Telephone Call | | | 3/13/2003 | | DONE |
|
|
|
|
Telephone Call | | | 3/13/2003 | | DONE |
|
|
|
|
DOC - Permit Finaled | 12/31/2002 | 12/31/2002 | 12/31/2002 | A | PASS |
Jack Frank
|
|
|
Finaled by inspector at 12/31/2002 11:02:13 AM
|
ELE-Aging Inspection | 12/31/2002 | 12/31/2002 | 12/31/2002 | | DONE |
Jack Frank
|
|
|
ok 12/31/2002 11:02:08 AM
|
DOC - Permit Finaled | 12/30/2002 | 12/30/2002 | 12/30/2002 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 12/30/2002 1:44:10 PM
|
ELE-Aging Inspection | 12/30/2002 | 12/30/2002 | 12/30/2002 | | PASS |
Jack Frank
|
|
|
stopped at job site final ok 12/30/2002 1:44:03 PM
|
Final | 10/28/2002 | 10/29/2002 | 10/29/2002 | P | FAIL |
Tim McCullough
|
|
|
Ready for corrections to be inspected.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
corrections: 110.12 & 110.12(A)M 10/30/2002 9:20:59 AM
|
Final | 10/15/2002 | 10/15/2002 | 10/15/2002 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/15/2002 at 11:27:54. Contact: ###-####. cor. not made still using light fixteres as raceways for recepts called 10/15/2002 6:33:16 PM
|
Final | 9/23/2002 | 9/25/2002 | 9/25/2002 | P | FAIL |
Jack Frank
|
|
|
call dan at ###-#### to meet you and show you what was done.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell 2 corrections posted 1 is for owner the other for mitchell, 410.31 outlet feeds passing through fixtures, 314.23 secure boxes to cooler bell boxes that are airmailed, 300.7 cooler conduits, 430.102(B) disconnects needed for fan ciol units in cooler 9/25/2002 6:38:29 PM
|
Application received | | | 9/6/2002 | | |
|
|
|
|
Issue & PRINT permit | | | 9/6/2002 | | |
|
|
|
|