Final | 12/12/2002 | 12/12/2002 | 12/12/2002 | P | PASS |
Jack Frank
|
|
|
bill- ###-#### ok 12/12/2002 2:46:29 PM
|
DOC - Permit Finaled | 12/12/2002 | 12/12/2002 | 12/12/2002 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 12/12/2002 2:46:36 PM
|
Rough-In Permanent Service | 10/3/2002 | 10/3/2002 | 10/3/2002 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/03/2002 at 06:40:56. Contact: ###-####. ok
p/s u/g new ok 10/3/2002 12:43:37 PM
|
Rough-In Permanent Service | 10/1/2002 | 10/2/2002 | 10/2/2002 | A | FAIL |
Jack Frank
|
|
|
###-#### cor. posted called 334.30 romex stapled on edge, 314.20 boxes set at 1/4 inch or less should be set 1/2 inch 110.3(B) too many cables under one staple 10/2/2002 12:05:10 PM
|
Issue & PRINT permit | | | 10/1/2002 | | DONE |
|
|
|
|
Application received | | | 10/1/2002 | | |
|
|
|
|