Final | 11/14/2001 | 11/14/2001 | 11/14/2001 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 11/14/2001 at 09:18:39. Contact: ###-####. ok 11/14/2001 4:59:02 PM
|
DOC - Permit Finaled | 11/14/2001 | 11/14/2001 | 11/14/2001 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 11/14/2001 4:59:04 PM
|
Final | 11/12/2001 | 11/12/2001 | 11/12/2001 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 11/12/2001 at 01:06:12. Contact: ###-####. cor. posted called 110-26(d) lighting for panels in warehouse 11/13/2001 12:58:49 PM
|
Permanent Service | 11/7/2001 | 11/8/2001 | 11/8/2001 | A | PASS |
Jack Frank
|
|
|
###-#### KAY ok to set meter
needs to bond hot and cold 11/8/2001 1:17:29 PM
|
Rough-In Permanent Service | 11/7/2001 | 11/7/2001 | 11/7/2001 | P | FAIL |
Joe Ray
|
|
|
Scheduled by a contractor via Hello! on 11/07/2001 at 06:20:08. Contact: ###-####. grounding and bonding of transformer and panel conference4 11/7/2001 1:21:42 PM
|
Electrical Rough-In | 11/2/2001 | 11/5/2001 | 11/5/2001 | A | CANC |
Mike Kinnear
|
|
|
t grid ceiling\\###-#### contractor cancelled 11/5/2001 9:32:42 AM
|
Electrical Rough-In | 11/5/2001 | 11/5/2001 | 11/5/2001 | P | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 11/05/2001 at 09:29:41. Contact: ###-####. OK COVER CEILING ONLY 11/5/2001 3:07:38 PM
|
Electrical Rough-In | 11/2/2001 | 11/2/2001 | 11/2/2001 | P | FAIL |
Mike Kinnear
|
|
|
###-#### corrections NEC 348-13 & 300-11(a) - note 2 first year app. doing work on the no journeyman 11/2/2001 2:30:28 PM
|
Electrical Rough-In | 10/11/2001 | 10/12/2001 | 10/12/2001 | A | PART |
Jack Frank
|
|
|
###-#### R\I FOR WALLS only ok 10/12/2001 11:09:40 AM
|
Electrical Rough-In | 10/4/2001 | 10/5/2001 | 10/5/2001 | P | NR |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 10/04/2001 at 22:07:03. Contact: ###-####. This is at 1256 west end of building 10/5/2001 4:27:41 PM
|
Application received | | | 10/4/2001 | | |
|
|
|
|
Issue & PRINT permit | | | 10/4/2001 | | DONE |
|
|
|
|