Fee Review-notes | 6/18/2003 | 6/18/2003 | 6/18/2003 | | DONE |
|
|
|
|
Permanent Occupancy | | 1/29/2001 | 1/29/2001 | | DONE |
|
|
|
|
BLD-Final | 1/26/2001 | 1/29/2001 | 1/29/2001 | A | PASS |
Carl Dependahl
|
|
|
|
Permanent occupancy | | | 1/29/2001 | | DONE |
|
|
|
Perm. Occ. Cert. #8549 issued 1-29-01 to the Leisure Villa Apts.
|
FIRE-Final Inspection | 11/16/2000 | 11/17/2000 | 11/17/2000 | A | PASS |
Joe Tawney
|
|
|
Scott Asin ###-#### Reinsp OK for permanant occupancy 11/17/2000 11:56:04 AM
|
Temporary occupancy | | | 10/31/2000 | | PART |
|
|
|
Temp. Occ. Cert. #4072 issued 10-31-00 to the Leisure Villa Apts.
|
BLD-Final | 10/27/2000 | 10/30/2000 | 10/30/2000 | A | FAIL |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 10/27/2000 at 13:55:51. Contact: ###-####.
|
FIRE-Final Inspection | 10/27/2000 | 10/27/2000 | 10/27/2000 | P | PART |
Joe Tawney
|
|
|
###-####. Reinsp OK for temporary occupancy. Paint and letter curbs 10/30/2000 8:06:06 AM
|
BLD-Other | 10/25/2000 | 10/26/2000 | 10/26/2000 | A | PART |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 10/25/2000 at 10:16:55. Contact: ###-####. need all other sigs for finals 10/26/2000 10:29:17 AM
|
FIRE-Final Inspection | 10/25/2000 | 10/25/2000 | 10/25/2000 | P | FAIL |
Joe Tawney
|
|
|
###-####.Final Fail Smoke detectors & signs and striping for FD access 10/26/2000 8:05:49 AM
|
BLD-Energy code compliance | 8/4/2000 | 8/4/2000 | 8/4/2000 | P | PASS |
Carl Dependahl
|
|
|
Mike ###-####; fra 8/4/2000 11:45:24 AM me ok 8/4/2000 11:45:32 AM
|
BLD-Energy code compliance | 8/3/2000 | 8/3/2000 | 8/3/2000 | P | NR |
Carl Dependahl
|
|
|
mike ###-#### energy code
|
BLD-Framing/Rough-in | 7/31/2000 | 7/31/2000 | 7/31/2000 | P | FAIL |
Carl Dependahl
|
|
|
mike ###-#### fr; c/n, draft stops, truss calcs & hip purlin support 7/31/2000 5:08:54 PM
|
BLD-Energy code compliance | 7/31/2000 | 7/31/2000 | 7/31/2000 | P | PART |
Carl Dependahl
|
|
|
mike ###-#### energy code, air-seal ok 7/31/2000 5:09:21 PM
|
BLD-Framing/Rough-in | 6/16/2000 | 6/16/2000 | 6/16/2000 | P | PART |
Tom Arcoraci
|
|
|
SHEETROCK ON THE SOFFIT MIKE ###-#### dry wall on soffia 6/19/00 2:02:26 PM
|
BLD-Framing/Rough-in | 5/30/2000 | 5/31/2000 | 5/31/2000 | P | PART |
Carl Dependahl
|
|
|
###-#### sheer wall and straps 1st fl. ext. "shear" walls. 6/1/00 11:25:30 AM
|
BLD-Foundation | 5/4/2000 | 5/5/2000 | 5/5/2000 | A | PART |
Carl Dependahl
|
|
|
###-#### Poured, appears ok. 5/8/00 9:38:14 AM
|
BLD-Footing | 5/3/2000 | 5/3/2000 | 5/3/2000 | P | PASS |
Tom Arcoraci
|
|
|
###-####
|
Issue PAID IN FULL permit | | | 4/21/2000 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 3/28/2000 | | 4/20/2000 | | |
|
|
|
|
Plan Reviewer's activity | | | 4/20/2000 | | DONE |
|
|
|
|
Print Pending Permit.LaserJet4 | | | 4/20/2000 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/20/2000 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 4/20/2000 | | DONE |
|
|
|
|
Print Pending Permit.LaserJet4 | | | 4/20/2000 | | DONE |
|
|
|
|
Print Occupancy Form | | | 4/20/2000 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 4/20/2000 | | DONE |
|
|
|
|
Telephone call | | | 4/20/2000 | | DONE |
|
|
|
|
Plan assigned to (M_P) | 7/12/1999 | | 4/20/2000 | | PASS |
Mike Phillips
|
|
|
4/20/2000 10:56:41 M_P - activity updated through activity BLDA022 from case BLD99-02086.
