Telephone Call | | | 10/23/2002 | | DONE |
|
|
|
|
Permanent Service | 4/10/2002 | 4/10/2002 | 4/10/2002 | P | PASS |
Jack Frank
|
|
|
###-####
p/s u/g new ok 4/10/2002 4:16:02 PM
|
DOC - Permit Finaled | 4/10/2002 | 4/10/2002 | 4/10/2002 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 4/10/2002 4:16:06 PM
|
Permanent Service | 4/9/2002 | 4/9/2002 | 4/9/2002 | P | FAIL |
Jack Frank
|
|
|
###-#### cor. posted called 250.64(C) shall not splice GEC in lug 4/9/2002 5:54:02 PM
|
Permanent Service | 4/3/2002 | 4/3/2002 | 4/3/2002 | P | FAIL |
Jack Frank
|
|
|
for an emmission test van--allison- ###-#### cor. posted called 250.24 shall terminate
GEC to grounded conductor at p/s useing manufactures means there is no connection between at time of inspection 4/3/2002 2:33:09 PM
|
Application received | | | 3/29/2002 | | |
|
|
|
|
Issue & PRINT permit | | | 3/29/2002 | | |
|
|
|
|