BLD-Concrete | 10/19/1999 | 10/20/1999 | 10/20/1999 | A | PART |
|
|
|
for columns--- a2, a3, b4, c5, d6 -----###-#### -dave - Made ok w/spec. insp. Blessing
|
BLD-Concrete | 10/18/1999 | 10/18/1999 | 10/18/1999 | P | PART |
|
|
|
grid line 2, columns k, l , m , n--dave-- ###-#### R-bar placed special insp. Ok
|
BLD-Concrete | 10/13/1999 | 10/13/1999 | 10/13/1999 | P | PART |
|
|
|
grid line G from 1.30 to 2 line Made ok with sp. Insp. Approval
|
BLD-Concrete | 10/7/1999 | 10/7/1999 | 10/7/1999 | P | PART |
|
|
|
grid line G from grid line 1 to 1.60 grid line N grid line 1 to 1.1 r-bar placed spec insp approval req
|
BLD-Concrete | 10/1/1999 | 10/4/1999 | 10/4/1999 | A | PART |
|
|
|
from grid line 2 to 1 on C line. grade beam 1 sp insp re bar placed
###-####
|
BLD-Concrete | 9/29/1999 | 9/29/1999 | 9/29/1999 | P | PART |
|
|
|
GRID LINES 1-A TO G GRID LINE 2 D TO G COLUMNS ###-#### R-bar placed, spec approval required
|
BLD-Concrete | 9/24/1999 | 9/27/1999 | 9/27/1999 | P | PART |
|
|
|
REBAR INSP- TOM- ###-#### R-Bar placed sp. Insp. Approval ok
|
BLD-Foundation | 9/23/1999 | 9/24/1999 | 9/24/1999 | A | PART |
|
|
|
TOM-- ###-#### FOUND WALL INSP Made ok with spec. insp. Approval/ R-bar replaced
|
BLD-Footing | 9/23/1999 | 9/24/1999 | 9/24/1999 | A | PART |
|
|
|
TOM ###-#### Made ok with spec. insp. Approval
|
BLD-Concrete | 9/20/1999 | 9/21/1999 | 9/21/1999 | P | PART |
|
|
|
tom-- ###-#### concrete wall insp-k1 to n 1 Made ok with special insp. Approval
|
BLD-Concrete | 9/17/1999 | 9/20/1999 | 9/20/1999 | A | PART |
|
|
|
made ok spill insp
|
BLD-Concrete | 9/17/1999 | 9/17/1999 | 9/17/1999 | P | PART |
|
|
|
CONCRETE WALLS DAVE ###-#### ELEVATOR BASEMENT AREAmade ok r-bar placed sp insp ok
|
BLD-Framing/Rough-in | 9/15/1999 | 9/16/1999 | 9/16/1999 | A | PART |
|
|
|
###-####- krisenbeck -grid 1 colums j k & l--- grid line 2 column b - MADE OK WITH SPCL INSPCTN APPROVAL
|
INSP - Foundation | 9/13/1999 | 9/13/1999 | 9/13/1999 | P | PART |
|
|
|
grid line 1 e-f-h-m ###-#### sp insp made ok
|
SUPER- Supervisor's review | 9/3/1999 | 9/3/1999 | 9/3/1999 | | |
|
|
|
still in progress setting up east wall
|
INSP - Concrete | 8/30/1999 | 8/30/1999 | 8/30/1999 | P | PART |
|
|
|
08/30/99 338 - DAVE ###-#### GRID LINES G 1-2 GRID LINE C 1-2 FOOTING ON 1 GRID LINE B madeok with sp insp approval
|
SUPER- Supervisor's review | 8/26/1999 | 8/26/1999 | 8/26/1999 | | |
|
|
|
fill placed with confines of base footing pads ok
|
Plan resubmittals received | | | 8/26/1999 | | PEND |
|
|
|
RECEIVED PLAN RESUBMITTALS FROM HOSFORD LARSON RUDEEN, FORWARDED SAME TO JOHN MENARD. 8/26/99 DAR
|
SUPER- Supervisor's review | 8/25/1999 | 8/25/1999 | 8/25/1999 | | |
|
|
|
base pad for colum line adjacent to sheet piling. spec insp looks good
|
INSP - Concrete | 8/23/1999 | 8/23/1999 | 8/23/1999 | P | PART |
|
|
|
08/23/99 338 - TOM.###-####BETWEEN N6-G6 & N2-K2. PILE CAPSF6,E6,D6,B2.
