Final | 3/7/2003 | 3/7/2003 | 3/7/2003 | P | PASS |
Jack Frank
|
|
|
ERIC; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok 3/7/2003 1:55:02 PM
|
DOC - Permit Finaled | 3/7/2003 | 3/7/2003 | 3/7/2003 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 3/7/2003 1:55:07 PM
|
Final | 3/6/2003 | 3/6/2003 | 3/6/2003 | P | FAIL |
Jack Frank
|
|
|
george; Phone #: ###-#### Internet Inspection Request from: Annette Moore more corrections posted box fill island and desk area in dinning off kit, and grd wiremold box island called $42.00 fee due 3/6/2003 3:58:09 PM
|
Final | 3/5/2003 | 3/5/2003 | 3/5/2003 | P | FAIL |
Jack Frank
|
|
|
###-#### eric cor. posted art.100 bathrooms, 240-24(e) no overcurrent devices shall be installed in dwelling bathrooms, 210-8(a)(1) gfci for all recept outlets in bathrooms needs shower trim M bath, and gfci for elevator pit recept, correction for low voltage phone in elevator cabinet shall have same volt rating as high volt 300-3(c) met with contractor 3/5/2003 2:47:19 PM
|
Final | 3/3/2003 | 3/4/2003 | 3/4/2003 | A | FAIL |
Jack Frank
|
|
|
eirc; Phone #: ###-#### Internet Inspection Request from: Darla Downs job not ready no correction posted because not ready conference with contractor needs gfci in a number of locations outlets for all counters in kit. and dinning areas see jf for info 3/4/2003 10:06:04 AM
|
Change Status to I | | | 3/3/2003 | | DONE |
|
|
|
ok per mike to put into the issue mode so they can get a final inspection
|
Telephone call | | | 10/18/2002 | | DONE |
|
|
|
received post card. Work still in progress. Permit extended from 10/18/02
|
Issue permit | | | 10/18/2002 | | DONE |
|
|
|
|
PostCard Mailed | | | 10/17/2002 | | SENT |
|
|
|
PostCard has been mailed requesting inspection.
|
PostCard Mailed | | | 9/29/2002 | | SENT |
|
|
|
PostCard has been mailed requesting inspection.
|
Rough-In Permanent Service | 2/25/2002 | 2/26/2002 | 2/26/2002 | A | PASS |
Joe Ray
|
|
|
MIKE ###-#### p/s ug n ok 2/26/2002 11:03:45 AM
|
Electrical Rough-In | 1/16/2002 | 1/17/2002 | 1/17/2002 | A | PART |
Jack Frank
|
|
|
###-#### mech. rm upstairs and elevator eqiup. rm 1/17/2002 10:02:21 AM
|
Electrical Rough-In | 11/19/2001 | 11/19/2001 | 11/19/2001 | P | PASS |
Marv Burrus
|
|
|
###-#### ERIC STEP LIGHTING. step-lighsting r/i ok for concreted pour. 11/19/2001 4:02:24 PM
|
Electrical Rough-In | 11/15/2001 | 11/16/2001 | 11/16/2001 | A | CANC |
Jack Frank
|
|
|
OUT SIDE STEP LIGHTING ###-#### ERIC ERIC CALLED TO CANC THIS INSPECTION FOR 11-16-01 ///DLD
|
Issue & PRINT permit | | | 11/15/2001 | | DONE |
|
|
|
|
Application received | | | 11/15/2001 | | |
|
|
|
|