Final | 4/23/2003 | 4/24/2003 | 4/24/2003 | P | PART |
Tim McCullough
|
|
|
Scheduled by a contractor via Hello! on 4/23/2003 at 4:58:14 PM. Contact: ###-####.
f 4/24/2003 1:16:36 PM inal/ok 4/24/2003 1:16:44 PM
|
DOC - Permit Finaled | 4/24/2003 | 4/24/2003 | 4/24/2003 | P | PASS |
Tim McCullough
|
|
|
Finaled by inspector at 4/24/2003 1:16:46 PM
|
Electrical Rough-In | 2/12/2003 | 2/13/2003 | 2/13/2003 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 02/12/2003 at 13:11:28. Contact: ###-####. cor. made r/i ok
p/s u/g new ok 2/13/2003 2:36:28 PM
|
Electrical Rough-In | 1/23/2003 | 1/24/2003 | 1/24/2003 | P | FAIL |
Jack Frank
|
|
|
dennis-homeowner-call 1st before insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie cor. posted met owner COW, 110.3,110.12(A) plastic boxes, 210.11, all of 210.52, 300.4, 300.14, 410.8, 310.16 wise size p/s, all of 334, 250.148 tie all grds at boxes together,, 250.28 install bond screw, 250.104 bond water, all wiring shall be complete high and low voltage, 314.16 box fill 1/24/2003 3:15:11 PM
|
Application received | | | 11/22/2002 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 11/22/2002 | | DONE |
|
|
|
|