Information based on query as of Saturday, July 20, 2024.
Permit Information
Permit NumberELE02-02003
StatusFinaled
Name EXTREME ELECTRIC
Site Address 9124 W DONNYBROOK CT
Project Name 
Customer Number 
ePlanReview 
Description
jetted tub
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/12/20028/12/20028/12/2002PPASS
DetailsTim McCullough
Scheduled by a contractor via Hello! on 08/12/2002 at 06:56:33. Contact: ###-####.
final/ok 8/12/2002 2:52:38 PM
DOC - Permit Finaled8/12/20028/12/20028/12/2002PPASS
DetailsTim McCullough
Finaled by inspector at 8/12/2002 2:53:02 PM
DOC - Permit Finaled8/12/20028/12/20028/12/2002PPASS
DetailsTim McCullough
Finaled by inspector at 8/12/2002 2:52:42 PM
Electrical Rough-In7/3/20027/3/20027/3/2002PPASS
DetailsJack Frank
r/i ok corrections made
Electrical Rough-In7/2/20027/2/20027/2/2002AFAIL
DetailsJack Frank
Scheduled by a contractor via Hello! on 07/02/2002 at 06:42:12. Contact: ###-####. corrections not made, needs 11/4 inch for cables, and new violation 314.43 no nails in non metallic boxes as code states called 7/2/2002 12:20:27 PM
Electrical Rough-In7/2/20027/2/20027/2/2002PFAIL
DetailsJack Frank
r/i- rowdy ###-#### called all corrections not made still needs 11/4 inch for cables $45.00 reinspection fee due 7/2/2002 5:19:20 PM
Electrical Rough-In7/1/20027/1/20027/1/2002PFAIL
DetailsJack Frank
r/i rody ###-#### cor. posted called 314.43, 300.4 11/4 and nail plates, 210.52 (A)(B)needs outlet for wall space in new breakfast dinning area, 250.122 needs #12 pigtails not #14, 314.20 all boxes flush for 1/2 rock and outside boxes BCC all make up shall bo complete 7/1/2002 2:42:13 PM
Issue & PRINT permit  7/1/2002  
Application received  7/1/2002