Temporary Service | 11/7/2002 | 11/7/2002 | 11/7/2002 | P | PASS |
Jack Frank
|
|
|
###-#### RON
t/s u/g new ok 11/7/2002 3:25:35 PM
|
DOC - Permit Finaled | 11/7/2002 | 11/7/2002 | 11/7/2002 | P | PASS |
Jack Frank
|
|
|
Finaled by inspector at 11/7/2002 3:25:54 PM
|
Temporary Service | 11/5/2002 | 11/6/2002 | 11/6/2002 | A | FAIL |
Pat Lass
|
|
|
t/p ron ###-####
408.21 Grounded Conductor Terminations.
Each grounded conductor shall terminate within the panelboard in an individual terminal that is not also used for another conductor.
110.12 Mechanical Execution of Work.
(C) Integrity of Electrical Equipment and Connections. Internal parts of electrical equipment, including busbars, wiring terminals, insulators, and other surfaces, shall not be damaged or contaminated by foreign materials such as paint, plaster, cleaners, abrasives, or corrosive residues.
11/6/2002 8:59:55 AM
|
Issue & PRINT permit | | | 11/5/2002 | | |
|
|
|
|
Application received | | | 11/5/2002 | | |
|
|
|
|