DOC - Permit Finaled | | | 4/3/2003 | | DONE |
|
|
|
|
Final | 3/17/2003 | 3/17/2003 | 3/17/2003 | P | PASS |
Jack Frank
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok card signed 3/17/2003 3:50:15 PM
|
Final | 3/13/2003 | 3/14/2003 | 3/14/2003 | A | FAIL |
Pat Lass
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Annette Moore
GFCI outside front 3/14/2003 11:15:12 AM
|
Electrical Rough-In | 1/24/2003 | 1/24/2003 | 1/24/2003 | P | PASS |
Jack Frank
|
|
|
john--re-insp; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie r/i ok
p/s u/g rec. ok 1/24/2003 2:11:29 PM
|
Electrical Rough-In | 1/24/2003 | 1/24/2003 | 1/24/2003 | P | PASS |
Jack Frank
|
|
|
john--re-insp; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie r/i ok
p/s u/g rec. ok 1/24/2003 2:11:29 PM
|
Rough-In Permanent Service | 1/23/2003 | 1/23/2003 | 1/23/2003 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung cor. posted called 210.52(A&B) outspacin liv rm, and outlet required for wall in din rm 210.70 light for back entries outside, 110.26(A)(2) shall provide 30 inches width for panels only has 28inches, 250.50, 52,104, needs 2 grd rod , grd or bond water system 1/23/2003 2:13:52 PM
|
Rough-In Permanent Service | 1/22/2003 | 1/22/2003 | 1/22/2003 | P | FAIL |
Joe Ray
|
|
|
JOHN; Phone #: ###-#### Internet Inspection Request from: Darla Downs no access/doors locked/left note 1/22/2003 2:51:14 PM
|
Application received | | | 1/22/2003 | | |
|
|
|
|
Issue & PRINT permit | | | 1/22/2003 | | DONE |
|
|
|
|