PostCard Mailed | | | 10/1/2003 | | SENT |
|
|
|
PostCard has been mailed requesting inspection.
|
Permanent Service | 10/30/2002 | 10/30/2002 | 10/30/2002 | P | PASS |
Pat Lass
|
|
|
ren-- ###-#### cell--call 20 min before insp please ..re-insp
P/S O/H R Ok 10/30/2002 2:28:17 PM
|
Permanent Service | 10/11/2002 | 10/11/2002 | 10/11/2002 | P | CANC |
Jack Frank
|
|
|
Ren Gardner call first to meet there ; Phone #: ###-#### Internet Inspection Request from: Amy Lawson 10/11/2002 5:08:26 PM
|
Permanent Service | 10/11/2002 | 10/11/2002 | 10/11/2002 | P | FAIL |
Jack Frank
|
|
|
Ren Gardner call first to meet there ; Phone #: ###-#### Internet Inspection Request from: Amy Lawson cor. posted called 408.16(F) clip for backfed breaker sub panel 110.3(B) use manufactures listed breakers, 230. 24(A) shall provide 8 ft over roof if drop passes over foof, 250.52 (A)(1) shall run GEC too well casing 10/11/2002 4:46:33 PM
|
Final | 10/2/2002 | 10/2/2002 | 10/2/2002 | P | NR |
Pat Lass
|
|
|
needed it for this morning
|
Final | 10/2/2002 | 10/2/2002 | 10/2/2002 | A | FAIL |
Pat Lass
|
|
|
the whole sercice has to change
|
Final | 10/1/2002 | 10/1/2002 | 10/1/2002 | P | NH |
Pat Lass
|
|
|
for homeowner -ren; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
No access 10/1/2002 3:09:03 PM
|
Final | 9/16/2002 | 9/16/2002 | 9/16/2002 | P | FAIL |
Pat Lass
|
|
|
call ren to meet you there; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
service to be brought up to code. recommended he get contractor. 9/16/2002 5:04:19 PM
|
Application received | | | 9/10/2002 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 9/10/2002 | | DONE |
|
|
|
|