ELE-Aging Inspection | 12/26/2001 | 12/26/2001 | 12/26/2001 | | PASS |
Joe Ray
|
|
|
|
DOC - Permit Finaled | 12/26/2001 | 12/26/2001 | 12/26/2001 | A | PASS |
Joe Ray
|
|
|
Finaled by inspector at 12/26/2001 7:56:58 AM
|
Electrical Rough-In | 9/26/2001 | 9/26/2001 | 9/26/2001 | P | PASS |
Joe Ray
|
|
|
###-#### pool
|
Electrical Rough-In | 9/21/2001 | 9/21/2001 | 9/21/2001 | P | PART |
Jack Frank
|
|
|
bond insp for pool- dan -cell ###-#### partial cover only bond ok shall not cover pool light end of pool 9/21/2001 1:51:13 PM
|
Final | 9/18/2001 | 9/19/2001 | 9/19/2001 | A | FAIL |
Jack Frank
|
|
|
fn dan-- ###-#### swim pool u/g for pool shall be 18 inches (680-10) 300-5 for other areas shall bond 680-22 , and clearence for pool panel 110-26 also not ready 9/19/2001 11:54:56 AM
|
Issue & PRINT permit | | | 9/18/2001 | | DONE |
|
|
|
|
Application received | | | 9/18/2001 | | |
|
|
|
|