Permit Information
Permit NumberBLD99-01043
StatusFinaled
Name DISCOUNT TIRE COMPANY
Site Address 6200 W FAIRVIEW AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
To make changes to the exterior site, perform selective interior demolition, and to remodel this existing tire store per approved plans and engineering on file and CZC99-0024. Work to include, demolition of the interior restrooms, demolition of the existing mezzanine in the garage area, demolition of the existing stairway from the second story above the sales area, cut new openings in the exterior store front, rear wall and wall between garage and sales area, construct new mansard over front entarace, to install four smoke/heat vents in the garge area, install new storfront system, new windows and doors between the garage and the sales area openings will be protected with roll down fire assemblies, install new coil door to garage area and infill two existing openings with CMU, construct new exit stairs from second story, install new racking system per engineering, construct two new fully accessible restrooms, and Miscelaneous interior finishes. NOTE: This building is NOT Fire sprinklered. (#275-99)*RMH*
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Fee Review-notes1/13/20001/13/20006/20/2000 DONE
BLD-Final5/16/20005/17/20005/17/2000APASS
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 05/16/2000 at 15:27:50. Contact: ###-####. Card to owner. 5/18/00 3:02:42 PM
Letter of compliance  5/17/2000 DONE
Letter of Compliance #18487 issued 5-17-00.
Letter of compliance  5/17/2000 DONE
Letter of Compliance #18487 issued 5-17-00.
BLD-Final1/28/20001/31/20001/31/2000PFAIL
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 01/28/2000 at 15:04:24. Contact: ###-####. c\n seal firestop penetrations 2/1/00 9:04:17 AM
FIRE-Final Inspection1/27/20001/28/20001/28/2000APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 01/27/2000 at 11:58:39. Contact: ###-####.
BLD-Final1/27/20001/28/20001/28/2000PPART
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 01/27/2000 at 12:02:36. Contact: ###-####. ok for temp see c/ notice 1/31/00 8:30:06 AM
Code Occupancy Approval  1/26/2000 FAIL
Temporary signed - posted Check to finish striping and h/c insignia on prkg. spaces.
FIRE-Final Inspection1/21/20001/21/20001/21/2000AFAIL
DetailsRick Jackson
overhead door sill listing; extinguisher; exit sign
FIRE-Alarm Testing1/20/20001/21/20001/21/2000PPASS
DetailsJoe Tawney
alarms tested okay
FIRE-Alarm Testing1/20/20001/20/20001/20/2000PFAIL
DetailsJoe Tawney
Scheduled by a contractor via Hello! on 01/20/2000 at 11:09:08. Contact: ###-####. Final fail approved alarm submittals not on site. 1/20/00 4:12:27 PM
Code Occupancy Approval  1/20/2000 FAIL
Still need to complete stripping, h/c designations and repair the landscaping curbing at the north end of rear parking lot. Currently waiting for cost information to approve amount of bond.
BLD-Wall cover11/30/199911/30/199911/30/1999APART
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 11/30/1999 at 07:29:27. Contact: ###-####. 1hr. Occ. Wall ok, need RC @ 16" oc @ west 1/2, display area lid.
BLD-Wall cover11/29/199911/29/199911/29/1999PFAIL
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 11/29/1999 at 08:13:00. Contact: ###-####. Complete 1hr. Wall to deck, recall.
BLD-Wall cover11/24/199911/24/199911/24/1999AFAIL
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 11/24/1999 at 07:02:18. Contact: ###-####. Need firestop 1hr wall penetration above lid ok to cover exc. As noted.
BLD-Wall cover11/19/199911/19/199911/19/1999PPART
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 11/19/1999 at 09:59:02. Contact: ###-####. Dampers installed, should consult fire prior to cover re: smoke detectors ok to cover walls.
BLD-Conference11/10/199911/10/199911/10/1999PPASS
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 11/10/1999 at 10:16:17. Contact: ###-####. Met. Supt. Keep C/N; rec'd detail for occ. Separation.
BLD-Wall cover10/28/199910/28/199910/28/1999PFAIL
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 10/28/1999 at 08:11:50. Contact: ###-####. C/N; dampers, header, resubmit, etc.
BLD-Footing10/21/199910/22/199910/22/1999AFAIL
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 10/21/1999 at 11:31:09. Contact: ###-####. Need clarify 1hr lid penetrations.
BLD-Framing/Rough-in10/11/199910/11/199910/11/1999PPART
DetailsCarl Dependahl
mitch--- ###-#### fr insp Column supports for steel I-Beam only.
BLD-Framing/Rough-in10/7/199910/8/199910/8/1999PFAIL
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 10/07/1999 at 15:15:00. Contact: ###-####. No plans on site
Issue PAID IN FULL permit  8/16/1999
Telephone call  8/13/1999 MESS
LEFT MESSAGE W/TERESA. THE PLANS ARE READY FOR PICK UP
Routing - PLAN CHECK7/12/1999 7/16/1999 PASS
PLANS/APPL TAKEN TO FRONT DESK  7/16/1999 PASS
Plan resubmittals received  7/16/1999 PEND
RECEIVED PLAN RESUBMITTALS FROM BILL HAUGHEY, ARCHITECTURAL RESOURCE TEAM, FORWARDED SAME TO RON HILL. DAR 7/16/99
Print Pending Permit.LaserJet4  7/16/1999 PASS
Telephone call  7/16/1999
called Bill Haughey 1 ###-####
Inspection Record Card- Bld  7/16/1999
Print Occupancy Form  7/16/1999
Plan assigned to (R_H)4/19/1999 7/16/1999 PASS
Details
07/16/99 10:12:11 RMH - this action updated by action script from <<>> in Case No. BLD99-1043
Telephone call  7/13/1999 FAIL
Called Bill Hoye Architect, discussed our concerns about property lines, told him of the options availble, and to contact April Miller at P & Z.
Routing - FIRE7/7/1999 7/12/1999 PASS
Plan Reviewer's activity  7/7/1999 PASS
still needs fire department approval, will route to fire de[artment.
Routing - PLAN CHECK5/17/1999 7/7/1999 PASS
Plan resubmittals received  7/2/1999
RECEIVED THREE SETS OF REVISED DRAWINGS ONE RESPONSE TO BUILDING REVIEW COMMENTS, AND ONE RESPONSE TO FIRE REVIEW COMMENTS. ROUTED TO RON HILL KMM
Plan Review Completed(1st rev)  5/17/1999
Routing - FIRE5/13/1999 5/17/1999 FAIL
ROOF VENTS AREA TO FLOOR RATIO IS INADEQUATE. DOES NOT INDICATE VENTING IS AUTOMATIC.
Plan Reviewer's activity  5/12/1999 FAIL
faxed and mailed requirements to the architect. Will route to fire department.
Routing - PLAN CHECK4/26/1999 5/12/1999 FAIL
Routing - PUBLIC WORKS4/21/1999 4/26/1999 PASS
Routing - PLANNING4/20/1999 4/21/1999 PASS
x-ref. CZC99-0024
Plans ACCEPTED BY PLAN TECH  4/19/1999 PASS
Plan routing begun/TENANTS  4/19/1999
Route to PLANNING, PUBLIC WORKS, PLAN CHECK and FIRE.
Plan assigned to (MYS)4/16/1999 4/19/1999
DetailsMarlene Southard
Recd Pcfee & Taken To Pln CK  4/16/1999
Application received  4/16/1999
Received Certificate of Value  4/16/1999 PASS