Final | 2/10/2003 | 2/11/2003 | 2/11/2003 | A | PASS |
Jack Frank
|
|
|
###-#### kevin ok 2/11/2003 11:06:16 AM
|
DOC - Permit Finaled | 2/11/2003 | 2/11/2003 | 2/11/2003 | A | PASS |
Jack Frank
|
|
|
Finaled by inspector at 2/11/2003 11:06:20 AM
|
Final | 11/15/2002 | 11/18/2002 | 11/18/2002 | A | PASS |
Jack Frank
|
|
|
kevin ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok
p/s u/g new ok 11/18/2002 1:09:39 PM
|
Rough-In Permanent Service | 11/14/2002 | 11/14/2002 | 11/14/2002 | P | FAIL |
Jack Frank
|
|
|
###-#### KEVIN cor. posted met with contractor 210.52 (A&B) outlet for wall spce over 6ft NE upstairs bedrm, and remove light fixture from small appliance circuit in din. rm replace 2 gang boxes with broken clamps 314.20 outside boxes shall be flush with siding, 250.6and 200.7 shall not use 2 wire romex for 3and 4 ways 11/14/2002 3:44:23 PM
|
Issue & PRINT permit | | | 11/14/2002 | | DONE |
|
|
|
|
Application received | | | 11/14/2002 | | |
|
|
|
|