Final | 1/4/2001 | 1/5/2001 | 1/5/2001 | P | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 01/04/2001 at 08:25:18. Contact: ###-####. ok final 1/5/2001 1:18:41 PM
|
Electrical Rough-In | 1/5/2001 | 1/5/2001 | 1/5/2001 | P | PASS |
Mike Kinnear
|
|
|
Added by Inspector: 412 On 1/5/2001 1:17:37 PM ok cover ceiling
|
DOC - Permit Finaled | 1/5/2001 | 1/5/2001 | 1/5/2001 | P | PASS |
Mike Kinnear
|
|
|
Added by Inspector: 412 On 1/5/2001 1:18:17 PM
|
Final | 12/27/2000 | 12/28/2000 | 12/28/2000 | A | FAIL |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 12/27/2000 at 15:18:36. Contact: ###-####. job not ready people have moved in t/w tri state they to have all ceiling tile removed and the people moved out 12/28/2000 10:47:07 AM
|
Final | 12/22/2000 | 12/26/2000 | 12/26/2000 | P | FAIL |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 12/22/2000 at 14:55:36. Contact: ###-####. corr. bcc all ceiling tile must be removed for inspection bcc all outlets must be accessalbe for inspection 12/26/2000 1:25:19 PM
|
Electrical Rough-In | 12/8/2000 | 12/8/2000 | 12/8/2000 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 12/08/2000 at 10:20:55. Contact: ###-####. walls ok 12/8/2000 4:09:36 PM
|
Electrical Rough-In | 12/7/2000 | 12/7/2000 | 12/7/2000 | P | FAIL |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 12/07/2000 at 09:41:58. Contact: ###-####. corr.nec348-13,348-10,350-18,300-4 (2)(d) bcc all make up to be complete at ri inspect. 12/7/2000 4:32:23 PM
|
Application received | | | 12/5/2000 | | |
|
|
|
|
Issue & PRINT permit | | | 12/5/2000 | | DONE |
|
|
|
|