Final | 10/17/2002 | 10/18/2002 | 10/18/2002 | A | CANC |
Jack Frank
|
|
|
code 0975 and 0976 ###-#### vivian--cancel per vivian
|
Final | 10/2/2002 | 10/2/2002 | 10/2/2002 | P | PASS |
Jack Frank
|
|
|
duplex 0975 0976garage code; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ok both units 10/2/2002 5:38:36 PM
|
DOC - Permit Finaled | 10/2/2002 | 10/2/2002 | 10/2/2002 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 10/2/2002 5:38:41 PM
|
Electrical Rough-In | 6/21/2002 | 6/21/2002 | 6/21/2002 | A | PART |
Jack Frank
|
|
|
net with contractor at job site to go over correction posted
|
Rough-In Permanent Service | 6/21/2002 | 6/21/2002 | 6/21/2002 | P | PASS |
Jack Frank
|
|
|
###-#### VIVIAN r/i ok both units
p/s u/g new ok 6/21/2002 5:49:43 PM
|
Rough-In Permanent Service | 6/20/2002 | 6/20/2002 | 6/20/2002 | P | FAIL |
Jack Frank
|
|
|
cor. posted called 110.3(B) replace cut neutral bus both sub panels, and replace all 2,3,4 gang boxes with broken out internal cable clamps 110.26(F)(1)(a)shall move water piping, or sub panel for dedicated space below panel, 300.4 300.14 6 inches lenght of free conductor kit. in road front unit 6/20/2002 4:58:47 PM
|
Application received | | | 6/11/2002 | | |
|
|
|
|
Issue & PRINT permit | | | 6/11/2002 | | DONE |
|
|
|
|