Permit Information
Permit NumberBLD99-03348
StatusFinaled
Name INDEPENDENT SCHOOL DISTRICT #1
Site Address 3701 E LAKE FOREST DR
Project Name 
Customer Number 
ePlanReviewNo
Description
TRAIL WIND ELEMENTARY SCHOOL ADDITION * TO CONSTRUCT A 9500 SQ FT ONE STORY, TYPE VN, FULLY FIRE SPRINKLERED CLASSROOM ADDITION PER APPROVED PLANS AND ATTACHMENTS.PC#884-99 MLO FIRE SPRINKLERS USED FOR AREA.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Fee Review-notes6/12/20036/12/20036/12/2003 DONE
Permanent Occupancy 10/15/200110/15/2001 DONE
Details
BLD-Final10/12/200110/15/200110/15/2001PPASS
DetailsSteven Webb
Final affidavit letter from MTI was provided plus fire caulking in mechanical is ok--. 10/15/2001 2:50:11 PM
Permanent occupancy  10/15/2001 DONE
Perm. Occ. Cert. #8869 issued 10-15-01 to Trail Wind Elementary School (addn.)
FIRE-Final Inspection8/29/20018/29/20018/29/2001APASS
DetailsRick Jackson
Added by Inspector: 409 On 8/29/2001 9:24:22 AM
Telephone call  6/25/2001 DONE
Talked w/Steve Maber ###-#### x117 re: status on temp. occ. & he will follow up
Fee Review-notes8/8/20008/8/200010/24/2000 DONE
BLD-Final8/17/20008/18/20008/18/2000APART
DetailsRuss Owen
Jim ###-#### Need final inspections reports mti/ engineer, also fire caulk upper mec room 2 hr wall. other signatures req. job crd. 8/18/2000 1:14:43 PM
Temporary occupancy  8/18/2000 PART
Temp. Occ. Cert. #4053 issued 8-18-00 to Trail Wind Elementary School.
FIRE-Final Inspection8/15/20008/16/20008/16/2000APART
DetailsRick Jackson
Jim ###-#### Fire sprinkler this is for a temp please call before going out///// temp occupancy approved - sprinkler system must be converted to dry system by 8/30/00 per letter from the acrchitect and Dave Miller approval 8/16/2000 2:05:36 PM
FIRE-Alarm Testing8/14/20008/14/20008/14/2000PPASS
DetailsRick Jackson
###-####--JIM ALARM TEST alarms working per plans 8/15/2000 11:15:13 AM
Code Occupancy Approval  8/14/2000 PASS
LOOKS OK FINAL SIGNED OFF.
FIRE-Alarm Testing8/8/20008/8/20008/8/2000PFAIL
DetailsRick Jackson
Jim ###-#### tested the alarms: batteries need to be 55 amp; trouble on NACs activate the alarms; complete the wiring/horns in attice; F/S dampers not tested - not accessible; need exit sign; 2 hr and 1 hr wall penetrations 8/9/2000 8:40:30 AM
BLD-Framing/Rough-in7/28/20007/31/20007/31/2000APASS
DetailsRuss Owen
JIM ###-#### CEILING GRID 7/31/2000 12:51:16 PM
BLD-Framing/Rough-in7/11/20007/12/20007/12/2000PPASS
DetailsRuss Owen
ceiling grid Jim ###-####
BLD-Framing/Rough-in7/10/20007/11/20007/11/2000ACANC
DetailsRuss Owen
ceiling grid jim ###-####
BLD-Framing/Rough-in7/5/20007/5/20007/5/2000PFAIL
DetailsRuss Owen
###-#### fire wall Fresh air not permitted in parapet 7/7/00 12:57:56 PM
BLD-Framing/Rough-in6/29/20006/30/20006/30/2000AFAIL
DetailsRuss Owen
firewall jim ###-#### penetrations 6/30/00 3:21:48 PM
BLD-Framing/Rough-in6/23/20006/26/20006/26/2000AFAIL
DetailsRuss Owen
jim ###-#### cover C/N posted 6/26/00 2:59:47 PM
BLD-Framing/Rough-in6/8/20006/9/20006/9/2000APART
DetailsRuss Owen
jim ###-#### engineer to examine trusses and inside tails. 6/13/00 10:00:10 AM
BLD-Foundation5/16/20005/17/20005/17/2000APART
DetailsTom Arcoraci
###-#### Spec. insp. on site. 5/17/00 2:07:15 PM
BLD-Concrete5/15/20005/15/20005/15/2000PPART
DetailsRuss Owen
SPECIAL INSPECTION\\###-#### DOUG Subject to special inspection. 5/16/00 10:44:36 AM
BLD-Foundation3/16/20003/17/20003/17/2000APASS
DetailsWes Worcester
late am ###-#### or ###-#### pager Doug Stem walls ok 3/20/00 10:23:07 AM
