Final | 8/28/2001 | 8/29/2001 | 8/29/2001 | A | PASS |
Joe Ray
|
|
|
Scheduled by a contractor via Hello! on 08/28/2001 at 18:13:47. Contact: ###-####. p/s ug r ok called i.p. 8/29/2001 9:25:57 AM
|
DOC - Permit Finaled | 8/29/2001 | 8/29/2001 | 8/29/2001 | A | PASS |
Joe Ray
|
|
|
Finaled by inspector at 8/29/2001 9:23:59 AM
|
Rough-In Permanent Service | 8/27/2001 | 8/28/2001 | 8/28/2001 | A | FAIL |
Marv Burrus
|
|
|
chip ###-#### r/i & ser. nec: 331-11: pvc conduit shall be supported within 3ft of cabinet
nec: 350-18: flex metal conduit secured @intervals of 41/2ft. nec: 110-12: openings in boxes shall be closed. cables shall be inclosed in box of 1 hour fire-rated wall. 8/28/2001 11:56:00 AM
|
Issue & PRINT permit | | | 8/27/2001 | | DONE |
|
|
|
|
Application received | | | 8/27/2001 | | |
|
|
|
|