Permit Information
Permit NumberELE02-03169
StatusFinaled
Name RICHARD FRITZLEY
Site Address 3807 N HAWTHORNE DR
Project Name 
Customer Number 
ePlanReview 
Description
received warranty deed from records #101041916 /richard fritzley is the parcel owner/on 10/17/02/mls
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/20/20034/21/20034/21/2003APASS
DetailsPat Lass
Pat,
Have made following corretions per your last inspection: (1) Box extenders on outlets that pentrated through flammable material - this was for the microwave and the hallway; (2) GFI rescepticle for jetted tub in master bathroom; (3) Adjusted outlets that had excessive gaps; (4) enclosed wires in dining nook in metal box until bench seat is built; (5) extended outlet in basement on pegboard through pegboard so cover was accessible. Think that was everything. I have a dental appointment at 8:00 am but should be available by 9:00 AM. Will leave door unlocked if you need to go earlier. Thanks.; Phone #: ###-#### Internet Inspection Request from: Richard Fritzley
DOC - Permit Finaled4/21/20034/21/20034/21/2003APASS
DetailsPat Lass
Finaled by inspector at 4/21/2003 8:52:53 AM
Final4/14/20034/14/20034/14/2003PFAIL
DetailsPat Lass
###-#### early pm call first
recep position in faceplates, GFCI hydromassage tub, metal box for open wires,
add recep for pump 4/14/2003 1:34:15 PM
Extend Permit 180 days 4/14/20034/14/2003 DONE
DetailsPat Lass
ok per Jim Schmer
Electrical Rough-In12/2/200212/2/200212/2/2002APASS
DetailsPat Lass
Pat,
Ready for rough-in. Please call the number listed at least 20 minutes in advance so I can be at the site for the inspection. Thanks.; Phone #: ###-#### Internet Inspection Request from: Richard Fritzley
PostCard Mailed  11/1/2002 SENT
PostCard has been mailed requesting inspection.
Rough-In Permanent Service10/31/200210/31/200210/31/2002APASS
DetailsTim McCullough
Pat,
I have changed out the ground wire on the second 200 amp disconnect from #6 to #4 as you directed, so the service entrance is ready for inspection.; Phone #: ###-#### Internet Inspection Request from: Richard Fritzley

ps/ok/ug/new 10/31/2002 1:21:36 PM
Rough-In Permanent Service10/24/200210/25/200210/25/2002AFAIL
DetailsPat Lass
Scheduled by a contractor via Hello! on 10/24/2002 at 11:43:47. Contact: ###-####.Undersized GEC to 200a disconnect 10/25/2002 9:41:19 AM
Rough-In Permanent Service10/16/200210/17/200210/17/2002APART
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 10/16/2002 at 15:05:48. Contact: ###-####. conf 10/17/2002 12:21:11 PM
Electrical Rough-In10/13/200210/14/200210/14/2002ANR
DetailsPat Lass
Scheduled by a contractor via Hello! on 10/13/2002 at 22:10:42. Contact: ###-####.
conf only 10/14/2002 9:46:02 AM
Application received  10/11/2002  
Issue PAID IN FULL permit  10/11/2002