FIRE-Final Inspection | 5/22/2000 | 5/23/2000 | 5/23/2000 | A | FAIL |
Joe Tawney
|
|
|
jim ###-#### Final fail C/N issued. 5/23/00 2:12:10 PM
|
BLD-Final | 5/22/2000 | 5/23/2000 | 5/23/2000 | A | FAIL |
Carl Dependahl
|
|
|
jim ###-#### Need other sig's. 5/24/00 11:11:50 AM
|
BLD-Framing/Rough-in | 4/27/2000 | 4/28/2000 | 4/28/2000 | A | PART |
Carl Dependahl
|
|
|
Jim ###-#### Rec'd ARch's detail re: 1hr const...ext. side gyp. ok 4/28/00 3:05:31 PM
|
BLD-Framing/Rough-in | 4/27/2000 | 4/27/2000 | 4/27/2000 | P | FAIL |
Carl Dependahl
|
|
|
###-#### Need Arch's detail for 1hr walls. 4/28/00 3:00:39 PM
|
BLD-Framing/Rough-in | 4/24/2000 | 4/25/2000 | 4/25/2000 | P | FAIL |
Carl Dependahl
|
|
|
###-#### Need detail for 1 hr. ext. wall const. 4/26/00 11:16:38 AM
|
BLD-Concrete | 4/20/2000 | 4/21/2000 | 4/21/2000 | P | PART |
Carl Dependahl
|
|
|
###-####\\rebar
|
BLD-Framing/Rough-in | 3/28/2000 | 3/29/2000 | 3/29/2000 | P | PART |
Carl Dependahl
|
|
|
drainage around fd insp--- jim ###-#### cell Drain rock & "filter" installed. 3/30/00 10:49:58 AM
|
BLD-Footing | 3/23/2000 | 3/24/2000 | 3/24/2000 | A | PART |
Carl Dependahl
|
|
|
perimeter insulation around the foundation jim ###-#### Slab insulated 3/24/00 2:02:34 PM
|
BLD-Foundation | 3/17/2000 | 3/20/2000 | 3/20/2000 | A | PART |
Carl Dependahl
|
|
|
JIM ###-#### CELL FOUND Strata onsite for FDN. & cylinders. 3/21/00 4:10:42 PM
|
BLD-Footing | 3/14/2000 | 3/14/2000 | 3/14/2000 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 03/14/2000 at 10:47:24. Contact: ###-####. rebar work in progress special insp. to be on site Pending report & scope of work. "Strata" 3/16/00 11:29:43 AM
|
Telephone call | | | 2/3/2000 | | DONE |
|
|
|
called Kyle Freutel from BRS at ###-#### permit ready
|
Print Occupancy Form | | | 2/3/2000 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 2/3/2000 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 2/3/2000 | | DONE |
|
|
|
|
Routing - FIRE | 2/2/2000 | 2/2/2000 | 2/2/2000 | | PASS |
|
|
|
|
Plan assigned to (M_P) | 9/27/1999 | 9/27/1999 | 2/2/2000 | | PASS |
Mike Phillips
|
|
|
2/2/2000 15:09:12 M_P - activity updated through activity BLDA022 from case BLD99-02888.
|
Routing - PLAN CHECK | 10/25/1999 | | 2/2/2000 | | |
|
|
|
|
Plan Reviewer's activity | | | 2/2/2000 | | DONE |
|
|
|
|
Print Pending Permit.LaserJet4 | | | 2/2/2000 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 2/2/2000 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/2/2000 | | DONE |
|
|
|
|
Plan resubmittals received | | | 2/2/2000 | | DONE |
|
|
|
RECEIVED PLAN RESUBMITTALS FROM BRS ARCHITECTS, FORWARDED SAME TO MIKE PHILLIPS, SHEETS SD1 AND A2, 2 SHEETS EACH. 2/2/00 DAR
|
Plan resubmittals received | | | 2/1/2000 | | PEND |
|
|
|
RECEIVED PLAN RESUBMITTALS FROM BRS ARCHITECTS, KYLE FREUTEL, SHEETS SD1 AND A1. 2/1/00 DAR
|
Plan resubmittals received | | | 12/22/1999 | | PEND |
|
|
|
RECEIVED PLAN RESUBMITTALS FROM BRS ARCHITECTS, KYLE FREUTEL, FORWARDED SAME TO MIKE PHILLIPS. 12/22/ 99 DAR
|
Telephone call | | | 12/1/1999 | | DONE |
|
|
|
Talked to Bill Strite. He has taken over project while Kyle is on vacation. I told him of the requirement to classify the products per Table 3-D and 3-E and he said he would do that and submit the info.
|
Meeting | | | 11/24/1999 | | DONE |
|
|
|
Had a meeting with Kyle Freutel and Bill Alexander to discuss the requirements for classification of the products to be stored and/or used in the building. Informed him that he needed to determine what hazard class, amount, location in building to comply with UBC/UFC Tables 3-D and 3-E.
