Final | 5/23/2003 | 5/27/2003 | 5/27/2003 | A | PASS |
Pat Lass
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
DOC - Permit Finaled | 5/27/2003 | 5/27/2003 | 5/27/2003 | A | PASS |
Pat Lass
|
|
|
Finaled by inspector at 5/27/2003 9:46:44 AM
|
Electrical Rough-In | 5/19/2003 | 5/19/2003 | 5/19/2003 | P | PART |
Pat Lass
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Annette Moore
ANOP 5/19/2003 3:53:01 PM
|
Final | 4/29/2003 | 4/30/2003 | 4/30/2003 | A | PART |
Pat Lass
|
|
|
mark ; Phone #: ###-#### Internet Inspection Request from: Annette Moore
Partial T/O ANOP 4/30/2003 8:41:20 AM
|
Electrical Rough-In | 4/23/2003 | 4/23/2003 | 4/23/2003 | P | PART |
Pat Lass
|
|
|
MARK CELING; Phone #: ###-#### Internet Inspection Request from: Darla Downs
anop 4/23/2003 4:27:16 PM
|
Electrical Rough-In | 4/18/2003 | 4/18/2003 | 4/18/2003 | P | PART |
Pat Lass
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Annette Moore
anop 4/18/2003 2:43:27 PM
|
Electrical Rough-In | 4/7/2003 | 4/7/2003 | 4/7/2003 | P | PART |
Pat Lass
|
|
|
###-####
as noted on print 4/7/2003 3:15:41 PM
|
Final | 3/10/2003 | 3/10/2003 | 3/10/2003 | P | PASS |
Tim McCullough
|
|
|
MARK TEMP FINAL FOR OCC; Phone #: ###-#### Internet Inspection Request from: Darla Downs
temp. occ. ph.2 ok 3/10/2003 1:59:56 PM
|
Electrical Rough-In | 2/25/2003 | 2/25/2003 | 2/25/2003 | P | PART |
Pat Lass
|
|
|
ceiling
; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
as noted on print 2/25/2003 3:12:35 PM
|
Electrical Rough-In | 2/4/2003 | 2/5/2003 | 2/5/2003 | A | PART |
Pat Lass
|
|
|
###-####
noted area on print 2/5/2003 12:00:57 PM
|
Electrical Rough-In | 1/30/2003 | 1/31/2003 | 1/31/2003 | A | PART |
Pat Lass
|
|
|
###-####
area noted on print 1/31/2003 9:51:59 AM
|
Electrical Rough-In | 1/24/2003 | 1/24/2003 | 1/24/2003 | P | CANC |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
|
Electrical Rough-In | 1/22/2003 | 1/23/2003 | 1/23/2003 | A | PART |
Pat Lass
|
|
|
MARK; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
Noted area on print 1/23/2003 11:08:14 AM
|
Electrical Rough-In | 1/13/2003 | 1/13/2003 | 1/13/2003 | P | PART |
Pat Lass
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
area noted on print 1/13/2003 2:37:59 PM
|
Electrical Rough-In | 12/31/2002 | 12/31/2002 | 12/31/2002 | P | PART |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
noted area on print 12/31/2002 2:19:51 PM
|
Electrical Rough-In | 12/20/2002 | 12/23/2002 | 12/23/2002 | A | PASS |
Tim McCullough
|
|
|
###-####
ri/walls/ok 12/23/2002 10:36:59 AM
|
Electrical Rough-In | 11/21/2002 | 11/21/2002 | 11/21/2002 | P | PART |
Pat Lass
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
noted area on print 11/21/2002 4:18:59 PM
|
Final | 7/31/2002 | 7/31/2002 | 7/31/2002 | P | PART |
Pat Lass
|
|
|
TEMP OCCUP. ###-#### MARK
Phase 1 T/O Ok 7/31/2002 3:15:23 PM
|
Electrical Rough-In | 7/8/2002 | 7/8/2002 | 7/8/2002 | P | PASS |
Pat Lass
|
|
|
mark ###-#### r/i
reception area ok 7/8/2002 3:45:36 PM
|
Electrical Rough-In | 6/28/2002 | 7/1/2002 | 7/1/2002 | A | PART |
Jack Frank
|
|
|
MARK ###-#### basement and bishop rm ceilings 7/1/2002 10:41:18 AM
|
Electrical Rough-In | 6/12/2002 | 6/12/2002 | 6/12/2002 | P | PASS |
Pat Lass
|
|
|
###-#### MARK
Narthex and reception 101 ceiling ok 6/12/2002 6:11:06 PM
|
Electrical Rough-In | 6/6/2002 | 6/6/2002 | 6/6/2002 | P | PART |