BLD-Foundation3/15/20003/16/20003/16/2000AFAIL
DetailsCarl Dependahl
LATE AM PLEASE\\###-####\\###-#### Rained out? recall. 3/17/00 10:28:09 AM
BLD-Footing3/14/20003/15/20003/15/2000ANR
DetailsRuss Owen
336/4082 or ###-####
BLD-Foundation3/14/20003/15/20003/15/2000ANR
DetailsRuss Owen
###-####
BLD-Footing3/13/20003/14/20003/14/2000PPASS
DetailsWes Worcester
Scheduled by a contractor via Hello! on 03/13/2000 at 16:26:27. Contact: ###-####. East elevation done & south elevation ok from 85 to 120 on Gride 5.6 than Grid C from 4.6 to 5.6 3/16/00 11:25:33 AM
BLD-Footing3/10/20003/13/20003/13/2000PPASS
DetailsWes Worcester
Scheduled by a contractor via Hello! on 03/10/2000 at 13:56:57. Contact: . 85' + 20' @ vesitbule ok. 3/14/00 1:44:44 PM
Routing Off Site - A.C.H.D2/16/20002/16/20002/16/2000 DONE
no impact fee due 1-26-00 plans stamped David Szpilett from ACHD
Issue PAID IN FULL permit  2/16/2000 DONE
Plan assigned to (MLO)11/29/1999 2/1/2000 DONE
DetailsMike Otto
PLANS/APPL TAKEN TO FRONT DESK  2/1/2000 PASS
Inspection Record Card- Bld  2/1/2000 DONE
Print Occupancy Form  2/1/2000 DONE
Telephone call  2/1/2000 DONE
left mess for tarrie that permit is ready
Routing - PLAN CHECK1/28/2000 1/31/2000 PASS
Routing - PUBLIC WORKS1/27/2000 1/28/2000 DONE
Routing - FIRE1/21/20001/21/20001/26/2000 PASS
PLANS SENT BACK TO PLAN CHECK
Routing - PLAN CHECK1/18/2000 1/20/2000 FAIL
CORRECTIONS MAILED AND FAXED TO ARCHITECT. MLO
Plan resubmittals requested  1/20/2000 FAIL
BUILDING CODE CORRECTIONS
Routing Off Site - STRUCTURAL1/12/2000 1/18/2000 PASS
SENT RESUBMITTALS TO CONSULTANTING ENGINEER VIA PDQ. 1/12/00 DAR
Plan resubmittals received  1/18/2000 DONE
RECEIVED PLAN RESUBMITTALS FROM TARRIE WAGNER OF ARMSTRONG ARCHITECTS AT 3:54 0N 1/14/00 LOGGED IN THESE PLANS AS RECEIVED ON 1/18/00 BECAUSE OF TIME RECEIVED AND AND HOLIDAY ON THE FOLLOWING MONDAY. PLANS RECEIVED CONSISTED OF PPLAN REVIEW COMMENTS/CORRECTIONSFOR ARCHITECTURAL, ELECTRICAL, AND MECHANICAL, FORWARDED SAME TO MIKE OTTO. 1/18/00 DAR
Plan resubmittals received  1/12/2000 DONE
RECEIVED TWO COPIES OF REVISED SHEET S2.0, ONE COPY OF SUPPLEMENTAL STRUCTURAL CALCULATIONS. ROUTED TO MIKE O. KMM
Routing - FIRE12/2/199912/6/199912/6/1999 FAIL
WATER SUPPLY INFORMATION REQUIRED FOR FIRE SPRINKLER SYSTEM.

11/23/99 PUBLIC WORKS IS READY FOR THE PLANS TO REREVIEW THEM. WHEN THE FIRE DEPARTMENT HAS REVIEWED THEM PW WAS READY FOR THEM ON 11/15/99. DAR
Plan Review Completed(1st rev)  12/6/1999 PEND
plans sent back to plan check
Plan resubmittals requested  12/3/1999 FAIL
STRUCTURAL CORRECTIONS FAXED TO ARCHITECT. MLO
Routing Off Site - STRUCTURAL11/9/1999 12/3/1999 FAIL
CONTACTED PDQ TO TAKE PLANS TO OUTSIDE ENG. KMM
RECEIVED STRUCTUAL REVIEW LETTER BY CH2MHILL DATED 12/2/99. ROUTED TO MIKE OTTO. KMM
Plan resubmittals requested  12/2/1999 FAIL
PLAN REVIEW CORRECTIONS
Routing - PLAN CHECK11/29/1999 12/2/1999 FAIL
CORRECTIONS MAILED AND FAXED TO ARCHITECT. MLO
Routing - PLANNING11/23/1999 11/24/1999 DONE
Routing - PLUMBING11/10/1999 11/23/1999 PASS
Routing - PUBLIC WORKS11/8/199911/8/199911/10/1999 PEND
REQUIRES DRAINAGE PLAN PER BRIAN MURPHY. 11/10/99 DAR
Plans ACCEPTED BY PLAN TECH  11/9/1999 DONE
RECEIVED THRID SET OF PLANS. SOILS REPORT IS IN PROJECT MANUEL. KMM
Case Summary (BLD)  11/8/1999 PEND
Application received  11/8/1999  
Plans ACCEPTED BY PLAN TECH  11/8/1999 PEND
REQUIRES 3RD SET OF PLANS FOR ENGINEER. REQUIRES SOILS REPORT. 2000 LBS USED FOR SOIL BEARING PRESSURE. SCOTT SPJUTE STATED THAT A ZONING CERTIFICATE IS REQUIRED FOR THIS PROJECT. 11/8/99 DAR