Final | 1/24/2003 | 1/27/2003 | 1/27/2003 | A | PASS |
Jack Frank
|
|
|
trax elec monica--code for gar door is 0000; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok 1/27/2003 9:15:35 AM
|
DOC - Permit Finaled | 1/27/2003 | 1/27/2003 | 1/27/2003 | A | PASS |
Jack Frank
|
|
|
Finaled by inspector at 1/27/2003 9:15:39 AM
|
Rough-In Permanent Service | 10/18/2002 | 10/18/2002 | 10/18/2002 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/18/2002 at 07:31:24. Contact: ###-####. r/i ok 10/18/2002 10:33:14 AM
|
Rough-In Permanent Service | 10/17/2002 | 10/17/2002 | 10/17/2002 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/17/2002 at 08:48:32. Contact: ###-####. see added p/s corrections not made for r/i 10/17/2002 4:16:41 PM
|
Permanent Service | 10/17/2002 | 10/17/2002 | 10/17/2002 | P | PASS |
Jack Frank
|
|
|
p/s u/g new ok
|
Electrical Rough-In | 10/14/2002 | 10/16/2002 | 10/16/2002 | A | FAIL |
Jack Frank
|
|
|
###-#### late pm cor. posted met with contractor 314.43, 134.16, 210.52(A) 250.104 (A)(1) 314.17(A) replace all boxes with broken clamps 10/16/2002 12:02:20 PM
|
Rough-In Permanent Service | 10/16/2002 | 10/16/2002 | 10/16/2002 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/16/2002 at 10:59:38. Contact: ###-####. cor. posted $45.00 reinspection fee due called corrections not made and more violations created 314.43, 314.17(A) , broken clamps in 2,3,4,gang boxes 110.3(A) replace plastic boxes damaged by drilling holes in them 10/16/2002 6:16:12 PM
|
Application received | | | 10/2/2002 | | |
|
|
|
|
Issue & PRINT permit | | | 10/2/2002 | | |
|
|
|
|