Final | 1/22/2003 | 1/22/2003 | 1/22/2003 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ok 1/22/2003 4:38:37 PM
|
DOC - Permit Finaled | 1/22/2003 | 1/22/2003 | 1/22/2003 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 1/22/2003 4:38:42 PM
|
Final | 1/21/2003 | 1/21/2003 | 1/21/2003 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung cor. posted met with owner 250.148 terminate all equip grds in switch box together, 300.14 short grdwires 1/21/2003 3:29:04 PM
|
Final | 9/16/2002 | 9/17/2002 | 9/17/2002 | A | FAIL |
Jack Frank
|
|
|
###-#### cor. and do not cover posted called left message250.148, and 250.8 grd light fixtures with approved screws or clips, 250.104(C) bond building using a lug ,not a nutand bolt with 2 washers, 210.70 needs switch and light for back door of shop, 300.14 cut wires too short at boxes, 334.30 secure romex within 8 inches of plastic boxes and 12 inches where boxes have romex connectors 9/17/2002 11:21:59 AM
|
Permanent Service | 7/19/2002 | 7/19/2002 | 7/19/2002 | P | PASS |
Jack Frank
|
|
|
scott---###-#### home or cell ###-#### no r/i
p/s u/g new ok shop in back of house 7/19/2002 4:57:17 PM
|
Application received | | | 2/5/2002 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 2/5/2002 | | DONE |
|
|
|
|