Temporary Service | 3/12/2002 | 3/12/2002 | 3/12/2002 | P | PASS |
Mike Kinnear
|
|
|
###-#### BRYAN
t/s u/g n ok 3/12/2002 1:42:48 PM
|
DOC - Permit Finaled | 3/12/2002 | 3/12/2002 | 3/12/2002 | P | PASS |
Mike Kinnear
|
|
|
Finaled by inspector at 3/12/2002 1:42:51 PM
|
Final | 2/6/2002 | 2/7/2002 | 2/7/2002 | A | FAIL |
Jack Frank
|
|
|
###-#### BRIAN cor. and $42.00 fee due posted called 250.53(g) grd rod driven at less than 45 degrees 110.3(b) needs square D breakers 358.10 emt not approved in dirt without protection, 200.6 shall not not I D 6 or smaller neutral 2/7/2002 11:33:06 AM
|
Issue & PRINT permit | | | 2/6/2002 | | DONE |
|
|
|
|
Application received | | | 2/6/2002 | | |
|
|
|
|