Permit Information
Permit NumberELE00-02468
StatusFinaled
Name ROMAR ELECTRIC
Site Address 1256 E EXCHANGE ST
Project NameGOWEN BUSINESS PARK
Customer Number 
ePlanReview 
Description
6/29/00-$222,962.00-Electrical wiring per boise city approved plans-Initial cert. of value.mps 3-6-fnal cert 209,837.00 value went down.. lh
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Telephone call  3/2/2001 DONE
DetailsKim Harrison
Final1/18/20011/19/20011/19/2001APASS
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 01/18/2001 at 15:53:24. Contact: ###-####. ok final 1/19/2001 12:05:48 PM
DOC - Permit Finaled1/19/20011/19/20011/19/2001PPASS
DetailsMike Kinnear
Added by Inspector: 412 On 1/19/2001 12:06:17 PM
Final11/29/200011/29/200011/29/2000PPART
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 11/29/2000 at 10:10:07. Contact: ###-####. 324 & 412 went out ok temp occ. per tim hogland. corr. no third party testing on remote radiator & 4 vent fans on roof. no inspection on back up battery inverters work not completed. 11/29/2000 4:06:40 PM
Permanent Service11/20/200011/21/200011/21/2000PPART
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 11/20/2000 at 15:56:16. Contact: ###-####. this inspection was for temp occ. failed need third party testing strickers on 4 vent fans on roof & on radiator for generator 11/21/2000 4:22:53 PM
Temporary Service11/14/200011/14/200011/14/2000PFAIL
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 11/14/2000 at 08:15:02. Contact: ###-####. this inspection is for temp. occ. failed corr. nec 110-3(b)3rd party listing for 4 vent fans on roof, generator remote radiator, & ground clamps for main service nec110-26(b) working space for radiator disconnect 42" 11/14/2000 4:42:09 PM
Final11/9/200011/13/200011/13/2000ANR
DetailsMike Kinnear
temp occ\###-#### need to locate 3rd party testing strickers 11/13/2000 4:08:01 PM no strickers on 4 roof vent fans & radiator for generator 11/13/2000 4:09:38 PM
Permanent Service9/26/20009/27/20009/27/2000APASS
DetailsMike Kinnear
Kelly Smith ###-#### Third party lable found ok 9/29/00 11:10:22 AM
Permanent Service9/22/20009/25/20009/25/2000AFAIL
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 09/22/2000 at 13:01:48. Contact: ###-####. Correction need third party lable on generator. 9/26/00 11:36:03 AM
Electrical Rough-In9/19/20009/19/20009/19/2000PPASS
DetailsMike Kinnear
KELLY --###-#### R/I Ok cover ceiling 9/21/00 4:25:52 PM
Permanent Service9/11/20009/11/20009/11/2000PPASS
DetailsMike Kinnear
kelly ###-#### pager per ser P/S U/G reconnect ok 9/12/00 11:00:58 AM
Electrical Rough-In7/11/20007/12/20007/12/2000APART
DetailsJack Frank
###-#### Restroom & storage ok 7/13/00 11:25:54 AM
Electrical Rough-In6/29/20006/30/20006/30/2000APART
DetailsJack Frank
Kelly SMith ###-#### walls ok 6/30/00 3:09:28 PM
Application received  6/29/2000  
Issue & PRINT permit  6/29/2000 DONE