Final | 11/6/2002 | 11/7/2002 | 11/7/2002 | P | PASS |
Jack Frank
|
|
|
dan; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok 11/7/2002 3:41:31 PM
|
Permanent Service | 11/7/2002 | 11/7/2002 | 11/7/2002 | P | PASS |
Jack Frank
|
|
|
p/s o/h rec. ok
|
DOC - Permit Finaled | 11/7/2002 | 11/7/2002 | 11/7/2002 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 11/7/2002 3:45:27 PM
|
Permanent Service | 10/23/2002 | 10/25/2002 | 10/25/2002 | A | FAIL |
Jack Frank
|
|
|
###-#### owner is checking with city if she can have 2 meters for duplex, or apartment correction posted for contractor called 250.52,104 grd or bond water 250.66 needs # 4 to water, 314.16 box fill 4SQ boxes attic, 334.15 protect cables sub panel garage, 250.142(B) needs 4 wire to range from sub panel 10/25/2002 11:41:58 AM
|
Issue & PRINT permit | | | 10/23/2002 | | DONE |
|
|
|
|
Application received | | | 10/23/2002 | | |
|
|
|
|