Case Summary (BLD) | | | 10/5/2016 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 10/12/2011 | | DONE |
|
|
|
|
Letter of compliance | | | 5/21/2002 | | DONE |
|
|
|
Letter of Compliance #22485 issued 4-8-02.
|
Override - Parcel Holds | | | 11/29/2001 | | |
|
|
|
|
Temporary occupancy | | | 11/29/2001 | | DONE |
|
|
|
extended temp occ 11/28/01 new expiration will be 2/28/02 per Tim and Jenifer aml
|
Conference | 1/26/2001 | 1/26/2001 | 1/26/2001 | | PART |
|
|
|
Temp. Occ. Cert. #4068 extended for 30 days as per Tim Hogland.
|
Override - Parcel Holds | | | 1/25/2001 | | |
|
|
|
|
Fee Review-notes | 10/15/1999 | 10/15/1999 | 11/27/2000 | | DONE |
|
|
|
additional values from subs
|
Override - Parcel Holds | | | 11/3/2000 | | |
|
|
|
|
Override - Parcel Holds | | | 10/30/2000 | | |
|
|
|
|
FIRE-Final Inspection | 10/26/2000 | 10/27/2000 | 10/27/2000 | A | PASS |
Rick Jackson
|
|
|
MARK ###-#### FIRE FN
|
BLD-Final | 10/26/2000 | 10/27/2000 | 10/27/2000 | A | PART |
Jim Storey
|
|
|
FN OCC-- MARK ###-#### need special insp. stamped letter/achd/all others perm sign off. 10/27/2000 5:24:55 PM
|
Code Occupancy Approval | | | 10/27/2000 | | FAIL |
|
|
|
Bonded for Tempoarary - ($5,000) - landscaping, striping. Need to submit plans for add'l prkg. lot and landscaping.
|
Temporary occupancy | | | 10/27/2000 | | PART |
|
|
|
Temp. Occ. Cert. #4068 issued 10-27-00 to the Beaver River Power Co. Bldg. for the shell and core.
|
FIRE-Final Inspection | 10/25/2000 | 10/26/2000 | 10/26/2000 | A | FAIL |
Rick Jackson
|
|
|
Mark ###-#### need knox box 10/26/2000 12:02:15 PM
|
Override - Parcel Holds | | | 10/26/2000 | | |
|
|
|
|
Override - Parcel Holds | | | 10/26/2000 | | |
|
|
|
|
Override - Parcel Holds | | | 10/25/2000 | | |
|
|
|
|
BLD-Framing/Rough-in | 10/19/2000 | 10/20/2000 | 10/20/2000 | P | CANC |
Rick Jackson
|
|
|
###-####
|
FIRE-Final Inspection | 10/19/2000 | 10/20/2000 | 10/20/2000 | P | CANC |
Rick Jackson
|
|
|
###-#### called by mark brown
|
FIRE-Final Inspection | 10/13/2000 | 10/19/2000 | 10/19/2000 | A | FAIL |
Rick Jackson
|
|
|
MIKE-- ###-#### FIRE FN tested alarms - notification okay; need duct detectors for AHU shutdown installed; //need landings at exits; need sprinklers installed in room by restrooms; heads replaced that are painted 10/19/2000 3:18:22 PM
|
BLD-Concrete | 10/16/2000 | 10/16/2000 | 10/16/2000 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 10/16/2000 w/ bldr...need eng's reports, etc
|
FIRE-Conference | 9/28/2000 | 9/29/2000 | 9/29/2000 | A | PART |
Rick Jackson
|
|
|
###-#### talked about requiremments for an upcoming event. told him all requirements for shell and any other approval per building official. tenent plans haven't been approved yet. 9/29/2000 10:28:58 AM
|
Print Occupancy Form | | | 9/27/2000 | | DONE |
|
|
|
|
BLD-Framing/Rough-in | 9/26/2000 | 9/26/2000 | 9/26/2000 | P | PART |
Jim Storey
|
|
|
r/i-- mark ###-#### framing on restarooms and fur out for kitchen ok unclear as to permit numbers and city has approved plan talked with dan s. for clearity in plan review. 9/26/2000 5:29:25 PM
|
Routing - PLANNING | 4/14/2000 | | 5/4/2000 | | DONE |
|
|
|
2nd review.
|
Routing - PLANNING | 5/3/2000 | | 5/4/2000 | | DONE |
|
|
|
COMPLETE RESUBS
|
Routing - PLAN CHECK | 5/4/2000 | | 5/4/2000 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/4/2000 | | PASS |
|
|
|
|
Print Occupancy Form | | | 5/4/2000 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 5/4/2000 | | DONE |
|
|
|
|
Telephone call | | | 5/4/2000 | | DONE |
|
|
|
called John from Hummel Architects at ###-#### and Ken Beck ###-####
|
Issue PAID IN FULL permit | | | 5/4/2000 | | DONE |
|
|
|
|
Plan assigned to (CJW) | 10/19/1999 | | 5/4/2000 | | PASS |
Carl Westfall
|
|
|
5/4/00 13:31:06 CJW - activity updated through activity BLDA022 from case BLD99-03134.
