Final | 12/2/2002 | 12/2/2002 | 12/2/2002 | P | PASS |
Pat Lass
|
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
DOC - Permit Finaled | 12/2/2002 | 12/2/2002 | 12/2/2002 | P | PASS |
Pat Lass
|
|
|
Finaled by inspector at 12/2/2002 3:36:29 PM
|
Electrical Rough-In | 10/21/2002 | 10/22/2002 | 10/22/2002 | A | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 10/21/2002 at 12:26:57. Contact: ###-####. ok cover ri p/s o/h n ok 10/22/2002 11:19:33 AM
|
Electrical Rough-In | 10/18/2002 | 10/18/2002 | 10/18/2002 | P | PART |
Mike Kinnear
|
|
|
###-#### conf with contractor 10/18/2002 1:26:57 PM
|
Electrical Rough-In | 10/17/2002 | 10/17/2002 | 10/17/2002 | P | FAIL |
Mike Kinnear
|
|
|
###-#### CHRIS same correction some fix but not all them
. reinspection fee $42.00 10/17/2002 1:34:03 PM
|
Electrical Rough-In | 10/15/2002 | 10/15/2002 | 10/15/2002 | P | FAIL |
Mike Kinnear
|
|
|
###-#### bcc all make up shall be complete at ri, bcc o/h service shall have u-bolt or guy kit nec 250.148, 300.14, 300.4, 250.148 110-3(B) romex connector proper size, 314.16. 10/15/2002 3:09:32 PM
|
Rough-In Permanent Service | 10/9/2002 | 10/10/2002 | 10/10/2002 | A | FAIL |
Pat Lass
|
|
|
###-####
250.148 Continuity and Attachment of Equipment Grounding Conductors to Boxes.
314.16 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies.
Boxes and conduit bodies shall be of sufficient size to provide free space for all enclosed conductors.
300.14 Length of Free Conductors at Outlets, Junctions, and Switch Points.
At least 150 mm (6 in.) of free conductor,
300.4 Protection Against Physical Damage.
Where subject to physical damage, conductors shall be adequately protected.
230.2 Number of Services.
A building or other structure served shall be supplied by only one service
10/10/2002 9:25:54 AM
|
Issue & PRINT permit | | | 10/9/2002 | | DONE |
|
|
|
|
Application received | | | 10/9/2002 | | |
|
|
|
|