Permit Information
Permit NumberBLD99-02653
StatusExpired
Name OFFICE ENVIRONMENT COMPANY
Site Address 1063 W BOEING ST
Project NameBOEING WAREHOUSE #7
Customer Number 
ePlanReviewNo
Description
OFFICE ENVIRONMENT COMPANY * INSTALL STEEL RACKING AS MANUFACTURED BY INTERLAKE MATERIALS HANDLING* ENGINEERED BY BEN J. RIEHL, IDAHO LICENSED* LAYOUT PER FLOOR PLAN WITH (2)-1/2 ", HILTI-KB II, PER 3-1/2" x 7-3/4/" X 3/8" BASE PLATE AT EACH COLUMN LEG, OF SUFFICIENT LENGTH TO ALLOW MINIMUM OF 3-1/2" EMBEDMENT INTO EXISTING 6" CONCRETE SLAB. LOAD BEAMS LOCATED AT 78" & 180" TO TOP OF BEAM ABOVE FINISHED FLOOR. INSTALL INDIVIDUAL, MINIMUM 50 SQ. IN. PERMANENT PLAQUE'S, OF SUFFICIENT NUMBER, ALONG EACH LEVEL OF LOAD BEAMS (144" BEAM LENGTH) TO CLEARLY INDICATE MAXIMUM ALLOWABLE LOAD DESIGN OF 5400 LBS PER PAIR OF BEAMS, PER LEVEL. ALL PER CHAPTER 22, DIV. X, 1997 UBC, VOL.2, ENGINEERING, MANUFACTURE'S INSTALLATION INSTRUCTIONS AND APPROVED PLANS ON FILE. PC#703-99/ drs Note: This permit is being done in conjunction with BLD-02619.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIRE-Sprinkler Rough-in5/16/20005/16/20005/16/2000PPART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 05/16/2000 at 09:46:00. Contact: ###-####. Sprinklers ok for R/I. 5/18/00 3:00:59 PM
Issue PAID IN FULL permit  3/20/2000 DONE
PLANS/APPL TAKEN TO FRONT DESK  3/17/2000 PASS
APPROVED AS NOTED AND ATTACHED. ROUTING FOR PERMIT ISSUANCE.
Inspection Record Card- Bld  3/17/2000 DONE
Telephone call  3/17/2000 DONE
called matt gave dollar amount
Plan assigned to (DRS)2/3/2000 3/17/2000 PASS
DetailsDan Stuart
3/17/2000 12:12:26 DRS - activity updated through activity BLDA022 from case BLD99-02653.
Routing - PLAN CHECK3/2/2000 3/16/2000 PASS
APPROVED PLANS FOR TENANT IMPROVEMENT, BLD99-02619, FOR ISSUANCE.
Routing - FIRE3/10/20003/10/20003/10/2000 PASS
DetailsBill Alexander
Routing - FIRE3/7/20003/7/20003/7/2000 FAIL
DetailsBill Alexander
UFC issues to be addressed
Routing - FIRE2/28/20003/2/20003/2/2000 FAIL
DetailsBill Alexander
NEED FIRE SPRINKLER DESIGN INFORMATION WHICH INCLUDES HOSE, COMMODITY CLASSIFICATION, PLANS INDICATING LOCATIONS OF MIXED (IF APPLICABLE), OTHER UFC ARTICLE 81 REQUIREMENTS.
Plan Review Completed(1st rev)  3/2/2000 FAIL
DetailsBill Alexander
Routing - PLAN CHECK2/3/2000 2/26/2000 PEND
Approved per Ben J. Reihl engineering & manufacture's installation instructions. Issuance of permit pending the approval of tenant remodel & expansion being reviewed under separate permit BLD99-02619. Permits will be issued at same time.Routing to Fire Dept.
Pending Assignment by MYS2/3/2000 2/3/2000 DONE
DetailsMarlene Southard
THIS PERMIT ALLOWED TO PROCEED AFTER AN AGREEMENT WAS REACHED WITH NEIGHBORING TENANT PAM OIL. PAM OIL IS NOT BE TO AN H OCCUPANCY.
Plan assigned to (MYS)9/3/1999 9/3/1999 HOLD
DetailsMarlene Southard
PLACED PLANS ON HOLD ALONG WITH BLD99-2619 FOR THE TENANT SPACE. THIS PLAN CANNOT BE PROCESSED WITHOUT APPROVAL AND ISSUANCE OF BLD99-0711 FOR PAM OIL. SEE FAX TO TIM THORNTON AND MATT RHEES.
Plans ACCEPTED BY PLAN TECH9/2/1999 9/2/1999
Application received  9/2/1999
Print Pending Permit.LaserJet4     
Case Summary (BLD)