Pat Lass
|
|
|
r/i mark ###-####
Platform ok 6/6/2002 4:24:02 PM
|
Electrical Rough-In | 6/3/2002 | 6/3/2002 | 6/3/2002 | P | PART |
Jim Schmer
|
|
|
###-#### MARK 3rd flr ceiling, hall 1st & basement, part. 6/3/2002 12:34:17 PM
|
Electrical Rough-In | 5/24/2002 | 5/24/2002 | 5/24/2002 | P | PART |
Pat Lass
|
|
|
###-#### MARK
told mark that they must remove ceiling tiles for inspection in rooms that I could not see to inspect, and not to install tile in the future prior to inspection. 5/24/2002 5:04:43 PM
|
Electrical Rough-In | 5/8/2002 | 5/9/2002 | 5/9/2002 | A | NR |
Pat Lass
|
|
|
###-####
protection of mc cable 5/9/2002 1:48:28 PM
|
Electrical Rough-In | 5/9/2002 | 5/9/2002 | 5/9/2002 | P | PART |
Joe Ray
|
|
|
CEILING ###-#### MARK west side sant. 5/9/2002 5:08:26 PM
|
Rough-In Permanent Service | 4/16/2002 | 4/16/2002 | 4/16/2002 | P | PASS |
Marv Burrus
|
|
|
###-#### MARK. west sanctuary wall r/i. 4/16/2002 1:45:40 PM
|
Electrical Rough-In | 4/11/2002 | 4/11/2002 | 4/11/2002 | P | PASS |
Marv Burrus
|
|
|
ceiling ###-#### mark. lobby/entry r/i, 4/11/2002 2:18:47 PM
|
Electrical Rough-In | 3/28/2002 | 3/29/2002 | 3/29/2002 | A | PASS |
Marv Burrus
|
|
|
mark ###-#### r/i . 1st floor: hall 141 walls r/i.
2nd floor; hard-lid ceilings r/i. 3/29/2002 9:23:57 AM
|
Electrical Rough-In | 3/21/2002 | 3/22/2002 | 3/22/2002 | A | PASS |
Marv Burrus
|
|
|
###-#### mark. 1st floor; hard-lid ceiling r/i.. bishop's house walls r/i. 3/22/2002 10:42:40 AM
|
Electrical Rough-In | 3/8/2002 | 3/11/2002 | 3/11/2002 | A | PASS |
Marv Burrus
|
|
|
###-#### MARK. sanctuary walls r/i. 3/11/2002 9:41:16 AM
|
Electrical Rough-In | 2/26/2002 | 2/26/2002 | 2/26/2002 | P | PASS |
Jim Schmer
|
|
|
2nd floor walls\\###-#### walls only 2/26/2002 1:16:09 PM
|
Electrical Rough-In | 2/6/2002 | 2/6/2002 | 2/6/2002 | P | PART |
Marv Burrus
|
|
|
###-####. 1st floor; bathrm walls r/i. basemnt walls r/i. 2/6/2002 4:24:57 PM
|
ELE-Aging Inspection | 1/28/2002 | 1/28/2002 | 1/28/2002 | | NR |
Marv Burrus
|
|
|
no inspections requested 1/28/2002 7:54:17 AM
|
ELE-Aging Inspection | 11/28/2001 | 11/28/2001 | 11/28/2001 | | NR |
Marv Burrus
|
|
|
still under construction 11/28/2001 10:30:46 AM
|
Electrical Rough-In | 9/21/2001 | 9/21/2001 | 9/21/2001 | P | PASS |
Marv Burrus
|
|
|
ground insp mark- ###-#### .ufer ground and underslab conduit in church basement. 9/21/2001 3:15:33 PM
|
Electrical Rough-In | 8/22/2001 | 8/22/2001 | 8/22/2001 | P | PART |
Marv Burrus
|
|
|
mark ###-#### unground. pvc conduit in trench; fire-pump circuit. 8/22/2001 2:51:26 PM
|
Permanent Service | 8/14/2001 | 8/15/2001 | 8/15/2001 | A | PART |
Marv Burrus
|
|
|
Mark ###-####. connection for power, check on ufer grounding completion.
p/s u r romar ele #2180-0k 8/15/2001 2:31:02 PM
|
Electrical Rough-In | 8/13/2001 | 8/13/2001 | 8/13/2001 | P | PART |
Marv Burrus
|
|
|
MARK ###-#### R/I. basement hard-lid ceiling r/i 8/13/2001 3:03:49 PM
|
Electrical Rough-In | 7/18/2001 | 7/18/2001 | 7/18/2001 | P | PART |
Marv Burrus
|
|
|
underground Mark ###-####. service laterial underground p.v.c.. in trench, ok. 7/18/2001 1:20:24 PM
|
Electrical Rough-In | 6/28/2001 | 6/28/2001 | 6/28/2001 | P | PASS |
Jim Schmer
|
|
|
Mark ###-####
|
Application received | | | 6/27/2001 | | |
|
|
|
|
Issue & PRINT permit | | | 6/27/2001 | | DONE |
|
|
|
|