Final | 9/4/2001 | 9/4/2001 | 9/4/2001 | P | PASS |
Jack Frank
|
|
|
fn tim- ###-#### re-insp fn ok 9/4/2001 1:11:30 PM
|
DOC - Permit Finaled | 9/4/2001 | 9/4/2001 | 9/4/2001 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 9/4/2001 1:11:33 PM
|
Final | 8/31/2001 | 8/31/2001 | 8/31/2001 | P | NR |
Jack Frank
|
|
|
fn insp jim ###-#### called needs disconnect for furnaces 8/31/2001 3:53:03 PM
|
Rough-In Permanent Service | 8/1/2001 | 8/1/2001 | 8/1/2001 | P | PASS |
Jack Frank
|
|
|
###-#### r/i ok p/s o/h new ok 8/1/2001 4:12:53 PM
|
Rough-In Permanent Service | 7/31/2001 | 7/31/2001 | 7/31/2001 | P | FAIL |
Jack Frank
|
|
|
###-#### cor. and do not cover posted called 210-70(2), 300-4, 336-16, 210-52(c) (1) outlet spacing right and left of kit. sink both units,110-3(b) and 110-14(b) needs to use listed tool for crimp sleves 8/1/2001 10:02:07 AM
|
Issue & PRINT permit | | | 7/31/2001 | | DONE |
|
|
|
|
Application received | | | 7/31/2001 | | |
|
|
|
|