Second Notification | 5/8/2003 | 5/8/2003 | 5/28/2003 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | | 3/21/2003 | 5/8/2003 | | DONE |
|
|
|
|
DOC - Permit Finaled | 3/21/2003 | 3/21/2003 | 3/21/2003 | A | PASS |
Joe Ray
|
|
|
Finaled by inspector at 3/21/2003 11:11:29 AM
|
Final | 3/20/2003 | 3/21/2003 | 3/21/2003 | A | PASS |
Joe Ray
|
|
|
CORRECTIONS MADE- PLEASE RE-INSPECT. THANKS TERESA; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
|
Final | 3/18/2003 | 3/19/2003 | 3/19/2003 | A | FAIL |
Jack Frank
|
|
|
Ran a new 60amp ckt.in new 3/4" conduit for new receptacle.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell cor. posted called 250.146,148 shall grd 4sq box at recept, 358.30 strap 3/4 emt by panel 3/19/2003 10:40:23 AM
|
Application received | | | 3/17/2003 | | |
|
|
|
|
Issue & PRINT permit | | | 3/17/2003 | | DONE |
|
|
|
|