Owner Supplied Equipment | 5/1/2002 | | 2/10/2004 | | DONE |
|
|
|
|
Second Notification | 5/8/2003 | 5/8/2003 | 6/13/2003 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | | 9/20/2002 | 5/8/2003 | | DONE |
|
|
|
|
Final | 7/24/2002 | 7/25/2002 | 7/25/2002 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 07/24/2002 at 10:55:48. Contact: ###-####. ok 7/25/2002 2:51:38 PM
|
DOC - Permit Finaled | 7/25/2002 | 7/25/2002 | 7/25/2002 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 7/25/2002 2:51:53 PM
|
Final | 7/16/2002 | 7/17/2002 | 7/17/2002 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 07/16/2002 at 11:15:17. Contact: ###-####. new corrections will be posted will meet with contractor 2:30 pm 07/17/02 7/17/2002 2:52:20 PM
|
Final | 7/17/2002 | 7/17/2002 | 7/17/2002 | P | PART |
Jack Frank
|
|
|
conference with contractor conference ok temp occupancy ok note shall not use X-RAY equipment until correction made and inspection completed 7/17/2002 6:13:52 PM
|
Final | 7/9/2002 | 7/10/2002 | 7/10/2002 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 07/09/2002 at 14:19:35. Contact: ###-####. cor. posted called 110.14 copper and alum under small splice 406.4 recepts not secure, and set back in plates, welding cable not approved for installation in wireway or raceway, install all covers on wireway and provide bushing where x-ray cables exit covers call Jack for more info 7/10/2002 5:44:47 PM
|
Electrical Rough-In | 6/19/2002 | 6/20/2002 | 6/20/2002 | A | PASS |
Joe Ray
|
|
|
Scheduled by a contractor via Hello! on 06/19/2002 at 09:06:45. Contact: ###-####. ceiling ok for cover 6/20/2002 11:10:49 AM
|
Electrical Rough-In | 5/20/2002 | 5/21/2002 | 5/21/2002 | A | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 05/20/2002 at 10:24:15. Contact: ###-####.
U/G Ok 5/21/2002 12:52:00 PM
|
Electrical Rough-In | 5/15/2002 | 5/16/2002 | 5/16/2002 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 05/15/2002 at 15:50:10. Contact: ###-####. walls ok shall use approved metal raceway or cable for x ray units for patient care area u/g 5/16/2002 2:38:59 PM
|
Application received | | | 5/1/2002 | | |
|
|
|
|
Issue & PRINT permit | | | 5/1/2002 | | |
|
|
|
|