Temporary Service | 11/26/2002 | 11/27/2002 | 11/27/2002 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 11/26/2002 at 13:02:21. Contact: ###-####. ok t/s u/g new 11/27/2002 1:34:27 PM
|
DOC - Permit Finaled | 11/27/2002 | 11/27/2002 | 11/27/2002 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 11/27/2002 1:34:31 PM
|
Temporary Service | 11/25/2002 | 11/26/2002 | 11/26/2002 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 11/25/2002 at 14:48:50. Contact: ###-####. cor. posted called 310.12(C) & 250.119 shall not use green for phase conductors, 110.12(A) seal ko 11/26/2002 12:14:59 PM
|
Issue PAID IN FULL permit | | | 10/30/2002 | | DONE |
|
|
|
|
Application received | | | 10/8/2002 | | |
|
|
|
|
Telephone call | | | 10/8/2002 | | DONE |
|
|
|
left mess that permit is ready
|