Final | 6/19/2002 | 6/20/2002 | 6/20/2002 | A | PASS |
Jack Frank
|
|
|
ELEN ###-#### PLEASE CALL BEFORE SO ELEN CAN MEET YOU THERE ok 6/20/2002 10:53:19 AM
|
Permanent Service | 6/20/2002 | 6/20/2002 | 6/20/2002 | A | PASS |
Jack Frank
|
|
|
p/s o/h rec. ok
|
DOC - Permit Finaled | 6/20/2002 | 6/20/2002 | 6/20/2002 | A | PASS |
Jack Frank
|
|
|
Finaled by inspector at 6/20/2002 10:53:54 AM
|
Permanent Service | 6/10/2002 | 6/10/2002 | 6/10/2002 | P | FAIL |
Jack Frank
|
|
|
for homeowner call 1st before insp- ###-####-ellen all correcdtion s not made called need to grd to u/g water pipe within 5 ft of where it enters or verify that there is less than 10 ft of metal u//g water pipe in contact with earth 6/10/2002 5:01:39 PM
|
Final | 5/28/2002 | 5/29/2002 | 5/29/2002 | A | NH |
Tim McCullough
|
|
|
ellen ###-#### call 1stc
called 9:45 am & 2:24 pm 5/29/2002 4:10:47 PM
|
Electrical Rough-In | 5/8/2002 | 5/9/2002 | 5/9/2002 | P | PART |
Jack Frank
|
|
|
JERRY ###-#### CONF ONLY met with contractor went over corrections, contractor said the code is stupid 5/9/2002 3:08:04 PM
|
Final | 5/7/2002 | 5/8/2002 | 5/8/2002 | A | FAIL |
Jack Frank
|
|
|
call first 20 min. for access ###-#### cor. posted called 250.52 or 104 grd or bond, 300.10 bond bushing for all R E washers110.26 clearence dedicated space headrm 230.28 BBC U bolt guy kit, what is grd or bond wire at sub panel, that should all be done p/s 5/8/2002 11:04:43 AM
|
Permanent Service | 5/6/2002 | 5/7/2002 | 5/7/2002 | P | NH |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 05/06/2002 at 14:30:58. Contact: ###-####. no access called contractor will reschedule 5/7/2002 4:39:02 PM
|
Application received | | | 5/6/2002 | | |
|
|
|
|
Issue & PRINT permit | | | 5/6/2002 | | |
|
|
|
|