|
SUPER- Supervisor's review | 8/20/1999 | 8/20/1999 | 8/20/1999 | | |
|
|
|
pouring colum pads continuous special inspection on pours ok. wright brothers has concrete contract
|
INSP - Foundation | 8/17/1999 | 8/18/1999 | 8/18/1999 | A | PASS |
Jim Storey
|
|
|
08/18/99 301 - dave ###-#### footing, grid line1 c-f & elevator
|
INSP - Foundation | 8/16/1999 | 8/17/1999 | 8/17/1999 | P | CANC |
|
|
|
GRID LINES 1, C - G. canc at 11:34.
|
INSP - Foundation | 8/16/1999 | 8/16/1999 | 8/16/1999 | P | PART |
|
|
|
08/16/99 338 - FOOTING GRID LINES 1,H - N,r-bar placed per plan sp insp
|
SUPER- Supervisor's review | 8/16/1999 | 8/16/1999 | 8/16/1999 | | |
|
|
|
pouring colum pads perry and spec insp checking ok
|
INSP - Foundation | 8/10/1999 | 8/10/1999 | 8/10/1999 | P | FAIL |
Wes Worcester
|
|
|
08/10/99 342 - GRID LINE 2 C D E F G M N. DAVE ###-#### given to Perry
|
INSP - Concrete | 8/3/1999 | 8/6/1999 | 8/6/1999 | A | PART |
|
|
|
PIER CAP GRID LINE 6 THRU G / ###-####
|
INSP - Concrete | 8/4/1999 | 8/6/1999 | 8/5/1999 | P | PART |
|
|
|
08/06/99 338 - DAVE CASE ON CAPS ###-#### r-bar placed sp insp made ok
|
SUPER- Supervisor's review | 7/27/1999 | 7/27/1999 | 7/27/1999 | | |
|
|
|
excavation continuing. still in good sound gravel
|
SUPER- Supervisor's review | 7/15/1999 | 7/15/1999 | 7/15/1999 | | |
|
|
|
base excavation continuing still in pit run
|
Plan Modification Accepted | | | 7/14/1999 | | PASS |
|
|
|
RECEIVED STRUCTURAL UPDATES TO ORIGINAL FOOTING AND FOUNDATION SET. ADDITION OF STAIR/ELEVATOR SHAFT DRAWINGS. ROUTED TO JOHN M. WHO STATED HE WANTS TO ROUTE ONLY TO OUTSIDE ENG. AT THIS TIME. HE WANTS THEM TO REVIEW ALONG WITH THE PLANS FOR THE STRUCTURE. GENE BENETT STATED THAT STRUCTUAL PLANS FOR THE GARAGE WERE SUBMITTED ALONG WITH THE FOUNDATION PERMIT PLANS UNDER BLD99-1038 ON 4-16-99. KMM
|
SUPER- Supervisor's review | 7/9/1999 | 7/9/1999 | 7/9/1999 | | |
|
|
|
excavation in progress north side silt sand valuvium ok gs
|
INSP - Foundation | 7/1/1999 | 7/1/1999 | 7/1/1999 | | |
|
|
|
cason pours continuing ok
|
INSP - Concrete | 6/28/1999 | 6/29/1999 | 6/28/1999 | A | PART |
|
|
|
06/29/99 338 - Grid line 2 north and south Grid line H left grid line 6 north grid line K right and left
|
SUPER- Supervisor's review | 6/28/1999 | 6/28/1999 | 6/28/1999 | | |
|
|
|
pouring continuing special inspector on site tickets on trucks checked all ok
|
INSP - Concrete | 6/25/1999 | 6/28/1999 | 6/28/1999 | A | PART |
|
|
|
06/28/99 338 - grid lines 2 south grid line L left and right ok with sp
|
INSP - Concrete | 6/28/1999 | 6/28/1999 | 6/28/1999 | P | PART |
|
|
|
06/28/99 338 - Grid line 2 north and south Grid line H right madeok with sp insp appr.
