Final | 2/4/2003 | 2/4/2003 | 2/4/2003 | P | PASS |
Jack Frank
|
|
|
###-#### jim access code 2003 garage house 2752 ok 2/4/2003 12:01:53 PM
|
DOC - Permit Finaled | 2/4/2003 | 2/4/2003 | 2/4/2003 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 2/4/2003 12:01:59 PM
|
Final | 1/31/2003 | 2/3/2003 | 2/3/2003 | A | FAIL |
Jack Frank
|
|
|
access code 2003 for garage house 2752 ; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung cor. posted called 334.15 protect MNB in island counter,also box fill 314.16, all outside recept wiring is messed up, 210.63, needs gfci outlet 25ft of a/c 2/3/2003 9:35:49 AM
|
Final | 1/30/2003 | 1/31/2003 | 1/31/2003 | A | FAIL |
Mike Kinnear
|
|
|
###-#### no access all furn shall be move out before inspection 42.00 re-inspection fee 1/31/2003 10:58:27 AM
|
Electrical Rough-In | 11/19/2002 | 11/20/2002 | 11/20/2002 | A | DONE |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 11/19/2002 at 14:25:58. Contact: ###-####. called contractor called in wrong permit number 11/20/2002 11:48:11 AM
|
Electrical Rough-In | 10/18/2002 | 10/21/2002 | 10/21/2002 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/18/2002 at 13:24:31. Contact: ###-####.
p/s u/g new ok 10/21/2002 10:44:59 AM
|
Electrical Rough-In | 10/15/2002 | 10/16/2002 | 10/16/2002 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/15/2002 at 14:12:42. Contact: ###-####. 314.16, 300.4(A)(1)and (D) 300.14, 110.14(B), 110.12(A) and314.17(A) replace boxes with unsed KOs and broken clamps 110.3(B) use approved tool for crimp sleeves
cor. posted called and $45.00 reinspection fee due 10/16/2002 12:56:11 PM
|
Electrical Rough-In | 10/10/2002 | 10/11/2002 | 10/11/2002 | A | NR |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 10/10/2002 at 09:47:57. Contact: ###-####. COW not ready boxes not installed 10/11/2002 9:02:23 AM
most every violation you can have 10/11/2002 9:03:27 AM
|
Application received | | | 10/4/2002 | | |
|
|
|
|
Issue & PRINT permit | | | 10/4/2002 | | DONE |
|
|
|
|