Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE03-00245
StatusFinaled
Name PRECISION PUMPING SYSTEMS
Site Address 1001 N AMERICANA BLVD
Project NameKATHRYN ALBERTSON PARK
Customer Number 
ePlanReview 
Description
1/28/03//KATHRYN ALBERTSON PARK/CITY OF BOISE PARK & REC/INSTALL PUMP STATION & MAIN DISCONNECT ADJACENT TO PARKING LOT/INITIAL CERT OF VALUE $3,050/MLS 12-1-03 no additional value///dld
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Second Notice ELE11/3/200311/3/200312/1/2003 DONE
First Notice has not been responded to.
First Notice Sent 10/20/200311/3/2003 DONE
DOC - Permit Finaled10/20/200310/20/200310/20/2003PPASS
DetailsJack Frank
Finaled by inspector at 10/20/2003 1:54:00 PM
Final10/20/200310/20/200310/20/2003PPASS
DetailsJack Frank
TOM; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok 10/20/2003 1:53:55 PM
Final10/3/200310/3/200310/3/2003PCANC
DetailsJack Frank
tom; Phone #: ###-#### Internet Inspection Request from: Annette Moore see added r/i conference 10/3/2003 2:48:24 PM
Electrical Rough-In10/3/200310/3/200310/3/2003PPART
DetailsJack Frank
conference ok met with contractor
Final10/1/200310/2/200310/2/2003 FAIL
DetailsJack Frank
###-#### TOM cor. posted called grd or bond, and install n2 grd rods for p/s at pump house, needs neutral to p/s 250.24(B),, 300.4, 356.30 &348.30 strap sealtight and flex 10/2/2003 10:13:32 AM
ELE-Aging Inspection9/24/20039/24/20039/24/2003 NH
DetailsJack Frank
called no access contractor will call for inspection with combonation too lock so I can inspect 9/30/2003 1:48:33 PM
ELE-Aging Inspection4/29/20034/29/20034/29/2003 CANC
DetailsTim McCullough

work in progress .not ready 4/29/2003 3:41:05 PM
Application received  1/28/2003  
Issue & PRINT permit  1/28/2003