Final | 7/3/2002 | 7/5/2002 | 7/5/2002 | A | NH |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 07/03/2002 at 16:57:09. Contact: ###-####. no access 7/5/2002 10:06:44 AM
|
Final | 7/5/2002 | 7/5/2002 | 7/5/2002 | P | PASS |
Jack Frank
|
|
|
final ok no card at job site
|
DOC - Permit Finaled | 7/5/2002 | 7/5/2002 | 7/5/2002 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 7/5/2002 2:58:03 PM
|
Final | 7/2/2002 | 7/2/2002 | 7/2/2002 | P | FAIL |
Jack Frank
|
|
|
TODD ###-#### cor. posted 314.16 box fill island counters, 410.8 needs globe for closet fixture, 406.8 needs bubble covers all outside outlets, called left message 7/2/2002 3:37:15 PM
|
Electrical Rough-In | 5/17/2002 | 5/17/2002 | 5/17/2002 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 05/17/2002 at 11:09:53. Contact: ###-####. insideside soffits ok 5/17/2002 4:50:51 PM
|
Rough-In Permanent Service | 5/14/2002 | 5/15/2002 | 5/15/2002 | A | FAIL |
Jack Frank
|
|
|
###-#### TODD cor. not made 300.4 all locations 5/15/2002 2:11:08 PM
|
Electrical Rough-In | 5/15/2002 | 5/15/2002 | 5/15/2002 | P | PASS |
Jack Frank
|
|
|
r/i- todd ###-#### r/i ok 7 units
p/s ug new ok 5/15/2002 4:12:43 PM
|
Rough-In Permanent Service | 5/14/2002 | 5/14/2002 | 5/14/2002 | P | FAIL |
Jack Frank
|
|
|
r/i & ser/ todd ###-#### cor. posted called 250.148 terminate all grds at boxes together, 300.4 nail plates and 1 1/4 110.3(B) gutter manufactures states use R T hubs not sealing locknuts 5/14/2002 4:33:43 PM
|
Issue & PRINT permit | | | 5/14/2002 | | |
|
|
|
|
Application received | | | 5/14/2002 | | |
|
|
|
|