|
INSP - Concrete | 6/28/1999 | 6/28/1999 | 6/28/1999 | P | PART |
|
|
|
06/28/99 338 - grid line 6 north grid line L left made ok with sp insp a
|
SUPER- Supervisor's review | 6/25/1999 | 6/25/1999 | 6/25/1999 | | |
|
|
|
proceeding with cason pours, perry has given dave reeder super. letter changing rebar spacing from 2 inch clearance to 3 back for engineer stamp
|
INSP - Concrete | 6/25/1999 | 6/25/1999 | 6/25/1999 | P | PART |
|
|
|
06/25/99 338 - grid line 2 north and south grid line J left made ok with
|
INSP - Concrete | 6/24/1999 | 6/24/1999 | 6/24/1999 | P | PART |
|
|
|
06/24/99 338 - CAISONS//GRIDLINE 6 NORTH & SOUTH GRIDLINE L RIGHT r-bar
|
INSP - Concrete | 6/23/1999 | 6/24/1999 | 6/24/1999 | A | PART |
|
|
|
06/24/99 338 - grid line 2 north and south grid line J right ok to pour
|
INSP - Concrete | 6/22/1999 | 6/23/1999 | 6/23/1999 | A | PART |
|
|
|
06/23/99 338 - 06/23/99 338 - grid line 2 north grid line L left and rig ###-#### ok r-bar placed SP INSP
|
INSP - Foundation | 6/23/1999 | 6/23/1999 | 6/23/1999 | P | PART |
|
|
|
06/23/99 338 - ###-####//CAISONS GRIDLINE 6 NORTH GRIDLINE N RIGHT & LEFT SP INSP
|
INSP - Concrete | 6/21/1999 | 6/22/1999 | 6/22/1999 | A | PART |
|
|
|
06/22/99 338 - /CAISONS GRIDLINE 2 SOUTH GRIDLINE N LEFT & RIGHT
|
INSP - Foundation | 6/21/1999 | 6/21/1999 | 6/21/1999 | | |
|
|
|
starting 6 foot casons work proceeding on schedule perry i and dave reedar reviewd change in rebar placement on specific detail dave was getting engineer approval on
|
INSP - Concrete | 6/18/1999 | 6/21/1999 | 6/21/1999 | A | PART |
|
|
|
06/21/99 338 - CAISONS GRIDLINE 2 SOUTH GRIDLINE K LEFT & RIGHT sp insp ok
|
INSP - Concrete | 6/18/1999 | 6/18/1999 | 6/18/1999 | P | |
|
|
|
###-#### DAVE// CAISONS GRIDLINE 2 CENTER GRIDLINE N LEFT GRIDLINE 6 SOUTH GRIDLINE N LEFT & RIGHT GRIDLINE 2 NORTH GRIDLINE K LEFT & RIGHT
|
SUPER- Supervisor's review | 6/18/1999 | 6/18/1999 | 6/18/1999 | | |
|
|
|
perry back on site job on track
|
INSP - Concrete | 6/17/1999 | 6/18/1999 | 6/18/1999 | A | PART |
|
|
|
06/18/99 338 - grid line 2 north grid line K right and left ###-#### made ok sp insp appr.
