23/1999 | | PASS |
|
|
|
|
Plan assigned to (MYS) | 4/12/1999 | | 4/19/1999 | | |
Marlene Southard
|
|
|
|
Routing - PUBLIC WORKS | 4/19/1999 | | 4/19/1999 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 4/19/1999 | | 4/19/1999 | | |
|
|
|
Routing to other for review.
|
Plan routing begun/TENANTS | | | 4/19/1999 | | |
|
|
|
Route to PLAN CHECK, PUBLIC WORKS, PLUMBING and FIRE.
|
Plan Reviewer's activity | | | 4/19/1999 | | PEND |
|
|
|
Routing to others for approval. Waiting for information about accessibility issue.
|
Recd Pcfee & Taken To Pln CK | | | 4/12/1999 | | |
|
|
|
|
Application received | | | 4/12/1999 | | |
|
|
|
|
Received Certificate of Value | | | 4/12/1999 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 4/12/1999 | | PASS |
|
|
|
|