Telephone Call | | | 10/21/2002 | | DONE |
|
|
|
|
Final | 9/12/2002 | 9/12/2002 | 9/12/2002 | P | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ok final 9/12/2002 1:46:50 PM
|
DOC - Permit Finaled | 9/12/2002 | 9/12/2002 | 9/12/2002 | P | PASS |
Mike Kinnear
|
|
|
Finaled by inspector at 9/12/2002 1:46:52 PM
|
Electrical Rough-In | 9/10/2002 | 9/10/2002 | 9/10/2002 | P | FAIL |
Mike Kinnear
|
|
|
suspended ceiling ###-#### tom correction NEC210.62 need 2 outlets for show windows 9/10/2002 2:17:53 PM
|
Electrical Rough-In | 8/16/2002 | 8/19/2002 | 8/19/2002 | A | PASS |
Mike Kinnear
|
|
|
###-#### ok cover walls & hard lid ceiling only 8/19/2002 9:41:43 AM
|
Permanent Service | 8/2/2002 | 8/6/2002 | 8/6/2002 | A | PASS |
Jack Frank
|
|
|
###-#### meter for space #106 ok 8/6/2002 11:26:48 AM
|
Permanent Service | 8/2/2002 | 8/2/2002 | 8/2/2002 | P | NH |
Jim Schmer
|
|
|
tom please call for access; Phone #: ###-#### called & left mssge 8/2/2002 1:51:16 PM
|
Permanent Service | 7/31/2002 | 8/1/2002 | 8/1/2002 | A | FAIL |
Jack Frank
|
|
|
###-#### cor. , do not cover, and $45.00 reinspection fee due posted called 300.4(A)(1)&(D) 330.30 strap MC 12 inches of boxes 358.30 strap emt 3ft of boxes, 314.20, 250.8 no SMS, 250.148 ues grd screws or clips 110.3(B) use manufactures listed buses at sub panel and service 8/1/2002 11:16:22 AM
|
Electrical Rough-In | 7/31/2002 | 7/31/2002 | 7/31/2002 | P | NH |
Mike Kinnear
|
|
|
PLEASE CALL FOR ACCESS ###-#### TOM called no access they to recall for inspection 7/31/2002 2:15:06 PM
|
Application received | | | 7/23/2002 | | |
|
|
|
|
Issue & PRINT permit | | | 7/23/2002 | | DONE |
|
|
|
|