|
Plan resubmittals received | | | 4/19/2000 | | DONE |
|
|
|
RECEIVED TWO COPIES OF REVISED SHEETS A1.0, A2.0, A2.1, A8.0, A9.1 AND ONE COPY OF CALCS. ROUTED TO MIKE P. KMM
|
Routing - FIRE | 3/27/2000 | 3/28/2000 | 3/28/2000 | | PASS |
Bill Alexander
|
|
|
Provide water supply letter from Capitol Water with 1,500 gpm available.
|
Routing - FIRE | 12/15/1999 | 12/15/1999 | 12/16/1999 | | FAIL |
|
|
|
BUILDING - Need fire flows of 1500 gpm minimum per UFC.
|
Plan Review Completed(1st rev) | | | 12/16/1999 | | |
|
|
|
BUILDING
|
Plan resubmittals requested | | | 12/15/1999 | | FAIL |
|
|
|
Additional information requested to be submitted for further review.
|
Print Pending Permit.LaserJet4 | | | 12/15/1999 | | FAIL |
|
|
|
Additional information requested to be submitted for further review.
|
Plan resubmittals received | | | 12/2/1999 | | DONE |
|
|
|
RECEIVED PLAN RESUBMITTALS FROM MARK SANDERS ARCHITECTURAL, MECHANICAL AND STRUCTURAL CACULATIONS. 12/2/99 DAR
|
Routing - FIRE | 11/29/1999 | 11/29/1999 | 11/29/1999 | | PASS |
|
|
|
FOR GRADING ONLY AT THIS TIME . KMM NO FIRE FLOWS PROVIDED. NO BUILDING UNTILL PROVIDED.
|
Routing - PLAN CHECK | 11/24/1999 | | 11/29/1999 | | PEND |
|
|
|
|
Plan resubmittals received | | | 11/26/1999 | | DONE |
|
|
|
RECEIVED THREE COPIES OF REVISED SHEET A1.0. ROUTED TO MARLENE. KMM
|
Routing - FIRE | 11/23/1999 | 11/24/1999 | 11/24/1999 | | FAIL |
|
|
|
GRADING - Need fire access plot plan for area. Need info on south new structures blocked lane (bollards). Need fire hydrant locations and water flows verified by water purveyor.
|
Plan Review Completed(1st rev) | | | 11/24/1999 | | FAIL |
|
|
|
GRADING
|
Routing - PLUMBING | 10/15/1999 | 10/15/1999 | 10/18/1999 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 10/12/1999 | 10/12/1999 | 10/15/1999 | | |
|
|
|
Routing to plumbing.
|
Plan Reviewer's activity | | | 10/14/1999 | | FAIL |
|
|
|
Waiting for resubmittals to be submitted for review called and confirmed with Mark Sanders resubmittals have not been submitted for review.
|
Plan resubmittals received | | | 10/14/1999 | | PEND |
|
|
|
RECEIVED PLAN RESUBMITTALS FROM TUMURA AND ASSOCIATES, FORWARDED SAME TO MIKE PHILLIPS. 10/14/99 DAR
|
Routing - PUBLIC WORKS | 10/6/1999 | 10/6/1999 | 10/12/1999 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 9/28/1999 | 9/28/1999 | 10/6/1999 | | DONE |
|
|
|
Routing to P.W.
|
Routing - PUBLIC WORKS | 9/27/1999 | 9/27/1999 | 9/28/1999 | | FAIL |
|
|
|
|
Routing - PLAN CHECK | 9/21/1999 | 9/21/1999 | 9/27/1999 | | DONE |
|
|
|
Routomg to P.W.
|
Routing - PLUMBING | 9/16/1999 | | 9/21/1999 | | FAIL |
|
|
|
|
Routing - PLANNING | 9/9/1999 | 9/9/1999 | 9/16/1999 | | |
|
|
|
|
Routing - PLAN CHECK | 8/12/1999 | | 9/9/1999 | | |
|
|
|
|
Routing - PLANNING | 8/5/1999 | | 8/12/1999 | | FAIL |
|
|
|
need to submit final plans per DR conds. Contacted architect.
|
Telephone call | | | 8/12/1999 | | HOLD |
|
|
|
Talked to Mark Sanders he will be subbmitting new plans reflecting building changes.
|
Routing - PLANNING | 7/30/1999 | | 8/5/1999 | | PASS |
|
|
|
Pending Design Review Approval.
|
Routing - PUBLIC WORKS | 7/23/1999 | | 7/30/1999 | | FAIL |
|
|
|
Failed with Brian Murphy and Bill Colson.
|
Plan Reviewer's activity | | | 7/21/1999 | | |
|
|
|
Removed from hold received application.
|
Plan Reviewer's activity | | | 7/12/1999 | | HOLD |
|
|
|
WAITING FOR ADDITIONAL APPLICATIONS TO BE SUBMITTED.
|
Application received | | | 7/12/1999 | | |
|
|
|
|
Routing - PLAN CHECK | 12/16/1999 | | | | |
|
|
|
routing to fire
|