PostCard Mailed | | | 12/10/2003 | | SENT |
|
|
|
PostCard has been mailed requesting inspection.
|
VOIDED CHANGE STATUS | | | 12/20/2002 | | DONE |
|
|
|
didn't pass inspection per Jim s
|
Permanent Service | 12/17/2002 | 12/17/2002 | 12/17/2002 | P | FAIL |
Jack Frank
|
|
|
CALL FIRST ###-#### SCOTT , THIS PERMIT HAS BEEN APPROVED THROUGH TIM AND JENNIFER corrections posted met with owner, 11.26 (A)(1&2)230.6, 230.24(A), 230.28 needs 2" rigid or IMC, and guy kit, 230.72 group service disconnects, 250.90 bond nipple at p/s, 250.52 grd within 5 ft for u/g water pipe, 250.53 needs 2 grd rods, 110.3(B) install only 1 wire under screws at terminals, 312.5(A&C) needs con. for range cable and no exposed range wires allowed in wall 12/17/2002 5:46:27 PM
|
Application received | | | 12/17/2002 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 12/17/2002 | | DONE |
|
|
|
|