|
Plan resubmittals received | | | 11/16/1999 | | PEND |
|
|
|
RECEIVED MEMO FROM BRS ARCHITECTS, KYLE FREUTEL, FROWARDED SAME TO MARLENE SOUTHARD. 11/16/99 DAR
|
Plan Reviewer's activity | | | 11/12/1999 | | FAIL |
|
|
|
More data needed in design. Hazardous chemicals sufficient to warent professional design for building classification. Left message for Kyle and Clinton to call me.
|
Plan resubmittals received | | | 11/10/1999 | | PEND |
|
|
|
WRITTEN RESUBMITTALS RECEIVED FROM BRS ARCHITECTS, KYLE FREUTEL, FORWARDED SAME TO MIKE PHILLIPS. 11/10/99 DAR
|
Plan resubmittals received | | | 11/8/1999 | | PEND |
|
|
|
RECEIVED PLAN RESUBMITTALS FOR BILL ALEXANDER, FORWARDED SAME TO BILL FROM BRS ARCHITECTS. 11/8/99 DAR
|
Plan resubmittals received | | | 11/5/1999 | | PEND |
|
|
|
RECEIVED PLAN RESUBMITTALS FROM BRS ARCHITECTS, KYLE FREUTEL, FORWARDED SAME TO MIKE PHILLIPS. 11/5/99 DAR
|
Routing - FIRE | 10/20/1999 | 10/20/1999 | 10/25/1999 | | FAIL |
|
|
|
Need fire access, hydrant location, storage information (commodities, classifications, elevations).
|
Plan Review Completed(1st rev) | | | 10/25/1999 | | FAIL |
|
|
|
|
Plan resubmittals requested | | | 10/19/1999 | | FAIL |
|
|
|
ADDITIONAL INFORMATION REQUESTED FOR FURTHER REVIEW.
|
Print Pending Permit.LaserJet4 | | | 10/19/1999 | | FAIL |
|
|
|
ADDITIONAL INFORMATION REQUESTED FOR FOLLOW UP REVIEW.
|
Routing - PLAN CHECK | 10/6/1999 | | 10/19/1999 | | FAIL |
|
|
|
10/7/99 Mike I routed plans to fire for parking lot expansion and grading for the storage shed. KMM
ROUTING TO FIRE DEPARTMENT FOR THERE REVIEW. MJP
|
Routing - PLANNING | 10/6/1999 | | 10/6/1999 | | PASS |
|
|
|
No design review approval necessary - A zone. TKW
Cup99-00057 has been approved. BGN
|
Routing - PLUMBING | 9/30/1999 | | 10/6/1999 | | PASS |
|
|
|
no plumbing associated with this project
|
Routing - PUBLIC WORKS | 9/28/1999 | 9/28/1999 | 9/29/1999 | | PASS |
|
|
|
|
Case Summary (BLD) | | | 9/28/1999 | | PEND |
|
|
|
|
Fee Review-notes | 9/27/1999 | 9/27/1999 | 9/27/1999 | | DONE |
|
|
|
LINDA THIS PERMIT WAS SUBMITTED ALONG WITH THE PARKING LOT. I CONTACTED KYLE TO SEPARATE INTO TWO SEPARATE PERMITS. INITIAL PROJECT VALUE WHICH INCLUDED BUILDING AND PARKING LOT, WAS $135,750 ELECT. $8,000 MECH. $12,000 PLUMB. AND FIRE SPRINKLER N/A. THANKS KMM
REVISED CERT. OF VALUE FOR BLD99-02888 IS PROJECT VALUE $40,400 ELECT. $1,200 MECH. $3,000 PLUMB. AND FIRE SPRINKLER N/A BUILDING PERMIT # FOR THE PARKING LOT IS BLD99-02906. KYLE ADDED A GRADING AND DRAINAGE PERMIT FOR THE STORAGE BUILDING. THE BLD# FOR GRADING IS BLD99-02907 KMM
|
Plan routing begun/NEW & ADDTN | | | 9/27/1999 | | |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 9/27/1999 | | PEND |
|
|
|
REQUIRES PRE-ENGINEERED BUILDING PLANS. CONTACTED KYLE OF THIS NEED. WILL ROUTE TO PW, P&Z, AND PLAN CHECK. HOPEFULLY PRE-ENGINEERED PLANS WILL BE HERE BY THEN. PROJECT CONSITS OF THREE PROJECTS. THE NEW STORAGE BUILDING BLD99-02888, THE GRADING AND DRAINAGE FOR THE NEW BUILDING, BLD99- , AND THE PARKING LOT EXPANSION, BLD99- KMM
|
Received Certificate of Value | | | 9/27/1999 | | PEND |
|
|
|
SUBMITTED PLANS FOR STORAGE BUILDING AND PARKING LOT NEED TO SEPARATE OUT INTO DIFFERENT PERMITS. KMM KYLE ALSO REQUESTED GRADING PERMIT. HAD HIM FAX OVER THREE CERT. OF VALUE. ONE FOR BUILDING, ONE FOR PARKING LOT EXPANSION AND ONE GRADING PERMIT FOR THE NEW BUILDING. ALL WILL BE ROUTED ON THE SAME SET OF PLANS. KMM
|
Application received | | | 9/24/1999 | | |
|
|
|
|
Case Summary (BLD) | | | | | |
|
|
|
|
Routing - PLAN CHECK | 2/2/2000 | | | | PEND |
|
|
|
|