|
INSP - Concrete | 6/17/1999 | 6/17/1999 | 6/17/1999 | P | PART |
|
|
|
grid line 6 south grid line K right grid line L left ###-#### made ok with sp insp approval
|
INSP - Concrete | 6/16/1999 | 6/17/1999 | 6/17/1999 | A | PART |
|
|
|
###-#### dave//caisons gridline 2 center & north gridline m left madeok to pour with sp insp approval
|
SUPER- Supervisor's review | 6/16/1999 | 6/16/1999 | 6/16/1999 | | |
|
|
|
pevious information on spacing of rebar in casons, 2inches is what is on their approved foundation plan. dave readar cought the fact that the code says 3 inches and they are providing letter from engineer allowing clearances other than what the plan states.
|
INSP - Concrete | 6/15/1999 | 6/16/1999 | 6/16/1999 | A | PART |
|
|
|
06/16/99 338 - grid line 6 north on a M line left and right made ok with
|
INSP - Concrete | 6/16/1999 | 6/16/1999 | 6/16/1999 | P | |
|
|
|
###-#### dave// caisons gridline 2 center & north gridline n right Resaigned by 325.
|
SUPER- Supervisor's review | 6/15/1999 | 6/15/1999 | 6/15/1999 | | |
|
|
|
perry informed me that contractor said he did talk to wes and there is no change in plan from two to three inches until an addendum is approved
|
INSP - Concrete | 6/15/1999 | 6/15/1999 | 6/15/1999 | P | PART |
|
|
|
06/15/99 338 - ###-#### DAVE//CAISONS GRIDLINE 6 NORTH J RIGHT GRIDLINE LEFT
|
INSP - Concrete | 6/15/1999 | 6/15/1999 | 6/15/1999 | | PART |
|
|
|
06/15/99 338 - GRID LINE 2 GRID LINE M RIGHT made ok with sp insp approv
|
INSP - Concrete | 6/14/1999 | 6/15/1999 | 6/15/1999 | A | PART |
|
|
|
06/15/99 338 - GRID LINE 2 GRID LINE M RIGHT ok with sp insp app
|
INSP - Concrete | 6/14/1999 | 6/14/1999 | 6/14/1999 | P | PART |
|
|
|
Grid line 6 north and south Grid line J left and right made ok with sp insp approval
|
INSP - Concrete | 6/11/1999 | 6/14/1999 | 6/14/1999 | A | PART |
|
|
|
06/14/99 338 - made ok with sp insppapproval
|
SUPER- Supervisor's review | 6/11/1999 | 6/11/1999 | 6/11/1999 | | |
|
|
|
inspector ww left correction on deficiancies never made effort to talk to job super. did not look for plan addendum so call was incorrect on rebar spacing
|
INSP - Concrete | 6/11/1999 | 6/11/1999 | 6/11/1999 | P | PART |
Wes Worcester
|
|
|
06/11/99 342 - Grid line 6 South M left and right special inspector on s
|
INSP - Foundation | 6/11/1999 | 6/11/1999 | 6/11/1999 | P | PART |
Wes Worcester
|
|
|
06/11/99 342 - ###-####//CAISONS GRID LINE 6 NORTH G LINE RIGHT H LINE LEFT spec insp on site
|
INSP - Foundation | 6/9/1999 | 6/10/1999 | 6/10/1999 | A | PART |
Wes Worcester
|
|
|
06/10/99 342 - ###-####//CAISONS GRIDLINE 6 NORTH & SOUTH GRIDLINE H RIGHT GRIDLINE J LEFT
|
INSP - Concrete | 6/10/1999 | 6/10/1999 | 6/10/1999 | P | PART |
Jim Storey
|
|
|
06/10/99 301 - grid lines 6 north grid line E right F left ###-#### pend
|
Issue PAID IN FULL permit | | | 6/10/1999 | | |
|
|
|
|
Print Occupancy Form | | | 6/10/1999 | | |
|
|
|
|
Telephone call | | | 6/10/1999 | | PASS |
|
|
|
eugene
|
CHANGE STATUS TO (R) | | | 6/10/1999 | | PASS |
|
|
|
came back through, value increased, plan mod.