|
Routing - FIRE | 4/27/2000 | 4/27/2000 | 4/27/2000 | | PASS |
Bill Alexander
|
|
|
2nd review.
|
Routing - FIRE | 4/21/2000 | 4/25/2000 | 4/25/2000 | | |
Bill Alexander
|
|
|
Need fire sprinkler water supply information.
|
Plan Review Completed(1st rev) | | | 4/25/2000 | | |
Bill Alexander
|
|
|
|
Routing - PLUMBING | 4/19/2000 | | 4/21/2000 | | DONE |
|
|
|
RESUBMITTALS
|
Routing - PLUMBING | 4/14/2000 | | 4/21/2000 | | DONE |
|
|
|
2nd review.
|
Routing - PLANNING | 4/18/2000 | | 4/19/2000 | | |
|
|
|
Modification to DR has not been submitted.
|
Routing - PUBLIC WORKS | 4/14/2000 | | 4/18/2000 | | DONE |
|
|
|
2nd review.
|
Routing - PLAN CHECK | 11/10/1999 | | 4/14/2000 | | PASS |
|
|
|
Drawings dead until the redesign was received on March 31, 2000. UBC plan review completed April 14, 2000.
|
Plan Reviewer's activity | | | 4/11/2000 | | PASS |
|
|
|
Second UBC plan review started April 11, 2000 and finished April 14, 2000. The drawings were approved with conditions. See the conditions list.
|
Plan resubmittals received | | | 3/31/2000 | | DONE |
|
|
|
New drawings were submitted for review because of significant changes in the project. All previous approvals are void. Drawings need to be routed back to all applicable agencies.
|
Routing Off Site - STRUCTURAL | 12/14/1999 | | 12/21/1999 | | PASS |
|
|
|
SENT ARCHTICTURAL PLANS TO CONSULANTING STRUCTURAL ENGINEER. 12/14/99 DAR
|
Plan resubmittals received | | | 12/16/1999 | | DONE |
|
|
|
Received a letter from Hummel Architects addressing a structural comment faxed to them on 12/13/99. 12/15/99
|
Additional plans submitted | | | 12/14/1999 | | DONE |
|
|
|
ONE SET OF ADDITIONAL PLANS WERE SUBMITTED BY HUMMEL ARCHITECTS, FORWARDE SAME TO CARL WESTFALL. 12/14/99 DAR
CCARL ADVISED DAVE R. TO SEND THEM TO CH2MHILL
|
Routing Off Site - STRUCTURAL | 11/26/1999 | | 12/13/1999 | | PEND |
|
|
|
CONTACTED PDQ TO TAKE REVISED STRUCT. CALCULATION FOR REVISED DIAPHRAGM WEIGHTS AND 1ST. FLOOR SHEAR WALL CALCS ADDED. PHASE II OF THE SEISMIC UPGRADE KMM
|
Telephone call | | | 11/29/1999 | | DONE |
|
|
|
Called the architect and left a voice mail message. The plastic skylights are too big. Told him that he had to change the material or reduce the size of the skylight.
|
Plan resubmittals received | | | 11/19/1999 | | PEND |
|
|
|
RECEIVED PLAN RESUBMITTALS FROM HUMMEL ARCHITECTS, JIM OTRADOSKY, FORWARDED SAME TO CARL WESTFALL. 11/19/99 DAR
|
Routing - FIRE | 11/9/1999 | | 11/10/1999 | | |
|
|
|
|
Routing - PLAN CHECK | 10/29/1999 | | 11/9/1999 | | |
|
|
|
|
Plan Reviewer's activity | | | 11/8/1999 | | |
|
|
|
UBC plan review started Nov. 8, 1999 and finished Nov. 9, 1999. A response from the architect is required. See the conditions list. (this review void 4-14-00)
|
Routing - PLUMBING | 10/28/1999 | | 10/29/1999 | | |
|
|
|
discharge from sump must be connected to a 4" waste line, increase water line to 1 1/4" between water heater and urinal branch, verify condition of existing sewer service with field inspector.
|
Routing - PLANNING | 10/27/1999 | | 10/28/1999 | | |
|
|
|
DRH99-00199 and CVA99-00022
|
Routing - PUBLIC WORKS | 10/19/1999 | | 10/26/1999 | | |
|
|
|
|
Pending Assignment by MYS | 10/15/1999 | | 10/19/1999 | | DONE |
Marlene Southard
|
|
|
|
Plan routing begun/TENANTS | | | 10/19/1999 | | DONE |
|
|
|
Route to PUBLIC WORKS, PLANNING, PLUMBING, PLAN CHECK and FIRE.
|
Plans ACCEPTED BY PLAN TECH | | | 10/18/1999 | | PASS |
|
|
|
RECEIVED THREE COPIES OF PLANS. ONE FOR OUTSIDE ENG. TWO FOR INHOUSE ROUTING. NO STRUCT. CALCS SUBMITTED. KMM
|
Received Certificate of Value | | | 10/18/1999 | | PASS |
|
|
|
|
Application received | | | 10/15/1999 | | |
|
|
|
|
Routing - PLAN CHECK | 4/25/2000 | | | | PEND |
|
|
|
|
Routing - PLAN CHECK | 4/28/2000 | | | | PEND |
|
|
|
|