PostCard Mailed | | | 10/1/2003 | | SENT |
|
|
|
PostCard has been mailed requesting inspection.
|
PostCard Mailed | | | 5/10/2003 | | SENT |
|
|
|
PostCard has been mailed requesting inspection.
|
Electrical Rough-In | 10/21/2002 | 10/21/2002 | 10/21/2002 | P | FAIL |
Pat Lass
|
|
|
###-#### MARK
250.148 Continuity and Attachment of Equipment Grounding Conductors to Boxes.
Where circuit conductors are spliced within a box, or terminated on equipment within or supported by a box, any separate equipment grounding conductors associated with those circuit conductors shall be spliced or joined within the box
314.43 Nonmetallic Boxes.
Provisions for supports or other mounting means for nonmetallic boxes shall be outside of the box
300.4 Protection Against Physical Damage.
Where subject to physical damage, conductors shall be adequately protected.
(D) Cables and Raceways Parallel to Framing Members.
300.14 Length of Free Conductors at Outlets, Junctions, and Switch Points.
At least 150 mm (6 in.) of free conductor
314.16 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies.
Boxes and conduit bodies shall be of sufficient size to provide free space for all enclosed conductors.
10/21/2002 3:42:10 PM
|
Electrical Rough-In | 10/21/2002 | 10/21/2002 | 10/21/2002 | P | PASS |
Jim Schmer
|
|
|
|
Electrical Rough-In | 10/17/2002 | 10/18/2002 | 10/18/2002 | A | FAIL |
Mike Kinnear
|
|
|
###-#### corrections NEC210.52(A)(1)&(2)--300.4(D) 10/18/2002 11:08:38 AM
|
Application received | | | 10/14/2002 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 10/14/2002 | | DONE |
|
|
|
|