|
Inspection Record Card- Bld | | | 6/10/1999 | | |
|
|
|
|
INSP - Foundation | 6/9/1999 | 6/9/1999 | 6/9/1999 | P | PART |
Jim Storey
|
|
|
06/09/99 301 - Grid line A and 1 Grid line 6 north and grid D left and E
|
INSP - Foundation | 6/8/1999 | 6/9/1999 | 6/9/1999 | A | FAIL |
Wes Worcester
|
|
|
06/08/99 342 - no answer, spec insp to assess collapsed soils at caison
|
INSP - Foundation | 6/7/1999 | 6/8/1999 | 6/8/1999 | A | FAIL |
Wes Worcester
|
|
|
06/08/99 342 - ###-####//CAISONS*GRID 6 SO H LINE no answer, dirt has ca
|
INSP - Foundation | 6/7/1999 | 6/8/1999 | 6/8/1999 | P | PART |
Wes Worcester
|
|
|
06/08/99 342 - ###-####/no one at site, no answer/CAISONS GRID LINES A G
|
INSP - Foundation | 6/8/1999 | 6/8/1999 | 6/8/1999 | P | PART |
Jim Storey
|
|
|
06/08/99 301 - Dave ###-#### grid line A and 1 north 9 ft. Grid line A a
|
INSP - Concrete | 6/4/1999 | 6/7/1999 | 6/5/1999 | A | PART |
|
|
|
06/07/99 338 - grid line 6 grid line H South left and right madeok to po
|
INSP - Concrete | 6/4/1999 | 6/4/1999 | 6/4/1999 | P | PART |
|
|
|
06/04/99 338 - 3:00 PLEASE ###-#### GRID LINES 6 AND D SOUTH LEFT 6 AND F SOUTH RIGHT AND LEFT made ok to pour with sp inspapproval
|
INSP - Concrete | 6/3/1999 | 6/3/1999 | 6/3/1999 | P | PART |
|
|
|
06/03/99 338 - Dave ###-#### grid line A and 2.9 and 1.1 and .40 ft and grid line C .14 ft grid line 5.4 ft and B .9 ft made ok with sp insp approvals
|
INSP - Concrete | 5/28/1999 | 5/28/1999 | 5/28/1999 | P | PART |
|
|
|
05/28/99 338 - madeok for casson pour with sp insp approvals
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/19/1999 | | PASS |
|
|
|
|
Issue PAID IN FULL permit | | | 5/19/1999 | | |
|
|
|
|
Inspection Record Card- Bld | | | 5/19/1999 | | |
|
|
|
|
Print Occupancy Form | | | 5/19/1999 | | |
|
|
|
|
Telephone call | | | 5/19/1999 | | |
|
|
|
talked to eugene gave dollar amount
|
Routing - PUBLIC WORKS | 5/18/1999 | | 5/18/1999 | | PASS |
|
|
|
PLANS SENT TO BRIAN MURPHY TO REVIEW AND SIGN.
|
Routing - PLAN CHECK | 5/18/1999 | | 5/18/1999 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 5/17/1999 | | 5/18/1999 | | PEND |
|
|
|
|
Plan assigned to (JCM) | 4/16/1999 | | 5/18/1999 | | PASS |
John Menard
|
|
|
|
Routing - PUBLIC WORKS | 5/14/1999 | | 5/17/1999 | | FAIL |
|
|
|
Need ACHD letter.
|
Plan resubmittals requested | | | 5/14/1999 | | PEND |
|
|
|
A COPY OF THE COMMENT LIST FROM THE CONSULTING STRUCTURAL ENGINEER WAS FAXED TO GENE BENNETT, KREIZENBECK CONST. & DAVID BLODGETT, HOSFORD-LARSON-RUDEEN REQUESTING STRUCTURAL REVISIONS.
