Final | 10/9/2000 | 10/9/2000 | 10/9/2000 | P | PASS |
Pat Lass
|
|
|
###-#### john reinspection key is on fireplace vent
|
Final | 9/21/2000 | 9/21/2000 | 9/21/2000 | P | FAIL |
Mike Kinnear
|
|
|
John; ###-####. Key on fireplace vent Corrections NEC 110-26-430-102(B)-370-21 9/22/00 2:01:43 PM
|
Permanent Service | 7/18/2000 | 7/18/2000 | 7/18/2000 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 07/18/2000 at 07:59:11. Contact: ###-####. P/S ok U/G new 7/19/00 10:07:56 AM
|
Rough-In Permanent Service | 7/17/2000 | 7/17/2000 | 7/17/2000 | P | PART |
Mike Kinnear
|
|
|
###-#### reinspection OK R/I cover house only- corrections posted for garage Ufer ground #4 CU 20' PVC 310-5 18"- house service need access to Ufer ground terminal. 7/18/00 1:59:03 PM
|
Rough-In Permanent Service | 7/12/2000 | 7/13/2000 | 7/13/2000 | A | FAIL |
Jack Frank
|
|
|
###-#### John Correction posted twice no response needs concrete encased electrode at garage, uncover PVC u/g to garage, outlet required for wall space MB could not locate ground at house. 7/14/00 2:17:03 PM
|
Issue & PRINT permit | | | 7/12/2000 | | DONE |
|
|
|
|
Application received | | | 7/12/2000 | | |
|
|
|
|