PostCard Mailed | | | 10/17/2002 | | SENT |
|
|
|
PostCard has been mailed requesting inspection.
|
Final | 12/3/2001 | 12/3/2001 | 12/3/2001 | P | FAIL |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 12/03/2001 at 07:49:27. Contact: ###-####. bond or ground water called contractor 12/3/2001 4:23:30 PM
|
Final | 11/28/2001 | 11/28/2001 | 11/28/2001 | P | FAIL |
Jack Frank
|
|
|
###-#### kathy this is for a p/s corrections noted to contractor by phone problen deration of over 3 current carrying conductors in a raceway 310-15, and 250-148 electrician did not have any idea of what I explained to him will have to meet with him 11/28/2001 5:03:42 PM
|
Permanent Service | 11/13/2001 | 11/13/2001 | 11/13/2001 | P | FAIL |
Jack Frank
|
|
|
###-#### cathy called no correction posted need access 310-15 derate wires and follow manufactures instructions no conductors to exit top of panel 11/13/2001 5:48:01 PM
|
Issue & PRINT permit | | | 11/13/2001 | | DONE |
|
|
|
|
Application received | | | 11/13/2001 | | |
|
|
|
|