|
Routing Off Site - STRUCTURAL | 4/16/1999 | | 5/14/1999 | | FAIL |
|
|
|
CONTACTED PDQ TO TAKE PLANS TO OUTSIDE ENG. KMM
|
Plan Reviewer's activity | | | 5/13/1999 | | PASS |
|
|
|
PLANS REVIEWED AND APPROVED, AS DRAWN, FOR THE INSTALLATION OF THE REINFORCED CONCRETE CAISSONS.
|
Routing - PLAN CHECK | 5/3/1999 | | 5/13/1999 | | PEND |
|
|
|
|
Routing - PLUMBING | 4/28/1999 | | 5/3/1999 | | PASS |
|
|
|
4-16-99 HAVE NOT RECEIVED GRADING AND DRAINAGE PLANS FOR GRADING AND DRAINAGE PERMIT, AT THIS TIME. I AM SENDING TO PLUMB. ANY WAY. THERE ARE CIVIL SHEETS WITH THIS SUBMITTAL. PUT NOTE WITH PLANS BEFORE ROUTING TO PLUMB. ABOUT THIS FACT. KMM THIS SET OF PLANS HAS NO PLUMBING SHOWN AND THEREFORE NO PLUMBING HAS BEEN REVIEWED OR APPROVED FOR THIS PROJECT AT THIS TIME. DAR 5/3/99
|
Routing - PLANNING | 4/20/1999 | | 4/28/1999 | | PASS |
|
|
|
x-ref. drh98-0244
|
Routing - FIRE | 4/20/1999 | | 4/20/1999 | | PASS |
|
|
|
NO FIRE CONCERNS AT THIS TIME PER FLOYD VARLEY. DAR 4/20/99
|
Plans ACCEPTED BY PLAN TECH | | | 4/16/1999 | | PASS |
|
|
|
RECEIVED STRUCTURAL UPDATES TO ORIGINAL FOOTING AND FOUNDATION SET, ADDITION OF STAIR/ELVATOR SHAFT DRAWINGS. RECEIVED THREE COPIES OF SHEETS A0.00, S2.01A, S2.02, S2.03, S5.00, S6.03, S7.00, S7.01, S7.02 ROUTED TO JOHN M. FOR FURTER INSTRUCTION. KMM
|
Application received | | | 4/16/1999 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 4/16/1999 | | |
|
|
|
|
Received Certificate of Value | | | 4/16/1999 | | PEND |
|
|
|
SUBMITTED WITH A PROJECT VALUE ONLY. ELEC. PLUMB. MECH. FIRE SPRINKLER N/A. KMM
|
Plan routing begun/NEW & ADDTN | 4/16/1999 | | 4/16/1999 | | |
|
|
|
|
Routing - PUBLIC WORKS | 4/16/1999 | | 4/16/1999 | | FAIL |
|
|
|
DEMO PLAN TO BE REVISED TO REROUTE SEWER SERVICE TO FOSTTER BUILDING, JOHN JOHNSON. DAR 4/20/99 REQUIRES DRAINAGE PLAN REVISION, NEEDS STRUCTURAL ENGINEERING REVIEW ON 20 FT. DEEP RETAING WALL. PER MARLENE SOUTHARD. DAR 4/20/99
|
INSP - Foundation | 8/23/1999 | 8/23/1999 | 3/23/1999 | P | PART |
|
|
|
08/23/99 338 - TOM###-####.BETWEEN N6-G6 & N2-K2.PILE CAPS F6,E6,D6,B2
|
Fee Review-notes | 10/26/1999 | 10/26/1999 | | | |
|
|
|
|
Routing Off Site - STRUCTURAL | 7/14/1999 | | | | |
|
|
|
PLAN MODIFICATION. CONTACTED PDQ TO TAKE PLANS TO OUTSIDE ENG. KMM
|
SUPER- Supervisor's review | 6/18/1999 | | | | |
|
|
|
|